SmartFOAM
FLUSHING THE SMARTFOAM SYSTEM
When returning the apparatus to the ready condition after
foam operations
using Class “B” foam, the Hale SmartFOAM
foam pump must be FLUSHED.
Some Class “B” foam
concentrates deteriorate rapidly and residue cannot be left in
the lines.
Note
:
Approved Class “A” foam concentrates do not
deteriorate rapidly like Class “B” concentrates. As long as an
approved Class “A” foam concentrate is used and the
system is operated within 10-12 weeks no flushing is
required. When Class “B” foam concentrate is used, always
FL
USH the system, then switch back to Class “A” (see
: Dual Tank Selector Operating Positions
1. Energize the apparatus and establish water flow
through a foam capable discharge. Set the fire pump
for a LOW discharge pressure, 50 to 75 PSI (3.4 to
5.2 BAR).
2. Energize the Hale SmartFOAM by pressing the ON
button, allowing foam solution to discharge.
Note
: When the Hale ADT, MDTII or MST is in the
FLUSH position the Hale SmartFOAM foam injection
system runs for about twenty (20) second.
Figure 58
: Hale MST Selector Operation
3. Place the Hale ADT, MDT II or MST to the FLUSH
position (see Figure 58
4. Observe the discharge hose and allow Hale
SmartFOAM and discharge to run for several
seconds.
5. After several seconds place the Hale ADT or MDT II
to the TANK “A” position and allow the system to run
until all foam solution is discharged through the
foam capable hose line.
Note
: When the Hale MST is used for Class “B”
foam concentrates DO NOT allow the foam pump to
run in the FOAM TANK position after flushing foam
pump.
6. Place the Hale MST to the FOAM TANK position
and allow Hale SmartFOAM
to run until Class “A”
foam solution is discharged through the foam
capable hose line. If Class “B” foam concentrate is
used, shut down Hale SmartFOAM immediately
after switching to the FOAM TANK position.
7. Shut down Hale SmartFOAM allowing the foam
capable discharge to continue to flush out the fire
pump discharge manifold as required. Once clear
water flows, close foam capable discharge and shut
down the apparatus.
8. Perform required maintenance checks on the Hale
SmartFOAM and apparatus to return the apparatus
to the ready condition.
IMPORTANT!
MAKE SURE THE HALE ADT OR MDT II IS IN THE TANK
“A” POSITION AND THE HALE MST IS IN THE FOAM
TANK POSITION WHEN APPARATUS IS PLACED IN THE
READY CONDITION.
Содержание SmartFOAM 1.7AHP
Страница 3: ...Page 2 SmartFOAM NOTES...
Страница 13: ...Page 12 SmartFOAM HALE FOAM PUMP DIMENSIONS Figure 1 1 7 and 2 1 Foam Pump Installation Envelope Dimensions...
Страница 14: ...Page 13 SmartFOAM Figure 2 3 3 and 5 0 Foam Pump Installation Envelope Dimensions...
Страница 15: ...Page 14 SmartFOAM SYSTEM DIAGRAM Figure 3 Typical Hale SmartFOAM 2 1A and 1 7AHP System...
Страница 16: ...Page 15 SmartFOAM Figure 4 SmartFOAM 3 3 5 0 6 5 Single Tank System with In line Strainer...
Страница 17: ...Page 16 SmartFOAM Figure 5 SmartFOAM 3 3 5 0 6 5 Single Tank withMSTandIn lineStrainer...
Страница 18: ...Page 17 SmartFOAM Figure 6 SmartFOAM 3 3 5 0 6 5 Single Tank withMSTandFSSeriesStrainer...
Страница 19: ...Page 18 SmartFOAM Figure 7 SmartFOAM 3 3 5 0 6 5 Dual Tank withMDTIIandIn lineStrainer...
Страница 20: ...Page 19 SmartFOAM Figure 8 SmartFOAM 3 3 5 0 6 5 Dual Tank withMDTIIandFSSeriesStrainer...
Страница 21: ...Page 20 SmartFOAM Figure 9 SmartFOAM 3 3 5 0 6 5 Dual Tank with ADTandIn lineStrainer...
Страница 22: ...Page 21 SmartFOAM Figure 10 SmartFOAM 3 3 5 0 6 5 Dual Tank with ADTandFSSeriesStrainer...
Страница 30: ...Page 29 SmartFOAM REMOTE START OPTION Switch with indicator 513 0330 01 0 Harness 513 0680 00 0...
Страница 40: ...Page 39 SmartFOAM Figure 18 Typical 4 Inch Check Valve Installation Midship Pump...
Страница 51: ...Page 50 SmartFOAM Figure 33 ADT Option Air Hose Connections Part 2...
Страница 68: ...Page 67 SmartFOAM NOTES...
Страница 80: ...79 Page 79 SmartFOAM NOTES...