Cautions

Checks to electrical devices

    - Repair and maintenance to electrical components shall include initial safety checks and component inspection 

procedures. If a fault exists that could compromise safety, then no electrical supply shall be connected to the circuit until it 

is satisfactorily dealt with. If the fault cannot be corrected immediately but it is necessary to continue operation, an 

adequate temporary solution shall be used. This shall be reported to the owner of the equipment so all parties are 

advised.

    -  Initial safety checks shall include:

• that capacitors are discharged: this shall be done in a safe manner to avoid possibility of sparking;

• that no live electrical components and wiring are exposed while charging, recovering or purging the system;

• that there is continuity of earth bonding.

Repairs to sealed components

    - During repairs to sealed components, all electrical supplies shall be disconnected prior to any removal of sealed 

covers, etc. If it is absolutely necessary to have an electrical supply to equipment during servicing, then a permanently 

operating form of leak detection shall be located at the most critical point to warn of a potentially hazardous situation.    

    - Ensure that by working on electrical components, the casing is not altered in such a way that the level of protection is 

affected, including damage to cables, excessive number of connections, terminals not made to original specification, 

damage to seals, incorrect fitting of glands, etc.

    - Ensure that the apparatus is mounted securely.

    - Ensure that seals or sealing materials have not degraded to the point that they no longer serve the purpose of 

preventing the ingress of flammable atmospheres. Replacement parts shall be in accordance with the manufacturer’s 

specifications.

Repair to intrinsically safe components

    - Do not apply any permanent inductive or capacitance loads to the circuit without ensuring that this will not exceed the 

permissible voltage and current permitted for the equipment in use. 

    - Intrinsically safe components are the only types that can be worked on while live in the presence of a flammable 

atmosphere.

    - Replace components only with parts specified by the manufacturer. Other parts may result in the ignition of refrigerant 

in the atmosphere from a leak.

Cabling

 - Check that cabling will not be subject to wear, corrosion, excessive pressure, vibration, sharp edges or any other 

adverse environmental effects. The check shall also take into account the effects of aging or continual vibration from 

sources such as compressors or fans. 

Detection of flammable refrigerants

Removal and evacuation

 - The refrigerant charge shall be recovered into the correct recovery cylinders and the system shall be “flushed” with 

OFN to render the unit safe. This process may need to be repeated several times.

    - Compressed air or oxygen shall not be used for purging refrigerant systems.

    - Flushing shall be achieved by breaking the vacuum in the system with OFN and continuing to fill until the working 

pressure is achieved, then venting to atmosphere, and finally pulling down to a vacuum. This process shall be repeated 

until no refrigerant is within the system. When the final OFN charge is used, the system shall be vented down to 

atmospheric pressure to enable work to take place.

    - The vacuum pump is not close to any ignition sources and that ventilation is available.

Charging procedures

    - Ensure that contamination of different refrigerants does not occur when using charging equipment. Hoses or lines 

shall be as short as possible to minimise the amount of refrigerant contained in them. 

    - Cylinders shall be kept upright.

    - Ensure that the refrigeration system is earthed prior to charging the system with refrigerant.

    - Label the system when charging is complete (if not already).

    - Extreme care shall be taken not to overfill the refrigeration system.

    - Prior to recharging the system, it shall be pressure-tested with the appropriate purging gas. The system shall be leak-

tested on completion of charging but prior to commissioning. A follow up leak test shall be carried out prior to leaving the 

site.

Decommissioning

    - Before carrying out this procedure, it is essential that the technician is completely familiar with the equipment and all 

its detail.

    - Prior to the task being carried out, an oil and refrigerant sample shall be taken in case analysis is required prior to re-

use of reclaimed refrigerant.

    - Electrical power must be available before the task is commenced. 

24

Содержание AB25S2SC1FA

Страница 1: ... AB35S2SC1FA Uih cbg IUfhg UbX ibWh cbg HdYfUh cb MfciV Yg cch b ighcaYf GYYX hc _bck FU bhYbUbWY BbghU Uh cb IfcWYXifY 0 8 12 4 4 6 Hhbfdlc FDTTHUUH UYRH DLS FQPGLULQPHS QRHSDULQP ODPVDN DPG LPTUDNNDULQP ODPVDN 0150523237 ...

