background image

Forced fastening without careful centering

may damage the threads and cause a

leakage of gas.

Pipe Diameter   (     )

Liquid side  6.35mm(1/4")

Gas side  9.52mm(3/8")

Fastening torque

18N.m

40N.m

Gas side  12.7mm(1/2")

50N.m

Gas side  15.88mm(5/8")

60N.m

Liquid side  9.52mm(3/8")

40N.m

Outdoor unit

1.Installation of Outdoor Unit

3.Connection

4.Attaching Drain-Elbow

2.Connection of pipes

Install according to

To bend a pipe, give the roundness as large as possible not to crush the pipe
Connecting the pipe of gas side first makes working easier.
The max vertical distance between the indoor unit and the outdoor unit is 5 m.

Use the same method on indoor unit. Loosen the screws on terminal block and insert the  plugs fully into

terminal block, then tighten the screws.

If wiring is not correct, proper operation can not be carried out and controller may be damaged.

 If the drain-elbow is used, please attach it as

 figure. (Note: Only for heat pump unit.)

Drawing for the installation of indoor and outdoor units

Insert the cable according to terminal number in the same manner as the indoor unit.

Fix the cable with a clamp.

Half union

Flare nut

Spanner

Torque wrench

Outdoor unit

Be careful that matters, such as wastes of sands, etc. shall not enter the pipe.

6

Содержание HSU-09C12 - annexe 1

Страница 1: ...ose Heating insulating material Piping hole cover Arrangement of piping directions Rear left Rear right Left Below Right The marks from to in the figure are the parts numbers The distance between the...

Страница 2: ...Place nearby a power receptacle with enough space around Refer to drawings Place where the distance of more than lm from televisions radios wireless apparatuses and fluorescent lamps can be left In th...

Страница 3: ...ticle When the mounting plate is first fixed for the position of wall hole Fix to side bar and lintel a mounting bar Which is separately sold and then fasten the plate to the fixed mounting bar Make a...

Страница 4: ...aslant from the underside and then put it down perpendicularly Remove terminal cover at right bottom corner of indoor unit then take off wiring cover by removing its screws When connecting the cable a...

Страница 5: ...ables have been properly inserted and tightened After the cable connection never fail to fasten the connected cable with the wiring cover Note When connecting the cable confirm the terminal number of...

Страница 6: ...ng easier The max vertical distance between the indoor unit and the outdoor unit is 5 m Use the same method on indoor unit Loosen the screws on terminal block and insert the plugs fully into terminal...

Страница 7: ...caps on the valves with specified torque Valve rod Valve cap 7 9 20 25 Tighten torque N m During this procedure 50g or 80g only for 22k and 24k unit refrigerant will be discharged in piping This must...

Страница 8: ...nfirm that drainage is carried out surely to outdoor In case that the attached drain hose is in a room please apply heat insulation to it without fail Please kindly explain to our customers how to ope...

Страница 9: ...ber as Izquierda Trasera izquierda Trasera derecha Derecha Debajo m s de 10 cm m s de 5 cm m s de 10 cm Debe prestarse atenci n a que la manguera de drenaje no quede elevada m s de 10 cm m s de 10 cm...

Страница 10: ...y no aumentar las vibraciones ni el ruido La zona deber ser una en la que el ruido y el viento emitido no provoquen perturbaciones a los vecinos La zona ser una en la que una distancia marcada est dis...

Страница 11: ...a de montaje por vez primera para la situaci n del orificio en la pared 2 Perforaci n de la pared y ajuste de la tapa del orificio de la tuber a Hacer un orificio de 60 mm de di metro descendiendo lev...

Страница 12: ...ar el conectado al aislamiento t rmic de la pieza de conexi n Ajuste de la carcasa de la unidad interior Colgar con seguridad la unidad en las muescas de la placa de montaje Mover la unidad de lado a...

Страница 13: ...tituido por el fabricante o su agente de mantenimiento o una persona con cualificaci n similar El tipo de cable de conexi n es H05 07RN F o 245IEC57 YZW 2 Si el fusible de la placa PC est roto cambiar...

Страница 14: ...illos Introducir el cable de acuerdo al n mero del terminal de la misma forma que la unidad interior Si el cableado no es correcto no podr haber un funcionamiento correcto y puede estropearse el contr...

Страница 15: ...i n especificada 5 Ajustar las tapas en las v lvulas con la fuerza de torsi n especificada Torsi n de ajuste N m V stago de v lvula 7 9 Tapa de v lvula 20 25 Cuando el tubo de conexi n excede los 5 me...

Страница 16: ...sma aislamiento t rmico total Verificaci ndeinstalaci nypuestaapunto Explicar amablemente a nuestros clientes el modo de utilizaci n del aparato empleando el manual de instrucciones Verificarelementos...

Отзывы: