- The installation of pipe-work shall be kept to a minimum.

-  Pipe-work shall be protected from physical damage and shall not be installed in an unventilated space, if that space is 

smaller than Amin(2m2).

    - Compliance with national gas regulations shall be observed.

    -  Mechanical connections shall be accessible for maintenance purposes.

- The minimum floor area of the room: 2 m2. 

    - The maximum refrigerant charge amount: 1.7 kg.

    - Information for handling, installation, cleaning, servicing and disposal of refrigerant.

    - Warning: Keep any required ventilation openings clear of obstruction.

    - Notice: Servicing shall be performed only as recommended by the manufacturer.

Unventilated areas

    - Warning: The appliance shall be stored in a well-ventilated area where the room size corresponds to the room area as 

specified.

    - Warning: The appliance shall be stored in a room without continuously operating open flames (e.g. an operating gas 

appliance) and ignition sources (e.g. an operating electric heater).

Qualification of workers

    - Specific information about the required qualification of the working personnel for maintenance, service and repair 

operations.

    -  Warning: Every working procedure that affects safety means shall only be carried out by competent persons.

    Examples for such working procedures are:

         - breaking into the refrigerating circuit.

         - opening of sealed components

         - opening of ventilated enclosures.

Information on servicing

    - Prior to beginning work on systems, safety checks are necessary to ensure that the risk of ignition is minimized.

    - Work shall be undertaken under a controlled procedure so as to minimized the risk of flammable gas or vapor being 

present while the work is being performed.

 - Work in confined spaces shall be avoided. The area around the workspace shall be sectioned off. Ensure that the conditions 

within the area have been made safe by control of flammable material.

Checking for presence of refrigerant

-  The area shall be checked with an appropriate refrigerant detector prior to and during work. The leak detection equipment 

should be suitable for use with all applicable refrigerants, i.e. non-sparking, adequately sealed or intrinsically safe.

Presence of fire extinguisher

    - If any hot work is to be conducted, appropriate fire extinguishing equipment shall be available to hand. Have a dry powder 

or CO2 fire extinguisher adjacent to the charging area.

No ignition sources

    - All possible ignition sources, including cigarette smoking, should be kept sufficiently far away from the site of installation, 

repairing, removing and disposal. Prior to work taking place, the area around the equipment is to be surveyed to make sure 

that there are no flammable hazards or ignition risks. “No Smoking” signs shall be displayed.

Ventilated area

    - Ensure that the area is in the open or that it is adequately ventilated before breaking into the system or conducting any hot 

work. A degree of ventilation shall continue during the period that the work is carried out. The ventilation should safely disperse 

any released  refrigerant and preferably expel it externally into the atmosphere.

Checks to the refrigeration equipment

    - Where electrical components are being changed, they shall be fit for the purpose and to the correct specification. At all 

times the manufacturer’s maintenance and service guidelines shall be followed. If in doubt, consult the manufacturer’s 

technical department for assistance.

The following checks shall be applied to installations

-  The charge size is in accordance with the room size within which the refrigerant containing parts are installed;

    - The ventilation machinery and outlets are operating adequately and are not obstructed; 

    - If an indirect refrigerating circuit is being used, the secondary circuit shall be checked for the presence of refrigerant;

    - Marking to the equipment continues to be visible and legible. Markings and signs that are illegible shall be corrected;

    - Refrigeration pipe or components are installed in a position where they are unlikely to be exposed to any substance which 

may corrode refrigerant containing components, unless the components are constructed of materials which are inherently 

resistant to being corroded or are suitably protected against being so corroded. 

Cautions

23

Содержание AB25S2SC1FA

Страница 1: ... AB35S2SC1FA Uih cbg IUfhg UbX ibWh cbg HdYfUh cb MfciV Yg cch b ighcaYf GYYX hc _bck FU bhYbUbWY BbghU Uh cb IfcWYXifY 0 8 12 4 4 6 Hhbfdlc FDTTHUUH UYRH DLS FQPGLULQPHS QRHSDULQP ODPVDN DPG LPTUDNNDULQP ODPVDN 0150523237 ...

Страница 2: ... proof breaker of the air conditioner should be all pole switch Distance between its two contacts should not be no less than 3mm Such means for disconnection must be incorporated in the wiring Make sure installation is done according to local wiring regulation by professional persons Make sure ground connection is correct and reliable A leakage explosion proof breaker must be installed Do not use ...

