ISOLGUARD HIG93, HIG93/L, HIG94 

 

  V5.8/23 

HAKEL spol. s r.o. Hradec Králové                     

www.hakel.com

                                                               

Page 5 / 15 

3.  HIG93, HIG93/L, HIG94

 

controls and connecting terminals 

Green indicator lamp ON 

This control lights up when the device is ON (powered). It glimmers slightly after module 
activation. 

Yellow indicator lamp FAULT1  

The light indicates 

FAULT1

, when the measured insulation resistance value is lower than the 

set  critical  resistance 

R

crit1

  value.  It  even  lights  after  the  fault  status  removal,  if  the  fault 

memory  function is active. At the same  time,  this  status is signalled by  the 

FAULT1

  relay 

contacts. 

Yellow indicator lamp FAULT2 

The light indicates 

FAULT2

, when the measured insulation resistance value is lower than the 

set critical resistance

 R

crit2

. It even lights after the fault status removal, if the fault memory 

function is active. At the same time, this status is signalled by the 

FAULT2

 relay contacts. 

Display 

It serves to display the measured values, to show current function of the S1 – S3 pushbuttons, 
to  set the parameters  and to display information.  For description  of displayed  information, 
see chapter 

Information on the display

, page 8. 

FAULT1

 or 

FAULT2

 relay status change, eventually starting and ending device test, is 

signalled by short display flash. 
The display goes off if no button is pressed for 5 minutes and is again restored by pressing 
any button. The insulation monitoring device is operational even if the display is not active. 

Left push-button S1 

This is a module control button whose meaning in each menu is shown on the display. When 
the insulation resistance 

R

isol

 is displayed, this button has the meaning of 

TEST

 push-button. 

See chapter 

Information on the display

, page 8. 

Middle push-button S2 

This is a module control button whose meaning in each menu is shown on the display. It releases the relay 

FAULT

, when the 

fault memory function is active. It activates display of temperature inside the module if the insulation resistance value 

R

isol

 

is 

displayed.  

Right push-button S3 MENU 

This is a module control button whose meaning in each menu is shown on the display. When the insulation resistance 

R

isol

 

is 

viewed, it activates the parameter setting menu.  
Within the parameters setting menu, the prolonged pressing of this push-button terminates the data entering with memorizing 
the new value, whereas the short pressing of this push-button causes exit from the menu without memorizing the new 
parameter value. 

Terminals A1, A2 

These terminals serve to connect the module’s power supply. The power supply voltage is 90 to 265 V AC (47 ÷ 440 Hz) or 
90 to 370 V DC. 

Terminals CENTRE, PE  

Input terminals for the insulation resistance measurement, see recommended connections of the insulation monitoring device. 
If  the monitoring  of IT power supply  system  with  voltage higher than  275  V  AC  (without  brought-out neutral  conductor) is 
required, it is necessary to create an artificial centre using TL inductors. Such a created neutral is connected to the 

CENTRE

 

terminal. The value of external inductor DC resistance is set within the Parameters setting menu. 

Terminals of the signalling relay FAULT1 230 V AC /1 A 
Terminals of the signalling relay FAULT2 230 V AC /1 A 

Potential-free switching relay contact for signalling the status of the monitored IT power supply system. 

FAULT1

 and 

FAULT2 

relay status when insulation status fault occurs is determined by the setting of 

Set Relay FA

 parameter. 

This parameter can be set to one of two values 

N/C

 and 

N/O

The signalling is performed as follows when parameter 

Set Relay FA 

is set to 

N/C

 value: 

Relay 

FAULT1 (FAULT2)

 

is released

, when the device is connected to the power supply, is functional (the indicator lamp ON 

glimmers slightly) and insulation status 

fault

 

FAULT1

 (

FAULT2

is not indicated

. The insulation resistance of the monitored 

system is higher than the set critical value 

R

crit1

 

(

R

crit2

). 

