Wiring work
(AU182XFERA AU222XFERA AU252XGERA)
21
5. Example wiring diagram.
The distance between the signal wires and the power cables should be at least 50mm.
Please refer to the indoor unit installation manual to find detailly how to set and check the communication
address.
Incorrect address setting will cause abnormal to the system.
6. After installation, please fill in the following table for easy daily maintenance:
Indoor unit NO.
A
B
C
Model of indoor unit
Serial no.
Room name
Power supply cable: H05RN-F 3G 4.0mm
2
Communication cable (Shield wire): H05RN-F 2X1.5mm
2
Connecting cable : H05RN-F 3G 2.5mm
2
C
B
A
Q
P
1(L) 2(N)
1PH, 220-230V~, 50Hz
L
N
N
L
C1 C2
25A
P
Q
(P Q)
Indoor unit C
Indoor unit B
Indoor unit A
Outdoor unit