
Hampton
®
H35 Direct Vent Freestanding Gas Stove
7
INSTALLATION
GENERAL SAFETY
INFORMATION
1)
The
appliance
installation
must
conform
with
local Canadian Electrical Code.
2)
The appliance when installed, must be
electrically grounded in accordance with
local codes, or in the absence of local codes
with the current National Electrical Code,
ANSI/NFPA 70 or CSA C22.1 Canadian
Electrical Code.
3)
The appliance should be inspected for
shipping damage before use and
serv-
iced annually by a professional service
person
. More frequent cleaning may be
required due to excessive lint from carpet-
ing, bedding material, etc. It is imperative
that control compartments, and circulating
air passageways of the appliance be kept
clean and free from excessive lint from
carpeting.
4)
See general construction and assembly
instructions. The appliance and vent should
be enclosed when installed in or passing
through a living area, where children may
come in contact with it.
5)
This appliance must be connected to the
specifi ed vent and termination cap to the
outside of the building envelope.
Never
vent to another room or inside a building.
Make sure that the vent is fi tted as per the
instructions starting in the "Exterior Vent
Terminal Locations" section.
6)
Inspect the venting system annually for
blockage and any signs of deterioration.
7)
Venting terminals shall not be recessed into
a wall or siding.
8)
Any safety glass removed for servicing
must be replaced prior to operating the ap-
pliance.
9)
To prevent injury, do not allow anyone who
is unfamiliar with the operation to use the
fi replace.
INSTALLATION
CHECKLIST
1)
Locate your appliance. Refer to the following
sections:
a.
Clearances
to
combustibles
b. Locating Your Gas Stove
c. For venting requirements, see "Venting
Introduction" to "Venting Arrangements"
sections.
2)
Install Optional Fan. Refer to the "Optional
Fan Installation" section.
3)
Set vent restrictors. Refer to the "Vent Re-
strictor Position" section.
4)
Install venting. Refer to the following sections
where applicable:
a. Check all venting requirements.
See "Venting Introduction" to "Venting
Arrangements" sections.
b. Vertical Termination with Co-linear Flex
System
c. DV Stove Horizontal Vent Kit
d.
Dura-Vent
Termination
Kit.
5)
Make gas connections. Refer to the "Gas
Connection" section
Test the pilot. Must be as per diagram in the
"Maintenance Instruction" section.
If converting to Propane, make changes
prior see the "Conversion from Natrual Gas
to Propane" section.
6)
Test Gas Pressure. Refer to the "Gas Pipe
Pressure Testing" section.
7)
Install standard and optional features. Refer
to the following sections where applicable:
a. Log Set Installation
b.
Double
Door
Installation
c.
Decorative
Door
Grill
Installation
d. Tile Inset Installation
e.
Wall
Thermostat
f.
Remote
Control
8)
Final check. Refer to the "Final Check" sec-
tion.
Before leaving this unit with the customer,
the installer must ensure that the appli-
ance is fi ring correctly and
operation fully
explained to customer
.
This includes:
1)
Clocking the appliance to ensure the correct
fi ring rate (rate noted on label) after burning
appliance for 15 minutes.
2)
If required, adjusting the primary air to ensure
that the fl ame does not carbon. First allow
the unit to burn for 15-20 min. to stabilize.
CAUTION: Any alteration to the product that
causes sooting or carboning that results
in damage is not the responsibility of the
manufacturer.
CLEARANCES TO
COMBUSTIBLES
The clearances listed are MINIMUM distances.
Measure the clearance to both the appliance
and the chimney connector.
The farthest
distance is correct if the two clearances do
not coincide.
For example, if the appliance is set as indicated
in one of the fi gures but the connector is too
close, move the stove until the correct clearance
to the connector is obtained.
This appliance may be installed only with the
clearances as shown in the situations pictured.
Do not combine clearances from one type of
installation with another in order to achieve
closer clearances.
This unit can be installed on a solid combustible
surface like a wood fl oor. This unit can also be
installed directly on carpeting or vinyl.
Use the minimum clearances shown in the
diagrams below:
H35-NG1 & H35-LP1 Clearances
A Side Wall to Unit
6-1/2" / 165 mm
B Back Wall to Unit
6" / 152 mm
C Vertical Vent Pipe to Back Wall
2" / 50 mm
E Unit Corner to Wall
2" / 50 mm
Unit Top to Alcove Ceiling 36" / 914 mm
Minimum ceiling height is 36" /914 mm from
top of unit.
Emissions from burning wood or gas could
contain chemicals known to the State of Cali-
fornia to cause cancer, birth defects or other
reproductive harm.