background image

Figure 1

3

D

W

H

Table2: System Capacity

cooling

heating

Capacity

SEER

CFM

80

85

90

95

100

105

110

115

HR18D2VAE HB2400VD

2

M20

M

18000

13

670

20340

19746

19080

18000

17730

17460

17190

16920

HR24D2VAE HB2400VD

2

M20

H

24000

13

900

27120

26328

25440

24000

23640

23280

22920

22560

HR30D2VAE HB3600VD2M20-T

L

30000

13

1125

33900

32910

31800

30000

29550

29100

28650

28200

HR36D2VAE HB3600VD2M20-T

H

34000

13

1300

38420

37298

36040

34000

33490

32980

32470

31960

HR42D1VAE HB4800VD

3

M22

L

41000

13

1480

46330

44977

43460

41000

40385

39770

39155

38540

HR48D1VAE HB4800VD

3

M22

H

47500

13

1560

53675

52108

50350

47500

46788

46075

45363

44650

HR60D1VAE HB6000VD1M22-T

H

57500

13

1730

64975

63078

60950

57500

56638

55775

54913

54050

ARI data of indoor

Cooling Capacity with different outdoor temperature

Outdoor 

Indoor

Indoor fan speed

Capacity

HSPF

CFM

-10

0

10

20

30

40

50

60

HR18D2VAE HB2400VD

2

M20

M

1

68

00

7.7

670

5568

7488

9376

11295

13152

15474

18232

21000

HR24D2VAE HB2400VD

2

M20

H

22000

7.7

900

7000

9413

11787

14200

16533

19453

22920

26400

HR30D2VAE HB3600VD2M20-T

L

27800

7.7

1125

8845

11895

14894

17944

20892

24582

28963

33360

HR36D2VAE HB3600VD2M20-T

H

32000

7.7

1300

10182

13692

17144

20655

24048

28296

33338

38400

HR42D1VAE HB4800VD

3

M22

L

41000

7.7

1480

13045

17543

21966

26464

30812

36254

42715

49200

HR48D1VAE HB4800VD

3

M22

H

47500

7.7

1560

15114

20324

25448

30659

35697

42001

49486

57000

HR60D1VAE HB6000VD1M22-T

H

57000

7.7

1730

18136

24389

30538

36791

42836

50402

59384

68400

Outdoor 

Indoor

Indoor fan speed

ARI data of indoor

Heating Capacity with different outdoor temperature

Содержание HR18D2VAE

Страница 1: ...No 0150505381 D HR18D2VAE HR24D2VAE HR30D2VAE 13 SEER 1 5 to 5 0 Tons HR36D2VAE HR42D1VAE HR48D1VAE HR60D1VAE ...

Страница 2: ... vary due to the passage of new laws we suggest that any work on this unit be done by a certified technician Should you have any questions please contact the local EPA office The manufacturer s warranty does not cover any damage or defect to the air conditioner caused by the attachment or use of any components accessories or devices other than those authorized by the manufacturer into onto or in c...

Страница 3: ...eat Pump Improper installation can result in unsatisfactory operation or dangerous conditions Carefully read this manual and any instructions packaged with separate equipment required to make up the system prior to installation Give this manual to the owner and explain its provisions The owner should retain this manual for future reference H R 24 D 2 V A E Example HR24D2VAE Design series 1 1st Gen...

Страница 4: ... 3 0 3 4 1 4 2 4 1 4 2 1 7 7 6 1 6 6 1 6 8 3 0 3 4 1 4 2 4 1 4 2 1 7 7 6 1 6 6 1 6 8 3 0 3 4 1 4 2 4 1 4 2 1 7 7 6 1 6 6 1 6 8 3 0 3 4 1 4 2 4 1 4 2 1 7 7 6 1 6 6 1 6 8 1 6 3 8 5 0 3 8 5 0 3 7 1 9 9 7 7 9 7 7 0 4 8 5 0 3 8 5 0 3 7 1 0 1 9 7 7 9 7 7 4 4 8 5 0 3 8 5 0 3 7 1 1 1 9 7 7 9 7 7 2 3 8 7 6 2 8 7 6 2 3 1 8 2 8 6 2 8 6 2 3 8 7 6 2 8 7 6 2 3 1 8 2 8 6 2 8 6 2 3 8 7 6 2 8 7 6 2 3 1 8 2 8 6 2 8...