Страница 3: ...U bg Z icf bUhYX fYYb cigY UgYg WcjYfYX Vm h Y Dmchc IfchcWc ZUhcfm fYZf YfUbh W Uf Y cZ h Y dfcXiWh4gYY ib h bUaY d UhY UXX h cbU fYZf YfUbh Uacibh W Uf YX b h Y Z Y X hchU fYZf YfUbh W Uf Y cihXccf ib h fYZf YfUbh Wm bXYf UbX aUb Zc X Zcf W Uf b _ _ _ R32 P KGBG BZ h Y gidd m WcfX g XUaU YX h aigh VY fYd UWYX Vm h Y aUbiZUWhifYf hg gYfj WY U Ybh cf g a Uf m eiU Z YX dYfgcbg b cfXYf hc Ujc X U Un...

Страница 4: ...f U f WcbX h cbYf XcYg bch Yh XUaU YX df cf hc VY b d W_YX id Vm h Y fY YjUbh kUghY X gdcgU WYbhYf UbX Wcbhf VihY hc Ybj fcbaYbhU UkUfYbYgg Vm bg gh b cb Ub Uddfcdf UhY Ubh dc ih cb aYh cX cZ X gdcgU Tj dad mdihl M Y fYZf YfUh b W fWi h g YU_ dfccZ cf U h Y acXY g b h g aUbiU h Y U dc Y X gWcbbYl cb WcbbYWh cb aYh cX g ci X VY Udd YX b h Y dckYf gidd m LiW aYUbg Zcf X gWcbbYWh cb aigh VY bWcfdcfUh...

Страница 5: ...c b U f hcc cb UbX Xcbvh Yh h Y fcca hYadYfUhifY XYWfYUgY hcc ck Y h Yf cbvh dih Z b Yfg cf Ubm ch Yf h b g bhc h Y b Yh cih Yh UbX gk b cijYf k Y h Y WcbX h cbYf g b cdYfUh cb YWUigY h Y gdYYX ZUb g jYfm XUb Yfcig UbX aUm WUigY b if Yg P Yb bYYX aU bhYbUbWY UbX fYdU faYbh WU XYU Yf hc UbX Y h BbWcffYWh aU bhYbUbWY UbX fYdU faYbh aUm WUigY kUhYf YU_ Y YWhf WU g cW_ UbX Z fY UnUfX U h Y XYU Yf hc h...

Страница 6: ...Wi h VfYU_Yf f WcbX h cbYf g ci X VY cWUhYX b kY jYbhYX UbX YUg m UWWYgg V Y d UWY f WcbX h cbYf g ci X bch VY cWUhYX b h Y Zc ck b d UWYg4 wUx I UWYg k h aUW bY c g cf ch Yf c jUdcifg wVx LYUg XY k h gU h WcbhYbh b h Y U f wWx GYUf hc ch gdf b k h WcbhYbh cZ gi Z XY UgYg wXx fYU k h ZfYeiYbh Z iWhiUh cb cZ jc hU Y Y ZUWhcfm YhW wYx Bb jY W Yg cf g dg wZx D hW Yb k h YUjm c jUdcif cf ia X hm w x G...

Страница 7: ...S01 remote controller 6 Parts and Functions External View of the Remote Controller Notes This series of air conditioners is unable to realize the follow ing keys and functions HEALTH ECONOMY TURBO QUIET IFP FRESH 10 HEATER ...

Страница 8: ...he display is becoming less and less bright on the remote controller abnormal condition in some cases it means that the remote controller is of low battery and you need to replace the batteries with the new ones General knowledge if the remote controller is left unused for a long time please take out the batteries If there is still information display on the remote controller after the batteries a...

Страница 9: ...power failure of the air conditioner after the power failure compensation is set the air conditioner will recover the original operating status upon power restoration Setting the power failure compensation Press Sleep 10 times within 5s while the air conditioner is switched on and the indoor unit is powered on except the timing start and air blowing and the buzzer rings 4 times to enter the status...

Страница 10: ...COOL HEAT and DRY 1 In the event of starting up with remote controller execute refrigeration heating and dehumidification modes after pressing the COOL HEAT and DRY 2 Power on for the first time for the temperature and wind speed displayed in each mode see the following table power on not for the first time parameters set last time will display in each mode Mode Smart Heat Cool Dry Fan Initial Tem...

Страница 11: ... display Full display Full display Full display Full display Swing angle Position 3 Position 5 Position 3 Position 3 Position 3 2 After switch on press the key to choose panel 1 panel 2 panel 3 panel 4 or four side panel and then regulate the swing angel by using the key 9 1 angle 1 2 angle 2 3 angle 3 4 angle 4 5 angle 5 6 angle 6 reserved Press the key and choose the right angel you want There i...

Страница 12: ... pr cancelled If the preset time of TIME OFF is the same as the current time displayed by the clock TIME OFF keeps flashing and the preset time can t be confirmed The user need to set TIME OFF for another time When the current time reaches to the preset time of TIME OFF the preset time and TIME OFF will disappear 3 TIMER ON OFF After setting TIME ON and TIME OFF the remote controller will automati...