Страница 2: ... proof breaker of the air conditioner should be all pole switch Distance between its two contacts should not be no less than 3mm Such means for disconnection must be incorporated in the wiring Make sure installation is done according to local wiring regulation by professional persons Make sure ground connection is correct and reliable A leakage explosion proof breaker must be installed Do not use ...

Страница 3: ...U bg Z icf bUhYX fYYb cigY UgYg WcjYfYX Vm h Y Dmchc IfchcWc ZUhcfm fYZf YfUbh W Uf Y cZ h Y dfcXiWh4gYY ib h bUaY d UhY UXX h cbU fYZf YfUbh Uacibh W Uf YX b h Y Z Y X hchU fYZf YfUbh W Uf Y cihXccf ib h fYZf YfUbh Wm bXYf UbX aUb Zc X Zcf W Uf b _ _ _ R32 P KGBG BZ h Y gidd m WcfX g XUaU YX h aigh VY fYd UWYX Vm h Y aUbiZUWhifYf hg gYfj WY U Ybh cf g a Uf m eiU Z YX dYfgcbg b cfXYf hc Ujc X U Un...

Страница 4: ...f U f WcbX h cbYf XcYg bch Yh XUaU YX df cf hc VY b d W_YX id Vm h Y fY YjUbh kUghY X gdcgU WYbhYf UbX Wcbhf VihY hc Ybj fcbaYbhU UkUfYbYgg Vm bg gh b cb Ub Uddfcdf UhY Ubh dc ih cb aYh cX cZ X gdcgU Tj dad mdihl M Y fYZf YfUh b W fWi h g YU_ dfccZ cf U h Y acXY g b h g aUbiU h Y U dc Y X gWcbbYl cb WcbbYWh cb aYh cX g ci X VY Udd YX b h Y dckYf gidd m LiW aYUbg Zcf X gWcbbYWh cb aigh VY bWcfdcfUh...

Страница 5: ...c b U f hcc cb UbX Xcbvh Yh h Y fcca hYadYfUhifY XYWfYUgY hcc ck Y h Yf cbvh dih Z b Yfg cf Ubm ch Yf h b g bhc h Y b Yh cih Yh UbX gk b cijYf k Y h Y WcbX h cbYf g b cdYfUh cb YWUigY h Y gdYYX ZUb g jYfm XUb Yfcig UbX aUm WUigY b if Yg P Yb bYYX aU bhYbUbWY UbX fYdU faYbh WU XYU Yf hc UbX Y h BbWcffYWh aU bhYbUbWY UbX fYdU faYbh aUm WUigY kUhYf YU_ Y YWhf WU g cW_ UbX Z fY UnUfX U h Y XYU Yf hc h...

Страница 6: ...Wi h VfYU_Yf f WcbX h cbYf g ci X VY cWUhYX b kY jYbhYX UbX YUg m UWWYgg V Y d UWY f WcbX h cbYf g ci X bch VY cWUhYX b h Y Zc ck b d UWYg4 wUx I UWYg k h aUW bY c g cf ch Yf c jUdcifg wVx LYUg XY k h gU h WcbhYbh b h Y U f wWx GYUf hc ch gdf b k h WcbhYbh cZ gi Z XY UgYg wXx fYU k h ZfYeiYbh Z iWhiUh cb cZ jc hU Y Y ZUWhcfm YhW wYx Bb jY W Yg cf g dg wZx D hW Yb k h YUjm c jUdcif cf ia X hm w x G...

Страница 7: ...S01 remote controller 6 Parts and Functions External View of the Remote Controller Notes This series of air conditioners is unable to realize the follow ing keys and functions HEALTH ECONOMY TURBO QUIET IFP FRESH 10 HEATER ...

Страница 8: ...he display is becoming less and less bright on the remote controller abnormal condition in some cases it means that the remote controller is of low battery and you need to replace the batteries with the new ones General knowledge if the remote controller is left unused for a long time please take out the batteries If there is still information display on the remote controller after the batteries a...

Страница 9: ...power failure of the air conditioner after the power failure compensation is set the air conditioner will recover the original operating status upon power restoration Setting the power failure compensation Press Sleep 10 times within 5s while the air conditioner is switched on and the indoor unit is powered on except the timing start and air blowing and the buzzer rings 4 times to enter the status...

Страница 10: ...COOL HEAT and DRY 1 In the event of starting up with remote controller execute refrigeration heating and dehumidification modes after pressing the COOL HEAT and DRY 2 Power on for the first time for the temperature and wind speed displayed in each mode see the following table power on not for the first time parameters set last time will display in each mode Mode Smart Heat Cool Dry Fan Initial Tem...