Страница 5: ...500 56638 55775 54913 54050 ARI data of indoor Cooling Capacity with different outdoor temperature Outdoor Indoor Indoor fan speed Capacity HSPF CFM 10 0 10 20 30 40 50 60 HR18D2VAE HB2400VD2M20 M 16800 7 7 670 5568 7488 9376 11295 13152 15474 18232 21000 HR24D2VAE HB2400VD2M20 H 22000 7 7 900 7000 9413 11787 14200 16533 19453 22920 26400 HR30D2VAE HB3600VD2M20 T L 27800 7 7 1125 8845 11895 14894 ...

Страница 6: ...R Cooling SERVICE VALVE SERVICE PORT DISCHARGE TEMP SENSOR INDOOR COIL DISTRIBUTOR OUTDOOR COIL COMPRESSOR SERVICE PORT ACCUMULATOR HIGH PRESSURE SWITCH LOW PRESSURE DEFROST SENSOR DRIER Heating REVERSING VALVE R E S N E D N O C R O T A R O P A V E REVERSING VALVE R E S N E D N O C R O T A R O P A V E SERVICE VALVE SERVICE PORT SERVICE VALVE SERVICE PORT DISTRIBUTOR DISTRIBUTOR SWITCH SWITCH CHECK...

Страница 7: ...trical power to the unit before servicing Disconnect power to both the indoor and outdoor units NOTE There may be more than one electrical disconnect switch Failure to shut off power can cause electrical shock resulting in personal injury or death Frequent washing of the cabinet fan blade and coil with fresh water Regular cleaning and waxing of the cabinet with good automobile polish A good liquid...

Страница 8: ...ns are made from the service access area The most common application will find the unit best located about 10 from back wall with connection side facing the wall This application minimizes exposed tubing and wiring minimizing the space for youngsters to run around the unit with subsequent damage to the tubing or wiring In more confined application spaces such as corners provide a minimum of 10 cle...

Страница 9: ...not kink or twist the tubing Refrigerant piping should not be installed in a cement slab as this limits access to the refrigerant should a leak be suspected To ensure good oil return to the compressor it is important to pitch the horizontal suction line toward the compressor approximately 1 2 for every 10 of line Line Insulation Suction line requires insulation in order to prevent condensation fro...

Страница 10: ...strated in Figure 4 B 1 Tubing Connections CAUTION Use extreme caution in removing the caps from the suction and liquid line fittings as there is pressure present A fitting is on the liquid line to remove pressure CAUTION Heat Pumps are charged with refrigerant Heat Pump liquid and suction valves are closed to contain the charge within the unit Do not force the valve stem against the retaining rin...

Страница 11: ...h with a wet rag to cool the joint Reinstall the Schrader core in the valve if removed for brazing 8 Pressurize the lines to 150 psi maximum with dry nitrogen Check for leaks at all joints with liquid detergent If a leak is found repair it after removing the nitrogen Repeat the process and re ckeck 9 Do not purge the lines with refrigerant Evacuate the lines and indoor coil Refrigerant Metering De...

Страница 12: ...e outdoor unit and indoor coil must be an approved match per the unit specification The indoor conditions should be within 2 F of the desired comfort conditions WARNING Do not vent refrigerant to the atmosphere It is a violation of federal law to do so If the refrigerant needs to be removed from a system to correct the charge inside always use a recovery or recycling device WARNING To prevent pers...

Страница 13: ...5 11 ...

Страница 14: ...he condensing unit control wiring requires a 24 Volt minimum 25 VA service from the indoor transformer as shown on the wiring diagram 7 SYSTEM STARTUP 1 Turn thermostat to OFF turn on power supply at disconnect switch 2 Turn temperature setting as high as it will go 3 Turn fan switch to ON Indoor blower should run Be sure it is running in the right direction 4 Turn fan switch to AUTO Turn system s...

Страница 15: ...Table 7 included in this manual P14 9 3 Wiring Diagram Refer to the appropriate wiring diagram included in this manual P15 Table 7 Troubleshooting Guide WARNING Disconnect all electrical power to the unit before servicing Disconnect power to both the indoor and outdoor units NOTE There may be more than one electrical disconnect switch Failure to shut off power can cause electrical shock resulting ...

Страница 16: ...bes Replace coil assembly Low vapor cool Low evaporator airflow Increase blower speed or reduce restriction replace air filter compressor iced Operating below 65 F outdoors Add low ambient kit evaporator coil Moisture in the system Recover refrigerant evacuate recharge add filter drier High vapor Excessive load Recheck load calculation pressure Defective compressor Replace Fluctuating head Air or ...

Страница 17: ...HR18 36D2VAE HR42 60D1VAE 15 3 ...

Отзывы: