Instruction Manual PSE2xxDN
23
3 Sequence of positioning
a) Positioning run
- In order to control the drive using I/O connections, you must first establish an explicit
connection using the UCMM; this connection is then used to allocate and configure
the desired I/O connection.
- Transfer target value:
- Poll I/O message with control word 14h and target value
OR
- If release has not been set in the control word: set target value explicitly (using the
PSE object; class 100, instance 1, attribute 1); bit-strobe message, bit is set.
OR
- If release has been set in the control word: set explicit target value (using the PSE
object; class 100, instance 1, attribute 1).
Drive begins run.
- Aborting a run by withdrawing release:
- Poll I/O with control word 0
OR
- Bit strobe; bit is reset
OR
- Control word set explicitly to 0
- If a new target value is transferred during a positioning run, the device will
immediately proceed to the new target. This will occur with no interruption provided
the direction of rotation does not need to be altered.
- If a manual run is transmitted during a positioning run, the positioning run will be
aborted (speed will be reduced to that of a slow run) and the operator may proceed
with the manual run.
The following sequence of steps is also possible:
Starting condition:
- release has not been set
- Target value has already been transferred (in case of poll I/O transfer the release in
the control word was not set already)
Set release: drive begins run
b) Positioning run without a reference loop
The sequence corresponds to that of a positioning run with a loop; in addition to setting
the release, however, bit 6 in the control word also has to be set to execute the run
without loop.
c) Manual run
- Transfer manual run:
- Poll I/O with control word 11h or 12h
OR
- Set control word explicitly to 11h or 12h (using the PSE object; class 100, instance
1, attribute 36)
Drive begins run.
- End manual run by withdrawing manual run:
- Poll I/O with control word 10h