MAN1565-4
9
5.2
Terminal Block Numbering
Terminal Block
TP Number
AS4428
COMMUNICATIONS EXTERNAL
TB2/1
RS485 +
2
28
RS485 -
3
29
Shield
INPUTS
TB3/1
Common
2
25
Door Switch (monitored)
3
26
Manual Call Point (monitored)
4
27
Fault Input (monitored)
ZONES ( 25mA / Zone )
TB13/1
1
+ Zone 1
2
2
- Zone 1
3
3
+ Zone 2
4
4
- Zone 2
5
5
+ Zone 3
6
6
- Zone 3
7
7
+ Zone 4
8
8
- Zone 4
TB14/1
9
+ Zone 5
2
10
- Zone 5
3
11
+ Zone 6
4
12
- Zone 6
5
13
+ Zone 7
6
14
- Zone 7
7
15
+ Zone 8
8
16
- Zone 8
MONITORED OUTPUTS ( 500mA / O/p )
TB4/1
17
External Bell +
2
18
External Bell -
3
19
Warning
4
20
Warning System -
5
21
ACF + Aux Control Function
6
22
ACF -
7
23
ASE + Alarm Signaling Equipment
8
24
ASE -
OPEN COLLECTOR OUTPUTS ( 30 mA /O/P )
TB5/1
25
Alarm +
2
26
Alarm -
3
27
Fault +
4
28
Fault -
OUTPUTS VOLT FREE RELAY ( 1A @ 30V )
5
29
NO Alarm
6
30
C Alarm
7
31
NC Alarm
8
32
NO Fault
9
33
C Fault
10
34
NC Fault
AUX, RESET / BUZZER
TB12/1
35
Aux 24VDC + (Mon 500mA)
2
36
Aux 24VDC
–
3
37
Reset/Buzzer 100mA max