The signalling is performed as follows when parameter 

Set Relay FA 

is set to 

N/O

 value: 

Relay 

FAULT1 (FAULT2)

 

is released

, when the device is connected to the power supply, is functional (the indicator lamp ON 

glimmers slightly) and insulation status 

fault

 

FAULT1

 (

FAULT2

is indicated

A

B

SH

RS485

C

E

N

T

R

E

+

1

2V

A

1

A

2

P

E

T

E

S

T

MENU

Display

230VAC/1A

ON

FAULT2

FAULT1

HIG93

5   900 kΩ

S1

S2

S3

HAKEL

ISOLGUARD

SH

B

A

230VAC/1A

FAULT2

FAULT1

1

2

3

4

5

6

Picture 1: Terminals designation 

Содержание ISOLGUARD HIG93

Страница 1: ...LGUARD HIG93 HIG93 L HIG94 V5 8 23 HAKEL spol s r o Hradec Kr lov www hakel com Page 1 15 Insulation monitoring device ISOLGUARD HIG93 HIG93 L HIG94 Operating instructions Document s name DOK 70915 V5...

Страница 2: ...ion 5 Picture 2 Connection of HIG93 94 device 7 Picture 3 Connection of HIG93 94 device 7 Picture 4 Displayed information 8 Picture 5 Insulation resistance fault evaluation 11 Picture 6 Insulation sta...

Страница 3: ...1 1 Variants of devices ISOLGUARD HIG93 HIG93 L HIG94 Type Display Menu Signalling relay 1 Signalling relay 2 Range of displayed value Critical insulation resistance Communication bus bar MDS D connec...

Страница 4: ...c Outputs Two signalling relays with switching contact electric strength to the internal circuits electric strength to the supply circuits 250 V AC 1 A 3750 Vrms 3750 Vrms Communication line RS485 typ...

Страница 5: ...u is shown on the display When the insulation resistance Risol is viewed it activates the parameter setting menu Within the parameters setting menu the prolonged pressing of this push button terminate...

Страница 6: ...connections of the insulation monitoring Device Terminals A B SH These terminals are intended for connection of galvanic isolated communication line ISOLGUARD RS485 Individual insulation monitoring de...

Страница 7: ...FAULT2 FAULT1 S1 S2 S3 SH B A FAULT2 FAULT1 MENU 1 2 3 4 5 6 PE L1 L1 L2 PE L2 L3 N L3 TL400 L1 L2 L3 CENTRE Rtl ext TEST ALARM 2 ALARM 1 RS485 ISOLGUARD PE 4 Recommended connection of HIG93 HIG93 L...

Страница 8: ...C SET Relay Logic ESC SET N C FAULT ESC SET Picture 4 Displayed information 5 Information on the display Operating principles The meaning of the push buttons in each menu is shown on the display Press...

Страница 9: ...ation line is performed immediately after receiving the order and takes 5 seconds If the FAULT memory is set Mem FAULT menu the signal relay remains in a status of alarm indication even after the test...

Страница 10: ...label as Rin Typical values for three phase HAKEL inductors are as follows TL400 4 5 k TL500 4 5 k TL600 4 5 k TL1600 12 5 k TL6003 19 6 k Exact values may be obtained by measuring the inductor s wind...

Страница 11: ...LT2 is only terminated when the insulation resistance increases above the value Rcrit1 Rhyst or Rcrit2 Rhyst Signalling relay is released and FAULT1 FAULT2 signalling is terminated The following left...

Страница 12: ...assigned by the MASTER station In practice the communication proceeds in such a way that the MASTER station sends requests subsequently to all connected units and the SLAVE stations response The acces...

Страница 13: ...nt data determining the status of this measurement e g fault occurrence Parameter data are extended of priority character determining the importance of the set parameter This character divides paramet...

Страница 14: ...20 20 20 Delay in response of signalling the fault Set tON tON 0 sec 0 sec 0 sec External inductor resistance Set TLext Rtl ext 0 k 0 k 0 k Delay in device test start by remote test button Set tTEST t...

Страница 15: ...and service It is necessary to follow specified conditions for reliable operation do not expose the device to rough handling keep it clean and ensure maximum admissible temperature of the environment...

Отзывы: