C-5
C.3.
ANCILLARY EQUIPMENT PREVENTIVE MAINTENANCE PROCEDURES
Regular preventive maintenance assures continued dependable operation of the ancillary
equipment used with the Hale single stage booster pumps. This section provides recommended
actions to be completed for the ancillary equipment listed in this appendix. The pump preventive
maintenance actions listed are scheduled to be completed after each use and on a weekly, quar-
terly and annually basis.
C.3.1
Weekly Maintenance
Perform each the following procedures weekly.
C.3.1.1
Pump Shift Warning Indicator Lights
Verify the parking brake is set and the wheels are chocked to prevent any movement of the ap-
paratus.
A.
Follow operating procedures in (Section 3 — OPERATING PROCEDURES) to en-
gage pump if no local procedures exist.
B.
Verify warning indicators in cab and on pump control panel function properly.
C.
Verify indicator lights on control panel function properly and agree with indica-
tors in cab. Repair or replace any malfunctioning indicators.
C.3.1.2
Check Valves
Properly functioning valves are integral to the proper operation of the pump. Refer to the valve
manual for proper valve maintenance procedures.
A.
Lubricate all suction and discharge valves using an approved lubricant.
B.
Verify each valve operates easily and closes completely.
C.
Inspect and lubricate all valve linkages. Repair or replace any damaged or
nonfunctional linkages.
C.3.1.3
Check And Clean Intake Strainers
Remove the strainers. Clean any debris out of the intake. Flush the pump if required by depart-
ment procedures. Repair or replace any damaged strainers.
C.3.1.4
Check All Gauges
Any gauge that is repeated in the cab or another panel, must agree with the gauge on the opera-
tor's panel. Gauges not reading within 10% of the calibrated test gauge must be removed from
service and recalibrated.
C.3.1.5
Check Pump Controls
Operate the pump drive controls to verify the pump can be engaged. Verify the indicator lights
work properly.
C.3.1.6
Inspect Water and Foam Tanks
Visually inspect water and foam tanks for proper level and gauge readings. If any debris is pre-
sent, flush the tanks to protect the pump from wear caused by dirty water or foam concentrate.
C.3.1.7
Check Roof and Bumper Turrets
If the apparatus is so equipped, verify the turrets function properly, and no leaks are present.
Содержание AP
Страница 2: ......
Страница 28: ......
Страница 71: ...59 Figure 19 One Piece Volute AP CBP MBP Figure 20 Three Piece Volute RSD...
Страница 73: ...61 Figure 21 AP Pump Exploded View...
Страница 74: ...62 Figure 22 CBP Pump Exploded View...
Страница 75: ...63 Figure 23 MBP Pump Exploded View...
Страница 76: ...64 Figure 24 RSD Pump Exploded View...
Страница 77: ...65 Figure 25 Gearbox Exploded View All Except 3 74 1 GR...
Страница 78: ...66 Figure 26 Gearbox Exploded View 3 74 1 GR...
Страница 158: ...146 THIS PAGE INTENTIONALLY BLANK...
Страница 174: ...C 12 THIS PAGE INTENTIONALLY BLANK...
Страница 176: ...D 2 DATE HOURS RUN MAINTENANCE PROBLEM PART S USED REASON REPLACED INITIALS...