Страница 11: ... display Full display Full display Full display Full display Swing angle Position 3 Position 5 Position 3 Position 3 Position 3 2 After switch on press the key to choose panel 1 panel 2 panel 3 panel 4 or four side panel and then regulate the swing angel by using the key 9 1 angle 1 2 angle 2 3 angle 3 4 angle 4 5 angle 5 6 angle 6 reserved Press the key and choose the right angel you want There i...

Страница 12: ... pr cancelled If the preset time of TIME OFF is the same as the current time displayed by the clock TIME OFF keeps flashing and the preset time can t be confirmed The user need to set TIME OFF for another time When the current time reaches to the preset time of TIME OFF the preset time and TIME OFF will disappear 3 TIMER ON OFF After setting TIME ON and TIME OFF the remote controller will automati...

Страница 13: ...XY M Y U f WcbX h cbYf WUbbch VY fYghUfhYX gccb UZhYf h ghcdg f WcbX h cbYf XcYg bch ghUfh9 M g g VYWUigY cZ h Y gY Z dfchYWh cb ZibWh cb cZ h Y gmghYa h YfYZcfY h WUbbch VY fYghUfhYX Zcf UVcih h fYY a bihYg UZhYf h ghcdg I YUgY kU h Zcf h fYY a bihYg 32x zz f XcYg bch V ck cf h Y ZUb gdYYX WUbbch VY W Ub YX Xif b Xfm b Bb KQ acXY k Yb fcca hYadYfUhifY VYWcaYg Yf h Ub hYadYfUhifY gYhh b ib h f fib...

Страница 14: ... b Ug h aYg g h Y ZU ifY cZ cihXccf z cf YlUad Y ZU ifY WcXY h Uh cihXccf g gc bXccf ib h g ci X X gd Um g U fYgi h h aYf E Z Ug Yg hk WY Z fgh m h Yb fibb b E Z Ug Yg hk WY ZZYfYbh Zfca cihXccf ib h acXY cf h Y cihXccf ZU ifY bX WUhYX Vm h Y bXccf ib h d YUgY fYZYf hc h Y cihXccf ZU ifY WcXY gh MU4 UaV Ybh hYadYfUhifY gYbgcf 5 Ma4 Wc hYadYfUhifY gYbgcf MfciV Y g cch b BENK H wfibb b YX cZ bXccf f...

Страница 15: ...YjYbh WcadfYggcf k Yb ghUfh b A M acXY d YUgY Wih b h Y dckYf gidd m gk hW cifg VYZcfY ghUfh b fib Zifh YfacfY U kUmg _YYd h Y dckYf gidd m gk hW cb Xif b h Y ig b gYbgcb Icgh gYUgcb UfY Fnlmig k P _5mi5ehip I YUgY bghU h Y U f WcbX h cbYf UWWcfX b hc h Y fYei fYaYbhg gdYW Z YX b h g aUbiU hc YbgifY h Y U f WcbX h cbYf kcf_ kY Y WUfYZi bch hc gWfUhW h Y gifZUWY cZ h Y WUgY Xif b acj b h Y U f WcbX...

Страница 16: ...if ZcfYZ b Yf gc h Y Z hYf bYh WUb dUfh Zfca h Y YaVYX b gk hW Zcf ig hc Yh h YUg m I WhifY I WhifY M Y Vchhca f a cZ h Y Z hYf bYh M Y Vf a cZ U f b Yh f Y RTA h Y d WhifYg UVcjY UfY cb m acXY g d g cVYm h Y fYU aUW bYfm zz Ff h mc dk dhf m bkdff 2836 Qj h dk dhf m bkdff 2936 S gio dk adfm k 2 36 S gio mc dk dhf m bkdff 2 36 Ff h NgY gcZh Vfig kUhYf UbX bYihfU XYhYf Ybh hc W YUb h Yb h fck h Y kU...

