11.4.7 The communication fault between IPM and outdoor PCB
Outdoor display: LED1 flash 4 times
Method of Communication is detected by checking the IPM module and the outdoor PCB
Malfunction
Detection
Malfunction
■
The outdoor PCB broken leads to communication fault
Decision
■
The IPM module broken leads to communication fault
Conditions
Supposed
■
The outdoor PCB is broken
Causes
■
The IPM module is broken
■
Communication wiring disconnected
Troubleshooting * Caution Be sure to turn off power switch before connect or disconnect connector, or
else parts damage may be occurred.
1) Check whether Terminal CN23 and CN24 on the outdoor mainboard
CN10 and CN11 on IPM module
2) Check whether the connected wire between IPM and outdoor
Are they good?
Electrify the machine again and turn it
on, Check whether the voltage between
1 and 2 of Terminal CN23 is about DC5V,
Check whether the voltage between2
and 3 of Terminal CN23 is about DC15V,
Replace the outdoor mainboard with a new one
Replace the outdoor IPM module
with a new one.
YES
NO
NO
YES
Malfunction unsolved
1) Pull out and reinsert the terminals.
2) Replace connected wire
Service diagnosis
Domestic air conditioner
56
Содержание Z/N-Series
Страница 11: ... Pinping diagrams Domestic air conditioner 4ˊPinping diagrams 9 ...
Страница 12: ... Operation range Domestic air conditioner 5ˊOperation range 10 ...
Страница 15: ...CN9 CN10 CN36 CN3 CN23 CN24 CN25 CN28 PCB 1 Wiring diagram Domestic air conditioner 13 ...
Страница 16: ...PCB 2 CN1 CN5 CN6 CN7 CN10 CN11 CN8 CN9 CN4 CN3 CN2 Wiring diagram Domestic air conditioner 14 ...
Страница 17: ...Wiring diagram Domestic air conditioner 15 ...
Страница 33: ...Dimensinal drawings Domestic air conditioner 8 Dimensional drawings 9 Center of gravity Outdoor unit 31 ...
Страница 36: ...WARNING CAUTION Installations Domestic air conditioner 34 ...
Страница 37: ...Installations Domestic air conditioner 35 ...
Страница 38: ...Installations Domestic air conditioner 36 ...
Страница 39: ...Installations Domestic air conditioner 37 ...
Страница 40: ...Installations Domestic air conditioner 38 ...
Страница 41: ...Installations Domestic air conditioner 39 ...
Страница 42: ...Installations Domestic air conditioner 40 ...
Страница 45: ...Pressurize for over 3 minutes at 4 2MPa After above Installations Domestic air conditioner 43 ...