When the outdoor unit is shut down, the valve is opened completely for 2 minutes, and then
begin initialization.
The scope of refrigerationg valve
90-----480 steps
The scope of heating valve
80-----480 steps
The valves are adjusted according to the degree of superheat
SHa
SHa.
7.1.2
Four way control
For the details of defrosting four-way valve control, see the defrosting process.
Four way working in other ways:
Under the mode of heating, open the four-way valve, when the compressor is not started or
changed to non-heating mode, make sure the compressor is stoped for 2 minutes, and then
close the four-way valve.
7.1.3 Protection function
7.1.3.1
TTC high temperature-preventing protection
Once the machine is started, it can run TTC overheating protection of air-blowing, but air-blowing
sensor malfunction must alarm after 4 minutes during which the compressor is started (during the
course of self-detection, there’s no such limitation)
Sensor detection methods: 100 times (one cycle of procedure run is one time, and about 5ms,
detection method for each time: continuously sampling for 8 times, then order them and take the
mean value of the middle 2 values), take the mean value.
TTC
Abnormal stop
110
Decreasing the frequency rapidly 1HZ/second
100
Decreasing the frequency slowly (1HZ/10seconds)
98
The frequency doesn’t change.
93
Increasing the frequency (1HZ/10second)
90
Increasing the frequency 1HZ/1second
TTC>=110
lasts for 20 seconds. Overheating protection of air-blowing, alarm malfunction to
the indoor, others don’t last.
TC high
te
mperature-preventing control of the indoor heating unit
Tpg_indoor is the highest value of the effective indoor unit (start it and it is in accord with the
running state).
The indoor heat exchanger sensor tests the temperature of the indoor heat exchanger. If the
temperature is higher than 55 , decrease the rotate speed of the compressor and do the high
temperature-preventing protection of the indoor heat exchanger; if the temperature of the indoor
heat exchanger is lower than 47 , recover to the normal control.
7.1.3.2
Functions and control
Domestic air conditioner
18
Содержание Z/N-Series
Страница 11: ... Pinping diagrams Domestic air conditioner 4ˊPinping diagrams 9 ...
Страница 12: ... Operation range Domestic air conditioner 5ˊOperation range 10 ...
Страница 15: ...CN9 CN10 CN36 CN3 CN23 CN24 CN25 CN28 PCB 1 Wiring diagram Domestic air conditioner 13 ...
Страница 16: ...PCB 2 CN1 CN5 CN6 CN7 CN10 CN11 CN8 CN9 CN4 CN3 CN2 Wiring diagram Domestic air conditioner 14 ...
Страница 17: ...Wiring diagram Domestic air conditioner 15 ...
Страница 33: ...Dimensinal drawings Domestic air conditioner 8 Dimensional drawings 9 Center of gravity Outdoor unit 31 ...
Страница 36: ...WARNING CAUTION Installations Domestic air conditioner 34 ...
Страница 37: ...Installations Domestic air conditioner 35 ...
Страница 38: ...Installations Domestic air conditioner 36 ...
Страница 39: ...Installations Domestic air conditioner 37 ...
Страница 40: ...Installations Domestic air conditioner 38 ...
Страница 41: ...Installations Domestic air conditioner 39 ...
Страница 42: ...Installations Domestic air conditioner 40 ...
Страница 45: ...Pressurize for over 3 minutes at 4 2MPa After above Installations Domestic air conditioner 43 ...