Страница 13: ...XY M Y U f WcbX h cbYf WUbbch VY fYghUfhYX gccb UZhYf h ghcdg f WcbX h cbYf XcYg bch ghUfh9 M g g VYWUigY cZ h Y gY Z dfchYWh cb ZibWh cb cZ h Y gmghYa h YfYZcfY h WUbbch VY fYghUfhYX Zcf UVcih h fYY a bihYg UZhYf h ghcdg I YUgY kU h Zcf h fYY a bihYg 32x zz f XcYg bch V ck cf h Y ZUb gdYYX WUbbch VY W Ub YX Xif b Xfm b Bb KQ acXY k Yb fcca hYadYfUhifY VYWcaYg Yf h Ub hYadYfUhifY gYhh b ib h f fib...

Страница 14: ... b Ug h aYg g h Y ZU ifY cZ cihXccf z cf YlUad Y ZU ifY WcXY h Uh cihXccf g gc bXccf ib h g ci X X gd Um g U fYgi h h aYf E Z Ug Yg hk WY Z fgh m h Yb fibb b E Z Ug Yg hk WY ZZYfYbh Zfca cihXccf ib h acXY cf h Y cihXccf ZU ifY bX WUhYX Vm h Y bXccf ib h d YUgY fYZYf hc h Y cihXccf ZU ifY WcXY gh MU4 UaV Ybh hYadYfUhifY gYbgcf 5 Ma4 Wc hYadYfUhifY gYbgcf MfciV Y g cch b BENK H wfibb b YX cZ bXccf f...

Страница 15: ...YjYbh WcadfYggcf k Yb ghUfh b A M acXY d YUgY Wih b h Y dckYf gidd m gk hW cifg VYZcfY ghUfh b fib Zifh YfacfY U kUmg _YYd h Y dckYf gidd m gk hW cb Xif b h Y ig b gYbgcb Icgh gYUgcb UfY Fnlmig k P _5mi5ehip I YUgY bghU h Y U f WcbX h cbYf UWWcfX b hc h Y fYei fYaYbhg gdYW Z YX b h g aUbiU hc YbgifY h Y U f WcbX h cbYf kcf_ kY Y WUfYZi bch hc gWfUhW h Y gifZUWY cZ h Y WUgY Xif b acj b h Y U f WcbX...

Страница 16: ...if ZcfYZ b Yf gc h Y Z hYf bYh WUb dUfh Zfca h Y YaVYX b gk hW Zcf ig hc Yh h YUg m I WhifY I WhifY M Y Vchhca f a cZ h Y Z hYf bYh M Y Vf a cZ U f b Yh f Y RTA h Y d WhifYg UVcjY UfY cb m acXY g d g cVYm h Y fYU aUW bYfm zz Ff h mc dk dhf m bkdff 2836 Qj h dk dhf m bkdff 2936 S gio dk adfm k 2 36 S gio mc dk dhf m bkdff 2 36 Ff h NgY gcZh Vfig kUhYf UbX bYihfU XYhYf Ybh hc W YUb h Yb h fck h Y kU...

Страница 17: ...cb g U VY XcbY Vm dfcZYgg cbU dYcd Y Xcbvh bghU ib h Vm mcifgY Z BbWcffYWh bghU Uh cb k WUigY kUhYf YU_U Y Y YWhf W g cW_ cf Z fY BbghU ib h Ug dYf h Y FUbiU BbWcffYWh bghU Uh cb k WUigY kUhYf YU_U Y Y YWhf W g cW_ cf Z fY UWW XYbh Y gifY hc igY gdYW Z YX UWWYggUf Yg UbX dUfhg Hh Yfk gY kUhYf YU_U Y Y YWhf W g cW_ Z fY UWW XYbh cf ib h ZU b Xckb aUm UddYb Nb h g ci X VY d UWYX cb U d UWY ghfcb Ybc...

Страница 18: ... cihXccf ib h d d b Yb h g k h b a h wKYZYf hc BbghU Uh cb FUbiU Zcf cihXccf ib h x BbXccf UbX cihXccf ib h dckYf WUV Y bhYf ib h WUV Y UfY Uh YUgh a UkUm ZfcaM O fUXcd M g g Y dZi hc Ujc X d WhifY X ghifVUbWY UbX bc gY w jYb Z a g_Ydh bc gY WUb gh UddYUf Z fUX c kUjY g ghfcb x 6 cbvh X gWUfX Ubm UWWYggcf Yg ibh Wcad8 9 THNHFULQP QI LPTUDNNDULQP RNDFH YhYfa bY h Y kUm hc WUffm ib h hc bghU Uh cb d...

Страница 19: ...Lh_iik nhdm R h f I 1 B Lhlm ff mdih Rki _nk AB25S2SC1FA AB35S2SC1FA 18 ...

Страница 20: ...f cb Z cUh b gk hW WUig b kUhYf YU_U Y x w x KYacjY h Y kUg Yf acib h b UbX h hYb h Y bih UVcjY w0x KYacjY h Y dUdYf dUhhYfb w x g Zcf h Y X aYbg cbg cZ WY b c Y gYY dUdYf dUhhYfb g_ mcif fYU YghUhY XYU Yf Zcf XYhU g YbhYf cZ h Y c Y g aUf_YX cb h Y dUdYf dUhhYfb YbhYf cZ h Y ib h g aUf_YX cb h Y WUfX b h Y ib h UbX cb h Y dUdYf dUhhYfb Fcibh dUdYf dUhhYfb cbhc ib h ig b gWfYkg 0 l h Y WcfbYf cZ h...

Страница 21: ...U f VU Zfca UddYb b BZ XckbkUfX g cdY WUbvh VY aUXY hU_Y ch Yf aYUgifYg hc Zh h id DYYd U X ghUbWY cZ a VYhkYYb gigdYbX b VfUW_Yhg hc aU_Y kUhYf cgY ghfU h U f 8 K o 2 y 3 NgY h Y gY Z dfcj XYX gh ZZ d dY UbX W Uad k h ib h BbgYfh kUhYf d dY bhc kUhYf d i ibh h fYUW Yg h Y k hY hUdY M hYb h Y W d ibh YUX cZ h Y gWfYk g Ygg h Ub aa Zfca cgY P bX h Y XfU b cgY hc h Y W d ig b gYU dUX 3 Bbgi UhY XfU ...

Страница 22: ...Y fibb b Ndcb WcbZ faUh cb cZ U gacch kUhYf XfU bU Y VY gifY hc Wih cZZ dckYf gidd m YW_ kUhYf XfU bU Y b Wcc b cdYfUh cb w x YW_ Z kUhYf XfU bU Y g gacch UZhYf bghU Uh cb Pim A BZ gYjYfU kUhYf cgYg c b hc Yh Yf Xc Ug dYf Zc ck b dfcWYYXifYg LdYW Z YUh cbg cZ h Y kUhYf cgYg g U aYYh h Y fYei fYaYbhg Zcf h Y ib h fibb b M Y g cdY cZ kUhYf XfU b cgY w x g U VY k h b 1 aa Xcbvh Udd m hcc aiW ZcfWY cb...

Страница 23: ...cf kUhYf Xfcd aUm cWWif Yk cf kUhYf Xfcd aUm cWWif IfcV Ya aUm cWWif cf dUfhg ch VifbYX IfcV Ya aUm cWWif cf dUfhg ch VifbYX M YfY a h VY U XUb Yf cZ Y YWhf W g cW_ IfcV Ya aUm cWWif cf dUfhg ch VifbYX M g aUm WUigY dccf Wcc b Bh g UfX hc Wcbhfc fYZf YfUbh W Uf b Uacibh Dmm hmdihA UZhYf Z b g b bghU Uh cb WcbZ fa bc fYZf YfUbh YU_U Y WLSLPJ HXDORNH WLSLPJ gidd YX dUfhg aUhYf U g UbX k f b cdYfUh c...

Страница 24: ...tection equipment should be suitable for use with all applicable refrigerants i e non sparking adequately sealed or intrinsically safe Presence of fire extinguisher If any hot work is to be conducted appropriate fire extinguishing equipment shall be available to hand Have a dry powder or CO2 fire extinguisher adjacent to the charging area No ignition sources All possible ignition sources including...

Страница 25: ...ce components only with parts specified by the manufacturer Other parts may result in the ignition of refrigerant in the atmosphere from a leak Cabling Check that cabling will not be subject to wear corrosion excessive pressure vibration sharp edges or any other adverse environmental effects The check shall also take into account the effects of aging or continual vibration from sources such as com...

Страница 26: ...re that only appropriate refrigerant recovery cylinders are employed Ensure that the correct number of cylinders for holding the total system charge are available All cylinders to be used are designated for the recovered refrigerant and labelled for that refrigerant i e special cylinders for the recovery of refrigerant Cylinders shall be complete with pressure relief valve and associated shut off ...

Страница 27: ... YYgZhh4AV Zg BcYjhig Va IVg J VclVc Vc KdVY Xd MZX ZkZadebZci SdcZ J c YVd 00 L VcYdc I K dciVXih4 M E z20 223 03 5 Q z20 223 0333 PZWh iZ4 lll V Zg Xdb ...

Отзывы: