Page
10
SmartFOAM
Maximum Foam Solution Flow
Injection Rate
Percent (%)
Flow rate in GPM [LPM]
1.7AHP
2.1A
3.3
5.0
6.5
Dual 6.5
0.1
1,700 [6,426]
2,100 [7,949]
3,300 [12,492]
5,000 [18,927]
6,500 [24,606]
13,000 [49,213]
0.2
850 [3,213]
1,050 [3,974]
1,650 [6,245]
2,500 [9,464]
3,250 [12,303]
6,500 [24,606]
0.3
567 [2,143]
700 [2,650]
1,100 [4,164]
1,667 [6,310]
2,167 [8,202]
4,333 [16,404]
0.5
340 [1,285]
420 [1,590]
660 [2,498]
1,000 [3,785]
1,300 [4,921]
2,600 [9,843]
1.0
170 [643]
210 [795]
330 [1,249]
500 [1,893]
650 [2,461]
1,300 [4,921]
3.0
110 [416]
167 [632]
217 [820]
433 [1,640]
6.0
55 [208]
83 [314]
108 [410]
217 [820]
Table 1
: Maximum Foam Solution Flows
LOW PRESSURE STRAINER
A low pressure foam concentrate strainer is mounted at the inlet of the foam pump. The strainer protects the pump from
debris that might accumulate in the foam concentrate tank. The strainer/valve assembly has a composite non-metallic
housing with stainless steel mesh strainer element and includes a service shut-off valve.
The valve
inlet offers 1/2” NPT (13 mm) threads, with a fitting to connect a 1/2” (13 mm) ID foam concentrate suction
hose.
The strainer and valve are low pressure devices and are designed for installations where the strainer IS NOT subject to
HIGH pressure flushing water.
HIGH PRESSURE STRAINERS (FS Series)
Hale FS series strainers (FS15 and FS25) are panel mounted with a 500 PSIG (34 BAR) pressure rating, suitable for use
where flushing water pressure must pass through the strainer.
The FS15 strainer uses 3/4” (19mm) NPT connection ports and a 1-1/2” NST cap. It is suitable for use with Class “A” and
low viscosity Class “B” foam concentrates.
The FS25 strainer uses 1” (25mm) NPT connection ports and a 2-1/2” NST cap. It is suitable for use with both Class “A”
and Class “B” foam concentrates.
TANK SELECTOR VALVES
SmartFOAM models 3.3, 5.0, and 6.5 may use dual foam tanks for A and B foam concentrates. Selection of the desired
foam concentrate tank with the
ADT
panel mounted toggle switch or
MDT II
selector automatically changes the foam
concentrate injection rate to the preset default rate for the selected foam tank. No further operator Intervention is required.
The
ADT
,
MDT II
and
MST
include the check valves and connection points to provide foam pump flushing capabilities.
Air Dual Tank Selector (ADT)
The Air Dual Tank (ADT) valve is an air operated foam tank selector valve that enables selection of foam concentrate
dependent on fire ground operational demands.
The ADT is an integral part of the foam pump and provides an electrical interlock for the low tank level sensors and
concentrate injection rate. A panel mounted selector toggle switch with indicator lights controls foam concentrate tank
selection and shows which foam concentrate tank is in use.
Manual Dual Tank Selector (MDT II)
The Manual Dual Tank (MDT II) selector valve is available for the Hale Foam systems with dual tanks. The MDT II is a
panel mounted, manually operated selector that provides selection of foam concentrate dependent on fire ground
operational demands.
The MDT II also provides an electrical interlock for the low tank level sensors and concentrate injection rate. The MDT II is
not suitable for top mount operator panel installations and some side operator panels due to gravity feed requirements of
foam concentrate to the foam pump.
Содержание SmartFOAM 1.7AHP
Страница 3: ...Page 2 SmartFOAM NOTES...
Страница 13: ...Page 12 SmartFOAM HALE FOAM PUMP DIMENSIONS Figure 1 1 7 and 2 1 Foam Pump Installation Envelope Dimensions...
Страница 14: ...Page 13 SmartFOAM Figure 2 3 3 and 5 0 Foam Pump Installation Envelope Dimensions...
Страница 15: ...Page 14 SmartFOAM SYSTEM DIAGRAM Figure 3 Typical Hale SmartFOAM 2 1A and 1 7AHP System...
Страница 16: ...Page 15 SmartFOAM Figure 4 SmartFOAM 3 3 5 0 6 5 Single Tank System with In line Strainer...
Страница 17: ...Page 16 SmartFOAM Figure 5 SmartFOAM 3 3 5 0 6 5 Single Tank withMSTandIn lineStrainer...
Страница 18: ...Page 17 SmartFOAM Figure 6 SmartFOAM 3 3 5 0 6 5 Single Tank withMSTandFSSeriesStrainer...
Страница 19: ...Page 18 SmartFOAM Figure 7 SmartFOAM 3 3 5 0 6 5 Dual Tank withMDTIIandIn lineStrainer...
Страница 20: ...Page 19 SmartFOAM Figure 8 SmartFOAM 3 3 5 0 6 5 Dual Tank withMDTIIandFSSeriesStrainer...
Страница 21: ...Page 20 SmartFOAM Figure 9 SmartFOAM 3 3 5 0 6 5 Dual Tank with ADTandIn lineStrainer...
Страница 22: ...Page 21 SmartFOAM Figure 10 SmartFOAM 3 3 5 0 6 5 Dual Tank with ADTandFSSeriesStrainer...
Страница 30: ...Page 29 SmartFOAM REMOTE START OPTION Switch with indicator 513 0330 01 0 Harness 513 0680 00 0...
Страница 40: ...Page 39 SmartFOAM Figure 18 Typical 4 Inch Check Valve Installation Midship Pump...
Страница 51: ...Page 50 SmartFOAM Figure 33 ADT Option Air Hose Connections Part 2...
Страница 68: ...Page 67 SmartFOAM NOTES...
Страница 80: ...79 Page 79 SmartFOAM NOTES...