Outdoor unit

5.Purging Method:To use vacuum pump

Detach the service port's cap of 3-way valve, the

valve rod's cap for 2-way valve and 3-way's, connect

the service port into the projection of charge hose

(Iow) for gaugemanifold. Then connect the projection

of charge hose (center) for gaugemanifold into

vacuum pump.

3-way valve

Gas Side

12.7mm(1/2")

6.35mm(1/4")

2-way valve

3-way valve

2-way valve

Service port cap

Gaugemanifold(for R410A)

Anti countercurrent joint

Vacuum pump(for R410A)

Tube(for R410A)

Open

Close

Liquid Side

Open the handle at Iow in gaugemanifold, operate

vacuum pump. If the scale-moves of gause (Iow)

reach vacuum condition in a moment, check         again.

Vacuumize for over 15min. And check the level gauge

which should read -0.1 MPa (-76 cm Hg) at Iow

pressure side. After the completion of vacuumizing,

close the handle 'Lo' in gaugemanifold and stop the

operation of the vacuum pump.

Check the condition of the scale and hold it for 1-2min.

If the scale-moves back in spite of tightening, make

flaring work again, the return to the beginning of        .

Open the valve rod for the 2-way valve to an angle of

anticlockwise 90 degrees.

After 6 seconds, close the 2-way valve and make

the inspection of gas leakage.

No gas leakage?

In case of gas leakage, tighten

parts of pipe connection. If

leakage stops, then proceed

steps.

Detach the charge hose from the service port, open

2-way valve and 3-way. Turn the valve rod anticlockwise

until hitting lightly.

To prevent the gas leakage, turn the service port's

cap, the valve rod's cap for 2-way valve and 3-way's

a little more than the point where the torque increases

suddenly.

After attaching the each caps, check the gas leakage

around the caps.

CAUTION:

1.If the refrigerant of the air conditioner leaks, it is necessary to

 discharge all the refrigerant. Vacuumize first, then charge the liquid

 refrigerant into air conditioner according to the amount marked on

 the name plate.

2.Please do not let other cooling medium, except specified one (R410A),

  or air enter into the cooling circulation system. Otherwise, there will be

 abnormal high pressure in the system to make it crack and lead to

  personal injuries.

If it does not stop gas leakage, discharge
whole refrigerants from the service port.
After flaring work again and vacuumize,
fill up prescribed refrigerant from the gas
cylinder

Open

90

O

2-way valve

Valve rod cap

Valve rod cap

3-way valve

2-way valve

6.35mm(1/4")

9.52mm(3/8")

7

3-way valve

2-way valve

6.35mm(1/4")

9.52mm(3/8")

12.7mm(1/2")

12.7mm(1/2")

HSU-09HSA03/R2(DB)
HSU-12HSA03/R2(DB)

HSU-22HSA03/R2(DB)

HSU-18HSA03/R2(DB)

HSU-09HSA103/R2(DB)
HSU-12HSA103/R2(DB)

Содержание HSU-09HSA103

Страница 1: ...een the indoor unit and the floor should be more than 2m more than 10cm more than 10cm more than 10cm Adhesive tape Saddle L S with screws Attention must be paid to the rising up of drain hose Arrange...

Страница 2: ...by rain or direct sunlight and is sufficiently ventilated Place possible to bear the unit where vibration and noise are not increased Place where discharged wind and noise do not cause a nuisance to...

Страница 3: ...by hanging a thread with a weight from the central top of the plate then fasten securely the plate with the attachment steel nail 3 Find the wall hole location A using a measuring tape Find the level...

Страница 4: ...h heat insulation materials closely and make sure fixing with adhesive tape Indoor outdoor electric cable and drain hose must be bound with refrigerant piping by protecting tape Cut away with a nipper...

Страница 5: ...number of indoor and outdoor units carefully If wiring is not correct proper operation can not be carried out and will cause defect 1 If the supply cord is damaged it must be replaced by the manufactu...

Страница 6: ...professional air conditioner engineer Before adding additional refrigerant perform air purging from the refrigerant pipes and indoor unit using a vacuum pump then charge additional refrigerant Half u...

Страница 7: ...leakage No gas leakage In case of gas leakage tighten parts of pipe connection If leakage stops then proceed steps Detach the charge hose from the service port open 2 way valve and 3 way Turn the valv...

Страница 8: ...rried out Please install the drain hose so as to be downward slope without fail Please don t do the drainage as shown below Please pour water in the drain pan of the indoor unit and confirm that drain...

Отзывы: