background image

14

                                  Run or start capacitor defective                       Replace
                                  Loose connection                                             Check and tighten all connections.
Condenser fan runs,  Compressor stuck, grounded or open               Wait for 2 hours for overload to reset.
compressor doesn't   motor winding, open internal overload            Replace compressor if still open.
                                  Low voltage condition                                     At compressor terminals, voltage must be within 10% of rating
                                                                                                           plate volts when unit is running.
                                  Low voltage condition                                     Add start kit components
                                  Incorrect voltage                                              At compressor terminals, voltage must be within 10% of rating
Compressor                                                                                        plate volts when unit is running.
short-cycling             Defective overload protector                           Replace - check for correct voltage
                                  Refrigerant undercharge                                   Add refrigerant
Register sweat           Low evaporator airflow                                   Increase blower speed or reduce restriction - replace air filter
                                  Restriction in liquid line,                                 Replace defective components
 High head - Low     metering device or filter drier
vapor pressures         Flowrator piston size too small                        Change to correct size piston
                                  Incorrect capillary tubes                                   Change coil assembly
                                  Blocked outdoor coil                                        Clear away leaves and other debris
High head - High      Refrigerant overcharge                                    Correct system charge
 or normal vapor       Condenser fan not running                                Repair or replace
 pressures                  Air, non-condensibles or                                   Recover refrigerant, evacuate &
                                  moisture in system                                            recharge, add filter drier
Low head - High      Flowrator piston size too large                         Change to correct size piston
vapor pressures         Defective compressor valves                           Replace compressor
                                  Incorrect capillary tubes                                  Replace coil assembly
Low vapor - cool      Low evaporator airflow                                   Increase blower speed or reduce restriction - replace air filter
 compressor - iced    Operating below 65  F outdoors                      Add low ambient kit
evaporator coil          Moisture in the system                                    Recover refrigerant, evacuate & recharge, add filter drier
High vapor                Excessive load                                                 Recheck load calculation
pressure                     Defective compressor                                      Replace
Fluctuating head        Air or non-condensibles in system                  Recover refrigerant, evacuate & recharge.
and vapor pressures
Pulsing noise at         Air or non-condensibles in system                  Recover refrigerant, evacuate & recharge
metering device
or liquid line

                                  Power off or loose electrical connection         Make sure main switch is ON. Check and tighten all connections.
                                  Incorrect thermostat setting                             Set thermostat correctly
No cooling/heating   Defective contactor                                          Check for 24V at contactor coil.
                                  Open circuit breaker of blown fuses                Reset or replace
                                  Defective transformer                                      Check wiring - Replace it.
                                  Interconnecting low voltage wiring damage    Replace thermostat wiring
                                  Dirty filters                                                      Clean & replace
                                  Indoor air blockage                                          Check supply registers and return grills for blockage.
                                  Blocked outdoor coil                                       Clear away leaves and other debris
                                  Improperly sized unit                                       Recalculate load
Insufficient Cooling  Improper airflow                                              Check - should be 400CFM/Ton
/Heating                    Incorrect refrigerant charge                              Charge correctly per instruction.
                                  Air, non-condensibles or moisture in system   Recover refrigerant, evacuate & recharge, add filter drier
                                  Incorrect voltage                                              At compressor terminals, voltage must be within
                                                                                                           10% of rating plate volts when unit is running.
Water on floor or in
furnace                      Blocked condensate drain and "P" trap           Remove blockage

Symptom

Possible Cause

 Remedy

Defective four way valve

Check the valve coil or replace it

Содержание HR18D2VAR

Страница 1: ...No 0010578573 HR18D2VAR HR24D2VAR HR30D2VAR 13 SEER 1 5 to 3 0 Ton HR36D2VAR ...

Страница 2: ...ese instructions thoroughly before attempting installation or operation Failure to follow these instructions may result in improper installation adjustment service or maintenance possibly resulting in fire electrical shock property damage personal injury or death This product is designed and manufactured to permit installation in accordance with National Codes It is the installer s responsibility ...

Страница 3: ...stallation can result in unsatisfactory operation or dangerous conditions Carefully read this manual and any instructions packaged with separate equipment required to make up the system prior to installation Give this manual to the owner and explain its provisions The owner should retain this manual for future reference 2 NOMENCLATURE FOR MODEL NUMBER H Brand symbol H Haier R System type C Air con...

Страница 4: ... e N W g k s b L t h g i e 6 8 9 8 1 8 7 2 7 1 g n i p p i h S x o r p p A W 7 8 1 g k s b L t h g i e 3 9 5 0 2 5 8 The dimensions for the condensing unit are illustrated in Figure 1 Physical and electrical specifications are provided in Table 1 for 13 SEER systems respectively The Figure 2 show a schematic of a heat pump on the cooling cycle and the heating cycle Table 1 Model HR18 36D2VAR L E D...

Страница 5: ...ating Capacity HSPF CFM 10 0 10 20 30 40 50 60 HR18D2VAR HB2400VD1M20 M 15000 7 8 670 4773 6418 8036 9682 11272 73 13264 15627 18000 HR24D2VAR HB2400VD1M20 H 20000 7 8 900 6364 8558 10715 12909 15030 17685 20836 24000 HR30D2VAR HB3600VD1M22 L 26000 7 8 1125 8273 11125 13930 16782 19539 22990 27087 31200 HR36D2VAR HB3600VD1M22 H 32500 7 8 1240 10341 13906 17412 20977 24424 28738 33859 39000 Table 2...

Страница 6: ...TDOOR COIL COMPRESSOR SERVICE PORT ACCUMULATOR HIGH PRESSURE SWITCH LOW PRESSURE DEFROSED SENSOR CHECK VALVE ORIFICE DRIER optional Heating REVERSING VALVE R E S N E D N O C R O T A R O P A V E REVERSING VALVE R E S N E D N O C R O T A R O P A V E CHECK VALVE ORIFICE SERVICE VALVE SERVICE PORT SERVICE VALVE SERVICE PORT CHECK VALVE ORIFICE DISTRIBUTOR DISTRIBUTOR Warning The Bi flow drier is stron...

Страница 7: ...trical power to the unit before servicing Disconnect power to both the indoor and outdoor units NOTE There may be more than one electrical disconnect switch Failure to shut off power can cause electrical shock resulting in personal injury or death Frequent washing of the cabinet fan blade and coil with fresh water Regular cleaning and waxing of the cabinet with good automobile polish A good liquid...

Страница 8: ...ns are made from the service access area The most common application will find the unit best located about 10 from back wall with connection side facing the wall This application minimizes exposed tubing and wiring minimizing the space for youngsters to run around the unit with subsequent damage to the tubing or wiring In more confined application spaces such as corners provide a minimum of 10 cle...

Страница 9: ...not kink or twist the tubing Refrigerant piping should not be installed in a cement slab as this limits access to the refrigerant should a leak be suspected To ensure good oil return to the compressor it is important to pitch the horizontal suction line toward the compressor approximately 1 2 for every 10 of line Line Insulation Suction line requires insulation in order to prevent condensation fro...

Страница 10: ...ndoor unit is below the outdoor unit Figure 4 A and 50 when the indoor unit is above the outdoor unit Figure 4 B To ensure good oil return to the compressor when the indoor unit is below the outdoor unit suction line oil trap should be used as illustrated in Figure 4 A Tubing Connections CAUTION Use extreme caution in removing the caps from the suction and liquid line fittings as there is pressure...

Страница 11: ...rough the tubing while brazing 7 After brazing quench with a wet rag to cool the joint Reinstall the Schrader core in the valve if removed for brazing 8 Pressurize the lines to 150 psi maximum with dry nitrogen Check for leaks at all joints with liquid detergent If a leak is found repair it after removing the nitrogen Repeat the process and re ckeck 9 Do not purge the lines with refrigerant Evacua...

Страница 12: ...microns If unable to obtain 500 microns or vacuum rises above 800 microns over 15 minutes period discontinue evacuation pressurize and check for leaks Repair any leaks found and repeat the step 2 3 Close valve to the vacuum pump and stop pump 4 When sure of a tight well evacuated system charge with refrigerant Charging the System For systems with capillary tube or fixed orifice metering device Bef...

Страница 13: ...5 5 ...

Страница 14: ...he condensing unit control wiring requires a 24 Volt minimum 25 VA service from the indoor transformer as shown on the wiring diagram 7 SYSTEM STARTUP 1 Turn thermostat to OFF turn on power supply at disconnect switch 2 Turn temperature setting as high as it will go 3 Turn fan switch to ON Indoor blower should run Be sure it is running in the right direction 4 Turn fan switch to AUTO Turn system s...

Страница 15: ...Table 7 included in this manual P14 9 3 Wiring Diagram Refer to the appropriate wiring diagram included in this manual P15 Table 7 Troubleshooting Guide WARNING Disconnect all electrical power to the unit before servicing Disconnect power to both the indoor and outdoor units NOTE There may be more than one electrical disconnect switch Failure to shut off power can cause electrical shock resulting ...

Страница 16: ...vapor cool Low evaporator airflow Increase blower speed or reduce restriction replace air filter compressor iced Operating below 65 F outdoors Add low ambient kit evaporator coil Moisture in the system Recover refrigerant evacuate recharge add filter drier High vapor Excessive load Recheck load calculation pressure Defective compressor Replace Fluctuating head Air or non condensibles in system Rec...

Страница 17: ...HR18 36D2VAR 15 YL GR ...

Страница 18: ...Made in P R C ...

Отзывы: