background image

ISOLGUARD HIG93, HIG93/L, HIG94 

 

  V5.8/23 

HAKEL spol. s r.o. Hradec Králové                     

www.hakel.com

                                                               

Page 12 / 15 

MASTER
485Addr=0
DIP SW1 =ON

485Rte=No
485ADDR=1

485Rte=YES
(Rte = 120Ω)
485ADDR=3

MENU
Parameter: 

485Rte=No
485ADDR=2

MDS-D/66

A1 B1 SH1

B2 SH2

(+)

(-)

A2

1

2

3

4

5

6

7

8

Napájení 
MDS-D
24 V DC

HIG93

RS485

HIG94

RS485

HIG93

RS485

Externí linka RS485

Picture 7: RS485 bus 

 

Picture 8: RS485 ISOLGUARD 
bus

 

HIG93

MASTER

120Ω

Pull-Up

470Ω 1kΩ

Pull_Down

470Ω 1kΩ

A

B

station 1

HIG93

A

B

station 2

HIG94

A

B

station 3

HIG94

A

B

station n

+5V

A

B

Rte=YES

ADDR = 0

7.  Communication protocol 

Units HIG93, HIG93/L and HIG94 communicates via the industrial RS485 bus using the protocol based on the PROFIBUS 
protocol. Communication proceeds in the request – response mode. One MASTER station has to be connected to the bus, 
whereas this MASTER station sends requests to the other SLAVE stations. The slave stations only respond to requests, they 
never start communication. Unit HIG93/94 is in position of the slave station. 
Individual  stations  are  connected  with  TWISTED  PAIR-TP.  One  conductor  is  labelled  A,  the  second  one  B.  Logical  1 
(respectively 0) is determined by the voltage between these conductors. During an idle state (logical 1), the A conductor is 
more positive than the B conductor (at least by 200mV). 
An individual address must be set for each station being connected to the bus. The address for the unit HIG93/94 is adjustable 
within a range 1 to 126 (address 0 is reserved for the MASTER station).  
The length of the line can be up to 1200 meters; in view of proper installation, both ends of the line need to be terminated, 
namely  by  using  the  resistance  of  120  Ω.  At  a  given  moment,  each  station  connected  to  the  line  RS485  may  transmit  or 
receive. This mode is called half-duplex. In order to avoid any collision (i.e., two stations must not transmit simultaneously), 
the transmit right must be assigned by the MASTER station. In practice, the communication proceeds in such a way, that the 
MASTER station sends requests subsequently to all connected units and the SLAVE stations response. The accessibility of 
the station is ensured by its address, which must be unique for every station on the line. 
For ISOLGUARD system PC computer or programmable logic controller with RS485 line can be used as a MASTER station. 
Also, remote monitoring module MDS-D/66 with protection degree IP66 from HAKEL production may be used. This module 
allows  remote  displaying  of  measured  values  and  set  parameters and  also  data  transferring to  the  user’s  master system. 
Detailed description of HIG93/94 communication protocol is given in the programming manual. 

RS485 ISOLGUARD

 

line parameter setting 

In the menu 

Parameter settings

 may be selected the menu 

Set 485ADDR

 and 

Set 485Rte

.  

Menu 

Set 485ADDR

 serves for setting of the address for HIG93/94 device on the RS485 bus. The setting range for the address 

is 1 to 126.  
Menu 

Set 485Rte

 serves for setting the connection of an internal terminating resistor R

te

 to the RS485 line. This parameter 

may  be  set  to 

YES

  (when  the  resistance  120Ω  is  internally  connected  to  the  RS485  line  of  the  module),  or 

NO

  (without 

connected resistance). 

