Provide a level concrete slab. To prevent transmission of noise or vibration, slab should not be connected
to building structure. Some sort of sound-absorbing material should be placed between the condenser
and the slab. A good material to use is rubber and cork pad.

For rooftop application, make sure the building construction can support the weight and that proper
consideration is given to the weather-tight integrity of the roof. The condensing unit contains moving
parts and can vibrate. Therefore, sound is also a consideration in rooftop applications.

6

! WARNING

 - Install the unit securely in a place that can bear the weight of the unit. When installed

in an insufficiently strong place, the unit could fall causing injury.

6.2.UNIT CLEARANCES

The minimum clearances for the unit are illustrated in 

Figure 3

. Condenser air enters from three sides.

Air discharges upward from the top of the unit. Refrigerant tube and electrical connections are made
from the service access area. The most common application will find the unit best located about 10"
from back wall with connection side facing the wall. This application minimizes exposed tubing and
wiring, minimizing the space for youngsters to run around the unit with subsequent damage to the
tubing or wiring.

In more confined application spaces, such as corners provide a minimum of 10" clearance on all air
inlet sides. For service access to the compressor and control box, allow 18" minimum clearance. Ensure
top is unobstructed. If units are to be located under an overhang, there should be a minimum of 36"
clearance and provision made to deflect the warm discharge air out from the overhang.

In order to have an unrestricted air flow, owners should be advised to avoid lawn mower discharge
toward the unit depositing debris on the fin coil surface reducing the unit efficiency.

6.3.REFRIGERANT PIPING

The refrigerant piping is very important as it affects the proper operation and efficiency of the air
conditioning system. Note the following guidelines:

10" Min.

Service Access

    18" Min.

Figure 3

10" Min.

10"

10"

Service Access

    18" Min.

Содержание HR18D2VAE

Страница 1: ...No 0150505381 D HR18D2VAE HR24D2VAE HR30D2VAE 13 SEER 1 5 to 5 0 Tons HR36D2VAE HR42D1VAE HR48D1VAE HR60D1VAE ...

Страница 2: ... vary due to the passage of new laws we suggest that any work on this unit be done by a certified technician Should you have any questions please contact the local EPA office The manufacturer s warranty does not cover any damage or defect to the air conditioner caused by the attachment or use of any components accessories or devices other than those authorized by the manufacturer into onto or in c...

Страница 3: ...eat Pump Improper installation can result in unsatisfactory operation or dangerous conditions Carefully read this manual and any instructions packaged with separate equipment required to make up the system prior to installation Give this manual to the owner and explain its provisions The owner should retain this manual for future reference H R 24 D 2 V A E Example HR24D2VAE Design series 1 1st Gen...

Страница 4: ... 3 0 3 4 1 4 2 4 1 4 2 1 7 7 6 1 6 6 1 6 8 3 0 3 4 1 4 2 4 1 4 2 1 7 7 6 1 6 6 1 6 8 3 0 3 4 1 4 2 4 1 4 2 1 7 7 6 1 6 6 1 6 8 3 0 3 4 1 4 2 4 1 4 2 1 7 7 6 1 6 6 1 6 8 1 6 3 8 5 0 3 8 5 0 3 7 1 9 9 7 7 9 7 7 0 4 8 5 0 3 8 5 0 3 7 1 0 1 9 7 7 9 7 7 4 4 8 5 0 3 8 5 0 3 7 1 1 1 9 7 7 9 7 7 2 3 8 7 6 2 8 7 6 2 3 1 8 2 8 6 2 8 6 2 3 8 7 6 2 8 7 6 2 3 1 8 2 8 6 2 8 6 2 3 8 7 6 2 8 7 6 2 3 1 8 2 8 6 2 8...

Страница 5: ...500 56638 55775 54913 54050 ARI data of indoor Cooling Capacity with different outdoor temperature Outdoor Indoor Indoor fan speed Capacity HSPF CFM 10 0 10 20 30 40 50 60 HR18D2VAE HB2400VD2M20 M 16800 7 7 670 5568 7488 9376 11295 13152 15474 18232 21000 HR24D2VAE HB2400VD2M20 H 22000 7 7 900 7000 9413 11787 14200 16533 19453 22920 26400 HR30D2VAE HB3600VD2M20 T L 27800 7 7 1125 8845 11895 14894 ...

Страница 6: ...R Cooling SERVICE VALVE SERVICE PORT DISCHARGE TEMP SENSOR INDOOR COIL DISTRIBUTOR OUTDOOR COIL COMPRESSOR SERVICE PORT ACCUMULATOR HIGH PRESSURE SWITCH LOW PRESSURE DEFROST SENSOR DRIER Heating REVERSING VALVE R E S N E D N O C R O T A R O P A V E REVERSING VALVE R E S N E D N O C R O T A R O P A V E SERVICE VALVE SERVICE PORT SERVICE VALVE SERVICE PORT DISTRIBUTOR DISTRIBUTOR SWITCH SWITCH CHECK...

Страница 7: ...trical power to the unit before servicing Disconnect power to both the indoor and outdoor units NOTE There may be more than one electrical disconnect switch Failure to shut off power can cause electrical shock resulting in personal injury or death Frequent washing of the cabinet fan blade and coil with fresh water Regular cleaning and waxing of the cabinet with good automobile polish A good liquid...

Страница 8: ...ns are made from the service access area The most common application will find the unit best located about 10 from back wall with connection side facing the wall This application minimizes exposed tubing and wiring minimizing the space for youngsters to run around the unit with subsequent damage to the tubing or wiring In more confined application spaces such as corners provide a minimum of 10 cle...

Страница 9: ...not kink or twist the tubing Refrigerant piping should not be installed in a cement slab as this limits access to the refrigerant should a leak be suspected To ensure good oil return to the compressor it is important to pitch the horizontal suction line toward the compressor approximately 1 2 for every 10 of line Line Insulation Suction line requires insulation in order to prevent condensation fro...

Страница 10: ...strated in Figure 4 B 1 Tubing Connections CAUTION Use extreme caution in removing the caps from the suction and liquid line fittings as there is pressure present A fitting is on the liquid line to remove pressure CAUTION Heat Pumps are charged with refrigerant Heat Pump liquid and suction valves are closed to contain the charge within the unit Do not force the valve stem against the retaining rin...

Страница 11: ...h with a wet rag to cool the joint Reinstall the Schrader core in the valve if removed for brazing 8 Pressurize the lines to 150 psi maximum with dry nitrogen Check for leaks at all joints with liquid detergent If a leak is found repair it after removing the nitrogen Repeat the process and re ckeck 9 Do not purge the lines with refrigerant Evacuate the lines and indoor coil Refrigerant Metering De...

Страница 12: ...e outdoor unit and indoor coil must be an approved match per the unit specification The indoor conditions should be within 2 F of the desired comfort conditions WARNING Do not vent refrigerant to the atmosphere It is a violation of federal law to do so If the refrigerant needs to be removed from a system to correct the charge inside always use a recovery or recycling device WARNING To prevent pers...

Страница 13: ...5 11 ...

Страница 14: ...he condensing unit control wiring requires a 24 Volt minimum 25 VA service from the indoor transformer as shown on the wiring diagram 7 SYSTEM STARTUP 1 Turn thermostat to OFF turn on power supply at disconnect switch 2 Turn temperature setting as high as it will go 3 Turn fan switch to ON Indoor blower should run Be sure it is running in the right direction 4 Turn fan switch to AUTO Turn system s...

Страница 15: ...Table 7 included in this manual P14 9 3 Wiring Diagram Refer to the appropriate wiring diagram included in this manual P15 Table 7 Troubleshooting Guide WARNING Disconnect all electrical power to the unit before servicing Disconnect power to both the indoor and outdoor units NOTE There may be more than one electrical disconnect switch Failure to shut off power can cause electrical shock resulting ...

Страница 16: ...bes Replace coil assembly Low vapor cool Low evaporator airflow Increase blower speed or reduce restriction replace air filter compressor iced Operating below 65 F outdoors Add low ambient kit evaporator coil Moisture in the system Recover refrigerant evacuate recharge add filter drier High vapor Excessive load Recheck load calculation pressure Defective compressor Replace Fluctuating head Air or ...

Страница 17: ...HR18 36D2VAE HR42 60D1VAE 15 3 ...

Отзывы: