Haier HSU-09HSA103 Скачать руководство пользователя страница 6

Outdoor unit

1.Installation of Outdoor Unit

3.Connection

4.Attaching Drain-Elbow

2.Connection of pipes

Install according to

To bend a pipe, give the roundness as large as possible not to crush the pipe ,and the bending radius
should be 30 to 40 mm or longer.
Connecting the pipe of gas side first makes working easier.
The connection pipe is specialized for R410A.
The max vertical distance between the indoor unit and the outdoor unit is 5 m.

Be careful that matters, such as wastes of sands, etc. shall not enter the pipe.
The standard pipe length is 5m. If it is over 5m, the function of the unit will be affected. If the pipe has
to be lengthened, the refrigerant should be charged, according to 20 g/m. But the charge of refrigerant
must be conducted by professional air conditioner engineer. Before adding additional refrigerant,
perform air purging from the refrigerant pipes and indoor unit using a vacuum pump,then charge
additional refrigerant.

Half union

Use the same method on indoor unit. Loosen
the screws on terminal block and insert the
plugs fully into terminal block, then tighten the
screws.
Insert the cable according to terminal number
in the same manner as the indoor unit.

If wiring is not correct, proper operation can
not be carried out and controller may be
damaged.
Fix the cable with a clamp.

Drain hose

 If the drain-elbow is used, please attach it as
 figure.

Flare nut

Forced fastening without careful
centering may damage the
threads and cause a leakage of gas.

Pipe Diameter

Fastening torque

Spanner

Torque wrench

 Note: Only for heat pump unit.

Drawing for the installation of indoor and outdoor units

Liquid side 6.35mm(1/4")

18N.m

Gas side 9.52mm(3/8")

Gas side 12.7mm(1/2")

42N.m

55N.m

6

Содержание HSU-09HSA103

Страница 1: ...een the indoor unit and the floor should be more than 2m more than 10cm more than 10cm more than 10cm Adhesive tape Saddle L S with screws Attention must be paid to the rising up of drain hose Arrange...

Страница 2: ...by rain or direct sunlight and is sufficiently ventilated Place possible to bear the unit where vibration and noise are not increased Place where discharged wind and noise do not cause a nuisance to...

Страница 3: ...by hanging a thread with a weight from the central top of the plate then fasten securely the plate with the attachment steel nail 3 Find the wall hole location A using a measuring tape Find the level...

Страница 4: ...h heat insulation materials closely and make sure fixing with adhesive tape Indoor outdoor electric cable and drain hose must be bound with refrigerant piping by protecting tape Cut away with a nipper...

Страница 5: ...number of indoor and outdoor units carefully If wiring is not correct proper operation can not be carried out and will cause defect 1 If the supply cord is damaged it must be replaced by the manufactu...

Страница 6: ...professional air conditioner engineer Before adding additional refrigerant perform air purging from the refrigerant pipes and indoor unit using a vacuum pump then charge additional refrigerant Half u...

Страница 7: ...leakage No gas leakage In case of gas leakage tighten parts of pipe connection If leakage stops then proceed steps Detach the charge hose from the service port open 2 way valve and 3 way Turn the valv...

Страница 8: ...rried out Please install the drain hose so as to be downward slope without fail Please don t do the drainage as shown below Please pour water in the drain pan of the indoor unit and confirm that drain...

Отзывы: