Product models and accessories
• The central unit of Halton Safe HSM control centre can be modularly extended with Halton
Safe Link control units (HSL), to which the fire dampers and smoke detectors are connected.
You can connect 1–4 fire dampers and 1–4 smoke detectors to one Safe Link control unit.
Optionally You can order a special version of Safe Link that can connect 1-12 smoke
detectors but zero fire dampers. The unit’s internal control logic is used in their management.
Fire dampers and smoke detectors can be clustered into as many as 15 groups, enabling the
system to respond to a fire alarm by closing only those fire dampers that are in the affected
fire compartment.
• You can connect up to six Halton Safe Link (HSL) control units to a Halton Safe Power (HSP)
24 V unit.
• You can add a battery pack for the power failure operational in the main control unit.
• The system can be equipped with an optional 3G remote connection that makes all of the
touchscreen’s functions available via a Web browser.
• Smoke detectors for duct or room installation
2