RS485

 

bus structure 

 
 
 
 
 
 
 
 
 
 
 
 

Communication between HIG devices and MDS-D remote monitoring module 

Using MDS-D as the MASTER station allows the user smooth and convenient supervision of up to 24 IT power supply systems’ 
status, monitored by HIG93/94 devices or other devices of HIG ISOLGUARD series. MDS-D/66 touch panel in industrial design 
with protection degree IP 66 communicates with insulation monitoring devices via ISOLGUARD protocol fully automatically, 
including the ability to search monitoring devices on the connected bus. For proper function it is only necessary to set unique 
addresses in the device menu and connect monitoring devices and MDS-D/66 panel by twisted pair. HIG monitoring devices 
are always connected to the internal RS485 line of the MDS-D module, i.e. A1 B1 terminals. 

 
 
 
 
 
 
 
 
 
 
 
 

 

Содержание ISOLGUARD HIG93

Страница 1: ...LGUARD HIG93 HIG93 L HIG94 V5 8 23 HAKEL spol s r o Hradec Kr lov www hakel com Page 1 15 Insulation monitoring device ISOLGUARD HIG93 HIG93 L HIG94 Operating instructions Document s name DOK 70915 V5...

Страница 2: ...ion 5 Picture 2 Connection of HIG93 94 device 7 Picture 3 Connection of HIG93 94 device 7 Picture 4 Displayed information 8 Picture 5 Insulation resistance fault evaluation 11 Picture 6 Insulation sta...

Страница 3: ...1 1 Variants of devices ISOLGUARD HIG93 HIG93 L HIG94 Type Display Menu Signalling relay 1 Signalling relay 2 Range of displayed value Critical insulation resistance Communication bus bar MDS D connec...

Страница 4: ...c Outputs Two signalling relays with switching contact electric strength to the internal circuits electric strength to the supply circuits 250 V AC 1 A 3750 Vrms 3750 Vrms Communication line RS485 typ...

Страница 5: ...u is shown on the display When the insulation resistance Risol is viewed it activates the parameter setting menu Within the parameters setting menu the prolonged pressing of this push button terminate...

Страница 6: ...connections of the insulation monitoring Device Terminals A B SH These terminals are intended for connection of galvanic isolated communication line ISOLGUARD RS485 Individual insulation monitoring de...

Страница 7: ...FAULT2 FAULT1 S1 S2 S3 SH B A FAULT2 FAULT1 MENU 1 2 3 4 5 6 PE L1 L1 L2 PE L2 L3 N L3 TL400 L1 L2 L3 CENTRE Rtl ext TEST ALARM 2 ALARM 1 RS485 ISOLGUARD PE 4 Recommended connection of HIG93 HIG93 L...

Страница 8: ...C SET Relay Logic ESC SET N C FAULT ESC SET Picture 4 Displayed information 5 Information on the display Operating principles The meaning of the push buttons in each menu is shown on the display Press...

Страница 9: ...ation line is performed immediately after receiving the order and takes 5 seconds If the FAULT memory is set Mem FAULT menu the signal relay remains in a status of alarm indication even after the test...

Страница 10: ...label as Rin Typical values for three phase HAKEL inductors are as follows TL400 4 5 k TL500 4 5 k TL600 4 5 k TL1600 12 5 k TL6003 19 6 k Exact values may be obtained by measuring the inductor s wind...

Страница 11: ...LT2 is only terminated when the insulation resistance increases above the value Rcrit1 Rhyst or Rcrit2 Rhyst Signalling relay is released and FAULT1 FAULT2 signalling is terminated The following left...

Страница 12: ...assigned by the MASTER station In practice the communication proceeds in such a way that the MASTER station sends requests subsequently to all connected units and the SLAVE stations response The acces...

Страница 13: ...nt data determining the status of this measurement e g fault occurrence Parameter data are extended of priority character determining the importance of the set parameter This character divides paramet...

Страница 14: ...20 20 20 Delay in response of signalling the fault Set tON tON 0 sec 0 sec 0 sec External inductor resistance Set TLext Rtl ext 0 k 0 k 0 k Delay in device test start by remote test button Set tTEST t...

Страница 15: ...and service It is necessary to follow specified conditions for reliable operation do not expose the device to rough handling keep it clean and ensure maximum admissible temperature of the environment...

Отзывы: