Function

The central unit can be modularly extended with Halton Safe Linki control units, to which the fire

dampers and smoke detectors are connected. You can connect 1–4 fire dampers and 1–4 smoke

detectors to one SAFE LINK control unit. The unit’s internal control logic is used in their

management.

Fire dampers and smoke detectors can be clustered into as many as 15 groups, enabling the

system to respond to a fire alarm by closing only those fire dampers that are in the affected fire

compartment. Each fire damper or SAFE LINK control unit can also be set to function as an

independent group.

The fire dampers can be automatically tested weekly, at a time specified by the user. The system

creates a report on the tests carried out, indicating the functionality of each fire damper. The

system is used with a 5.7″ graphical touchscreen, through which all necessary user operations can

be performed. The system can be equipped with an optional 3G remote connection that makes all

of the touchscreen’s functions available via a Web browser.

In the event of a power cut or a fault in the Halton Safe central unit, the Halton Safe Link control

units operate independently. If a Halton Safe Link control unit loses its 24 VAC operating voltage

because of a fire or a power cut, the fire dampers are closed by a spring. It is also possible to

connect a backup battery to the central unit, so that the system can relay alarms even in the event

of a power cut. The operating voltage of the Halton Safe control centre is 230 VAC.

8

Содержание HSM

Страница 1: ...arm input Enables time controlled external or manual testing of fire damper operation It produces reports on the operation test The Halton Safe HSM shuts off the fans during test operation and in a fi...

Страница 2: ...internal control logic is used in their management Fire dampers and smoke detectors can be clustered into as many as 15 groups enabling the system to respond to a fire alarm by closing only those fire...

Страница 3: ...Dimensions 3...

Страница 4: ...erial Finishing Note Halton Safe HSM Plastic White IP40 Power supply 230VAC 5 7 touchscreen Halton Safe Link HSL Plastic White IP55 polystyrene casing UL94V 0 IEC 695 2 1 Halton Safe Power HSP Plastic...

Страница 5: ...onnect 1 4 fire dampers and 1 4 smoke detectors to one Halton Safe Link control unit Halton Safe Power HSP System allowing you to connect up to six Halton Safe Link HSL control units to a transformer...

Страница 6: ...Smoke bottle Assembly stand for a duct smoke detector 6...

Страница 7: ...Smoke detector duct installation Smoke detector ceiling installation 7...

Страница 8: ...specified by the user The system creates a report on the tests carried out indicating the functionality of each fire damper The system is used with a 5 7 graphical touchscreen through which all neces...

Страница 9: ...e cabinet The central unit features a 5 7 touchscreen attached to the front panel of the control centre cabinet The control centre can also be installed on top of the I O unit or next to it If necessa...

Страница 10: ...tor s contamination passes a certain threshold The alarm does not close the fire dampers Alarm This closes those fire dampers in the smoke detector s use group Short Cut This means that there is a sho...

Страница 11: ...s additional service to the Commissioning package Package 2 The Client connects the power cable attaches Halton Link according to the designs and does wiring for the system components Damper locations...

Страница 12: ...cut or a fault in the Halton Safe central unit the Halton Safe Linkcontrol units operate independently If a Halton Safe Link control unit loses its 24 VAC operating voltage because of a fire or a powe...

Страница 13: ...R Smoke detector room Calectro ST P DA S Test smoke aerosol Calectro RDP 300 ZT Tailored product ETO N No Y Yes Code example HSM D ZT N 13...

Отзывы: