background image

6

ECOVENT Operating Instructions

ECO

V/1

120

12/re

v1/EN

Section 1 – Installation

1.5 Commissioning

 

Information:   

1.5.1. Sequence of Operation. If all of the services have been

 

 

 

 

connected correctly, the sequence of operation is as follows.

 

 

 

 

Green illuminated on-off toggle switch will turn condensate hood

 

 

 

 

power on. At this time the fan will run at low speech (Idle). When

 

 

 

 

the door of the oven is opened, the magnetic reed switch triggers

 

 

 

 

the fan to increase in speed, and a cold water mist to be produced.

 

 

 

 

This will run for 24 seconds (factory setting) before returning to idle.

 

 

 

 

Closing the door will also return the condensate hood to idle.

 

Instruction:    

1.5.2. Prior to running the condensate hood for the first time, ensure

 

 

 

 

that both the mesh moisture eliminator (5) and baffle filters (6) are

 

 

 

 

fitted. Ensure all services and drains have been connected as

 

 

 

 

described in section 1.4 and oven is switched off.

 

 

 

 

1.5.3. Turn power on via toggle switch. Fan will run. Open oven

 

 

 

 

door to confirm activation of reed switch and allow to run for the

 

 

 

 

full 24 seconds. (Until the water stops automatically.) Open and

 

 

 

 

close the door twice more (and run for the full 24 seconds), to

 

 

 

 

allow the weir in the base of the condensate hood to fill. The

 

 

 

 

condensate hood is now ready for use.

Содержание ECOV-10

Страница 1: ...ECOVENT Condensate Hoods Model ECOV 10 ECOV 20 ECOV 30 ECOV 40 ECOVENT Condensate Hoods Operators Instructions...

Страница 2: ...to Oven 4 1 3 Fitting Door Magnet 4 1 4 Connection to Services 5 1 5 Commissioning 6 Section 2 Operation 2 1 Safety 7 2 2 Regular Operation 7 2 3 Cleaning and Maintenance 8 Section 3 Technical and Pe...

Страница 3: ...N Section 1 Installation Identification of Parts 1 Outer Casing 2 Top Shell 3 Bottom Shell 4 Cassette 5 Mesh Moisture Eliminator 6 Baffle Filter 7 Back Plate 8 Fixing Bracket 9 Nylon Branch 10 Flexibl...

Страница 4: ...e roof panel in place Screw the fixing bracket 8 into position using the holes provided 1 2 2 Remove the nuts from the two locating studs fitted to the bottom rear of the condensate hood Safety 1 2 3...

Страница 5: ...d a 120 volt single phase electrical supply Instruction 1 4 1 Cold Water Supply Fit the nylon Y branch 9 to the inlet connection on the underside of the oven Onto this flexible hose 10 is to be fitted...

Страница 6: ...ds factory setting before returning to idle Closing the door will also return the condensate hood to idle Instruction 1 5 2 Prior to running the condensate hood for the first time ensure that both the...

Страница 7: ...part of a condensate hood presents itself as a possible fire hazard Ensure baffle filters are cleaned regularly and while they are removed clean internal areas that are accessible 2 1 8 Damage due to...

Страница 8: ...ce suggests 2 3 6 The cold water mist nozzles should be checked for operating and the apertures cleaned with fine wire when required 2 3 7 To remove baffle filters lift and swing bottom away from you...

Страница 9: ...CFM Cold Water Supply Always 40PSI Weigth ECOV 10 lbs ECOV 20 lbs ECOV 30 lbs ECOV 40 lbs Construction Material 18 ga stainless steel ECOV 10 Electrolux Oven air o convect 62 102 Model PNC 269281 PNC...

Страница 10: ...holidays Travel time service charges miscellaneous tools material charges and labor charges resulting from inaccessibility of equipment will not be paid by Manufacturer This LIMITED WARRANTY SHALL AP...

Отзывы: