background image

Indoor unit

4.Connecting the indoor/outdoor Electric Cable

Fixing the indoor unit body

Removing the wiring cover

[Other direction piping]

Indoor/outdoor electric cable and drain hose must be bound with refrigerant piping by protecting tape.

Cut away, with a nipper, the lid for piping according to the piping direction and then bend the pipe according
to the position of wall hole. When bending, be careful not to crash pipes.
Connect beforehand the indoor/outdoor electric cable, and then pull out the connected to the heat insulation
of connecting part specially.

Hang surely the unit body onto the upper notches of the
mounting plate. Move the body from side to side to verify
its secure fixing.
In order to fix the body onto the mounting plate,hold up
the body aslant from the underside and then put it down
perpendicularly.

Remove terminal cover at right bottom corner of indoor unit, then
take off wiring cover by removing its screws.

When connecting the cable after installing the indoor unit

1. Insert from outside the room cable into left side of the wall hole, in which

    the pipe has already existed.

2. Pull out the cable on the front side, and connect the cable making a loop.

1. Insert the drain hose into the dent of heat insulation materials of indoor unit.
2. Insert the indoor/outdoor electric cable from backside of indoor unit, and pull it out on the front side, then
    connect them.
3. Coat the flaring seal face with refrigerant oil and connect pipes.
    Cover the connection part with heat insulation materials closely, and make sure fixing with adhesive tape

Heat insulation

material

Drain hose

Piping

Indoor/outdoor

electric cable

Lid for right piping

Lid for under piping

Lid for left piping

Fix with adhesive tape

4

Содержание HSU-09C12 - annexe 1

Страница 1: ...ose Heating insulating material Piping hole cover Arrangement of piping directions Rear left Rear right Left Below Right The marks from to in the figure are the parts numbers The distance between the...

Страница 2: ...Place nearby a power receptacle with enough space around Refer to drawings Place where the distance of more than lm from televisions radios wireless apparatuses and fluorescent lamps can be left In th...

Страница 3: ...ticle When the mounting plate is first fixed for the position of wall hole Fix to side bar and lintel a mounting bar Which is separately sold and then fasten the plate to the fixed mounting bar Make a...

Страница 4: ...aslant from the underside and then put it down perpendicularly Remove terminal cover at right bottom corner of indoor unit then take off wiring cover by removing its screws When connecting the cable a...

Страница 5: ...ables have been properly inserted and tightened After the cable connection never fail to fasten the connected cable with the wiring cover Note When connecting the cable confirm the terminal number of...

Страница 6: ...ng easier The max vertical distance between the indoor unit and the outdoor unit is 5 m Use the same method on indoor unit Loosen the screws on terminal block and insert the plugs fully into terminal...

Страница 7: ...caps on the valves with specified torque Valve rod Valve cap 7 9 20 25 Tighten torque N m During this procedure 50g or 80g only for 22k and 24k unit refrigerant will be discharged in piping This must...

Страница 8: ...nfirm that drainage is carried out surely to outdoor In case that the attached drain hose is in a room please apply heat insulation to it without fail Please kindly explain to our customers how to ope...

Страница 9: ...ber as Izquierda Trasera izquierda Trasera derecha Derecha Debajo m s de 10 cm m s de 5 cm m s de 10 cm Debe prestarse atenci n a que la manguera de drenaje no quede elevada m s de 10 cm m s de 10 cm...

Страница 10: ...y no aumentar las vibraciones ni el ruido La zona deber ser una en la que el ruido y el viento emitido no provoquen perturbaciones a los vecinos La zona ser una en la que una distancia marcada est dis...

Страница 11: ...a de montaje por vez primera para la situaci n del orificio en la pared 2 Perforaci n de la pared y ajuste de la tapa del orificio de la tuber a Hacer un orificio de 60 mm de di metro descendiendo lev...

Страница 12: ...ar el conectado al aislamiento t rmic de la pieza de conexi n Ajuste de la carcasa de la unidad interior Colgar con seguridad la unidad en las muescas de la placa de montaje Mover la unidad de lado a...

Страница 13: ...tituido por el fabricante o su agente de mantenimiento o una persona con cualificaci n similar El tipo de cable de conexi n es H05 07RN F o 245IEC57 YZW 2 Si el fusible de la placa PC est roto cambiar...

Страница 14: ...illos Introducir el cable de acuerdo al n mero del terminal de la misma forma que la unidad interior Si el cableado no es correcto no podr haber un funcionamiento correcto y puede estropearse el contr...

Страница 15: ...i n especificada 5 Ajustar las tapas en las v lvulas con la fuerza de torsi n especificada Torsi n de ajuste N m V stago de v lvula 7 9 Tapa de v lvula 20 25 Cuando el tubo de conexi n excede los 5 me...

Страница 16: ...sma aislamiento t rmico total Verificaci ndeinstalaci nypuestaapunto Explicar amablemente a nuestros clientes el modo de utilizaci n del aparato empleando el manual de instrucciones Verificarelementos...

Отзывы: