Halton HSM Скачать руководство пользователя страница 5

Accessories

Model /

Accessory

Code

Description

Note

Halton Safe,

control centre

HSM

A control centre to which

you can connect up to 50

Halton Safe Link control units.

The operating voltage

is 230 VAC

Halton Safe,

Link

HSL

Extension of the Halton Safe

control centre modularly with

Halton Safe Link control units,

to which the fire dampers

and smoke detectors are

connected.

You can connect

1–4 fire dampers and

1–4 smoke detectors to one

Halton Safe Link control unit.

Halton Safe,

Power

HSP

System allowing you to connect

up to six Halton Safe Link (HSL)

control units to a transformer

24 VAC

Optical

smoke

detector

HSM/D Model with connection

to ductwork

Calectro UG-3-O

IP54

Optical

smoke

detector

HSM/R

A model for

room installation

Calectro ST-P-DA

IP54

Aerosol

HSM/S

Container for smoke test

Calectro RDP-300

Smoke detectors for duct installation are delivered complete with installation base for round and

insulated ductwork and with 600-mm Venturi tube.

5

Содержание HSM

Страница 1: ...arm input Enables time controlled external or manual testing of fire damper operation It produces reports on the operation test The Halton Safe HSM shuts off the fans during test operation and in a fi...

Страница 2: ...internal control logic is used in their management Fire dampers and smoke detectors can be clustered into as many as 15 groups enabling the system to respond to a fire alarm by closing only those fire...

Страница 3: ...Dimensions 3...

Страница 4: ...erial Finishing Note Halton Safe HSM Plastic White IP40 Power supply 230VAC 5 7 touchscreen Halton Safe Link HSL Plastic White IP55 polystyrene casing UL94V 0 IEC 695 2 1 Halton Safe Power HSP Plastic...

Страница 5: ...onnect 1 4 fire dampers and 1 4 smoke detectors to one Halton Safe Link control unit Halton Safe Power HSP System allowing you to connect up to six Halton Safe Link HSL control units to a transformer...

Страница 6: ...Smoke bottle Assembly stand for a duct smoke detector 6...

Страница 7: ...Smoke detector duct installation Smoke detector ceiling installation 7...

Страница 8: ...specified by the user The system creates a report on the tests carried out indicating the functionality of each fire damper The system is used with a 5 7 graphical touchscreen through which all neces...

Страница 9: ...e cabinet The central unit features a 5 7 touchscreen attached to the front panel of the control centre cabinet The control centre can also be installed on top of the I O unit or next to it If necessa...

Страница 10: ...tor s contamination passes a certain threshold The alarm does not close the fire dampers Alarm This closes those fire dampers in the smoke detector s use group Short Cut This means that there is a sho...

Страница 11: ...s additional service to the Commissioning package Package 2 The Client connects the power cable attaches Halton Link according to the designs and does wiring for the system components Damper locations...

Страница 12: ...cut or a fault in the Halton Safe central unit the Halton Safe Linkcontrol units operate independently If a Halton Safe Link control unit loses its 24 VAC operating voltage because of a fire or a powe...

Страница 13: ...R Smoke detector room Calectro ST P DA S Test smoke aerosol Calectro RDP 300 ZT Tailored product ETO N No Y Yes Code example HSM D ZT N 13...