SmartFOAM
FOAM CONCENTRATE DISCHARGE HOSE
The system installer must supply fittings and hoses from
the foam pump inject connection to the check
valve/injector fitting inlet. All components selected transfer
foam concentrate, therefore they must be compatible with
the foam concentrates being used in the system.
The foam pump discharge connection is a
1/2” (13 mm)
compression fitting. The check valve injector fitting
connection has 1/2” NPT threads. Hoses and fittings of
1/2” minimum diameter rated at 500 PSI (34.5 BAR)
working pressure or maximum discharge pressure of the
fire pump must be used. Fittings and hoses must be
compatible with all foam agents to be used.
Recommended components
Hose:
Aeroquip 2580-8 or Equivalent Reinforced
Hydraulic Hose.
Fittings:
Brass or Stainless Steel Hose End Crimp or
Reusable Type (Aeroquip 412-9-8 or
Equivalent).
Note:
Although air brake tubing has been used for foam
concentrate discharge hose, it is not as flexible as the
hydraulic hose and readily kinks during installation.
Additionally, the air brake tubing may not meet NFPA 500
PSI (34 BAR) test requirements.
FOAM CONCENTRATE BYPASS HOSE
The foam concentrate bypass hose connection is a
1/2”
(13mm) hose barb connection. Hoses and fittings of
nominal 1/2” diameter must be used as bypass hose.
Since the bypass hose is used for calibration and draining
the system it does not see high operating pressures;
therefore, a hose with a lower pressure rating than the
inject hose may be used.
Fittings and hoses used must be compatible with all foam
agents expected to be used. Use fittings made of brass or
300 series stainless steel compatible with all foam
concentrates.
Recommended components
Hose:
Low Pressure Hydraulic Hose or Air Brake
Tubing.
Fittings:
Brass or Stainless Steel.
It is recommended that the foam concentrate bypass hose
be long enough to extend past the apparatus running
board to reach five (5) gallon (19 liter) containers, making
foam pump setup and calibration simpler.
CHECK VALVES
Check valves must be installed on the apparatus with foam
systems to prevent contamination of the foam concentrate
with water and contamination of the fresh water tank with
foam. When a Hale SmartFOAM foam Injection system and
related components are properly installed the required check
valves are integral parts of the system.
NFPA standards require a check valve in the foam
concentrate injection line at the injection point. The Hale part
number 038-1790-00-0 Integral Check Valve/ Injector Fitting,
a standard component included with the Hale SmartFOAM
system and installed when a manifold kit is ordered, meets
these requirements and threads directly into the foam
injection port on Hale manifolds.
Check valves must be installed in all water piping locations
where foam concentrate could drain back into pumps or
other components of the fire apparatus.
As a minimum one check valve must be installed where the
water piping that supplies foam solution connects to the fire
pump discharge. To more effectively keep foam
contamination out of the fire pump and water tank, double
check valves are recommended.
Separate two check valves by at least 6” to 8” (152 to
203mm) of piping to form a dead zone between the check
valves. Individual drain lines should be used on each check
valve. The waterway check valves must be rated for 500
PSIG (34.5 BAR) test pressure.
FLUSHING WATER HOSE
Flushing water connections for the Hale ADT, MDT II or
MST require using 1/2” (13mm) inside diameter tubing and
appropriate fittings. The tubing and fittings used must be
capable of withstanding the maximum fire pump discharge
pressure (500 PSI [34 BAR] minimum) and must be
compatible with foam concentrates being used in the
system.
When the ADT, MDT II or MST is installed, a check valve is
used integral to the flushing water line connection. This
provides protection against water system contamination with
foam concentrate.
Note:
The installer/builder should provide an additional
check valve and shut-off valve where the flushing water
hose connects to the water pump.
Hale recommends the use of one of the above selector
options to provide foam system flushing capabilities.
However, if the Hale SmartFOAM system is ordered with the
“no tank” option the system installer must maintain NFPA
compliance.
Содержание SmartFOAM 1.7AHP
Страница 3: ...Page 2 SmartFOAM NOTES...
Страница 13: ...Page 12 SmartFOAM HALE FOAM PUMP DIMENSIONS Figure 1 1 7 and 2 1 Foam Pump Installation Envelope Dimensions...
Страница 14: ...Page 13 SmartFOAM Figure 2 3 3 and 5 0 Foam Pump Installation Envelope Dimensions...
Страница 15: ...Page 14 SmartFOAM SYSTEM DIAGRAM Figure 3 Typical Hale SmartFOAM 2 1A and 1 7AHP System...
Страница 16: ...Page 15 SmartFOAM Figure 4 SmartFOAM 3 3 5 0 6 5 Single Tank System with In line Strainer...
Страница 17: ...Page 16 SmartFOAM Figure 5 SmartFOAM 3 3 5 0 6 5 Single Tank withMSTandIn lineStrainer...
Страница 18: ...Page 17 SmartFOAM Figure 6 SmartFOAM 3 3 5 0 6 5 Single Tank withMSTandFSSeriesStrainer...
Страница 19: ...Page 18 SmartFOAM Figure 7 SmartFOAM 3 3 5 0 6 5 Dual Tank withMDTIIandIn lineStrainer...
Страница 20: ...Page 19 SmartFOAM Figure 8 SmartFOAM 3 3 5 0 6 5 Dual Tank withMDTIIandFSSeriesStrainer...
Страница 21: ...Page 20 SmartFOAM Figure 9 SmartFOAM 3 3 5 0 6 5 Dual Tank with ADTandIn lineStrainer...
Страница 22: ...Page 21 SmartFOAM Figure 10 SmartFOAM 3 3 5 0 6 5 Dual Tank with ADTandFSSeriesStrainer...
Страница 30: ...Page 29 SmartFOAM REMOTE START OPTION Switch with indicator 513 0330 01 0 Harness 513 0680 00 0...
Страница 40: ...Page 39 SmartFOAM Figure 18 Typical 4 Inch Check Valve Installation Midship Pump...
Страница 51: ...Page 50 SmartFOAM Figure 33 ADT Option Air Hose Connections Part 2...
Страница 68: ...Page 67 SmartFOAM NOTES...
Страница 80: ...79 Page 79 SmartFOAM NOTES...