![Hamilton Sundstrand Company Gas Fuel Metering Valve HFG2.0 Скачать руководство пользователя страница 63](http://html1.mh-extra.com/html/hamilton-sundstrand-company/gas-fuel-metering-valve-hfg2-0/gas-fuel-metering-valve-hfg2-0_user-manual_3425095063.webp)
Symptom
Probable Causes
Corrective Action
RS232 Interface Inoperative Incorrect wiring
No or low 120 VDC power
COM1 not connected
RESET or RUN command is
ON
Ensure WHITE/ORANGE/YELLOW,
WHITE/ORANGE/BLUE, WHITE/ORANGE/GREEN
wires correctly connected to valve and laptop PC.
Ensure 120 VDC Primary System Power at Valve
Check laptop/PC com port
Remove RESET or RUN command
Table 5-1. Initial Installation Troubleshooting Chart
Symptom
Probable Causes
Corrective Action
No valve feedback
No or low 120 VDC power
Self-protective valve auto shut
down
Ensure 120 VDC at valve
Upload Fault File- check for motor windings over -
temperature faults.
Check for valve contamination
FAULT alarm
Various
Upload Fault File to identify source of fault
Clear indicated fault
OVER TEMP alarm
Ambient temperature limit
exceeded
Electronics or motor winding
temperature out of range
Allow actuator to cool and re-start
Reduce ambient temperature
Check for valve contamination
FAULT and OVERTEMP
alarm
No 120 VDC Power
DSP Failure
Ensure 120 VDC at actuator
Contact factory
Table 5-2. HFG2.0 In-Service Troubleshooting Chart
For troubleshooting purposes, use Table 5-3 to verify the valve electrical
continuity integrity.
Disconnect the HFG2.0 power and digital harness connectors and use a
digital multi-meter (DMM) to check the resistance values between the
wires indicated on the table. If an open circuit is detected, send the
HFG2.0 to Precision Engine Controls Corporation for test and repair.
WARNING – Shock Hazard
Remove all power to the HFG2.0 prior to continuity check.
CH. 4: TROUBLESHOOTING THE HFG2.0
57
Содержание Gas Fuel Metering Valve HFG2.0
Страница 15: ...Figure 1 4 HFG2 0 Dimensions 1 Piece Housing INSTALLING THE HFG2 0 9...
Страница 16: ...10 HFG2 0 USER GUIDE Figure 1 5 HFG2 0 Mounting Orientations...
Страница 18: ...12 HFG2 0 USER GUIDE Figure 1 7 HFG2 0 Mounting Provisions 1 Piece Housing Standard Mounting Orientation Shown...
Страница 30: ...24 HFG2 0 USER GUIDE INTENTIONALLY BLANK...
Страница 34: ...28 HFG2 0 USER GUIDE Figure 2 1 HFG2 0 Electronics System Block Diagram...
Страница 40: ...34 HFG2 0 USER GUIDE Figure 2 2 HFG2 0 Cut Away View Actuator Main Housing Assembly...
Страница 41: ...Figure 2 3 HFG2 0 Cut Away View Partial CH 2 UNDERSTANDING THE HFG2 0 35...
Страница 43: ...Figure 2 5 Typical Refurbishment Plate CH 2 UNDERSTANDING THE HFG2 0 37...
Страница 44: ...38 HFG2 0 USER GUIDE INTENTIONALLY BLANK...
Страница 47: ...Figure 3 1 HFG2 0 Basic Operation Flow Chart CH 3 OPERATING THE HFG2 0 41...
Страница 58: ...52 HFG2 0 USER GUIDE INTENTIONALLY BLANK...
Страница 60: ...54 HFG2 0 USER GUIDE INTENTIONALLY BLANK...
Страница 68: ...62 HFG2 0 USER GUIDE INTENTIONALLY BLANK...
Страница 70: ...INTENTIONALLY BLANK 64 HFG2 0 USER GUIDE...