Страница 17: ...cb g U VY XcbY Vm dfcZYgg cbU dYcd Y Xcbvh bghU ib h Vm mcifgY Z BbWcffYWh bghU Uh cb k WUigY kUhYf YU_U Y Y YWhf W g cW_ cf Z fY BbghU ib h Ug dYf h Y FUbiU BbWcffYWh bghU Uh cb k WUigY kUhYf YU_U Y Y YWhf W g cW_ cf Z fY UWW XYbh Y gifY hc igY gdYW Z YX UWWYggUf Yg UbX dUfhg Hh Yfk gY kUhYf YU_U Y Y YWhf W g cW_ Z fY UWW XYbh cf ib h ZU b Xckb aUm UddYb Nb h g ci X VY d UWYX cb U d UWY ghfcb Ybc...

Страница 18: ... cihXccf ib h d d b Yb h g k h b a h wKYZYf hc BbghU Uh cb FUbiU Zcf cihXccf ib h x BbXccf UbX cihXccf ib h dckYf WUV Y bhYf ib h WUV Y UfY Uh YUgh a UkUm ZfcaM O fUXcd M g g Y dZi hc Ujc X d WhifY X ghifVUbWY UbX bc gY w jYb Z a g_Ydh bc gY WUb gh UddYUf Z fUX c kUjY g ghfcb x 6 cbvh X gWUfX Ubm UWWYggcf Yg ibh Wcad8 9 THNHFULQP QI LPTUDNNDULQP RNDFH YhYfa bY h Y kUm hc WUffm ib h hc bghU Uh cb d...

Страница 19: ...Lh_iik nhdm R h f I 1 B Lhlm ff mdih Rki _nk AB25S2SC1FA AB35S2SC1FA 18 ...

Страница 20: ...f cb Z cUh b gk hW WUig b kUhYf YU_U Y x w x KYacjY h Y kUg Yf acib h b UbX h hYb h Y bih UVcjY w0x KYacjY h Y dUdYf dUhhYfb w x g Zcf h Y X aYbg cbg cZ WY b c Y gYY dUdYf dUhhYfb g_ mcif fYU YghUhY XYU Yf Zcf XYhU g YbhYf cZ h Y c Y g aUf_YX cb h Y dUdYf dUhhYfb YbhYf cZ h Y ib h g aUf_YX cb h Y WUfX b h Y ib h UbX cb h Y dUdYf dUhhYfb Fcibh dUdYf dUhhYfb cbhc ib h ig b gWfYkg 0 l h Y WcfbYf cZ h...

Страница 21: ...U f VU Zfca UddYb b BZ XckbkUfX g cdY WUbvh VY aUXY hU_Y ch Yf aYUgifYg hc Zh h id DYYd U X ghUbWY cZ a VYhkYYb gigdYbX b VfUW_Yhg hc aU_Y kUhYf cgY ghfU h U f 8 K o 2 y 3 NgY h Y gY Z dfcj XYX gh ZZ d dY UbX W Uad k h ib h BbgYfh kUhYf d dY bhc kUhYf d i ibh h fYUW Yg h Y k hY hUdY M hYb h Y W d ibh YUX cZ h Y gWfYk g Ygg h Ub aa Zfca cgY P bX h Y XfU b cgY hc h Y W d ig b gYU dUX 3 Bbgi UhY XfU ...

Страница 22: ...Y fibb b Ndcb WcbZ faUh cb cZ U gacch kUhYf XfU bU Y VY gifY hc Wih cZZ dckYf gidd m YW_ kUhYf XfU bU Y b Wcc b cdYfUh cb w x YW_ Z kUhYf XfU bU Y g gacch UZhYf bghU Uh cb Pim A BZ gYjYfU kUhYf cgYg c b hc Yh Yf Xc Ug dYf Zc ck b dfcWYYXifYg LdYW Z YUh cbg cZ h Y kUhYf cgYg g U aYYh h Y fYei fYaYbhg Zcf h Y ib h fibb b M Y g cdY cZ kUhYf XfU b cgY w x g U VY k h b 1 aa Xcbvh Udd m hcc aiW ZcfWY cb...

Страница 23: ...cf kUhYf Xfcd aUm cWWif Yk cf kUhYf Xfcd aUm cWWif IfcV Ya aUm cWWif cf dUfhg ch VifbYX IfcV Ya aUm cWWif cf dUfhg ch VifbYX M YfY a h VY U XUb Yf cZ Y YWhf W g cW_ IfcV Ya aUm cWWif cf dUfhg ch VifbYX M g aUm WUigY dccf Wcc b Bh g UfX hc Wcbhfc fYZf YfUbh W Uf b Uacibh Dmm hmdihA UZhYf Z b g b bghU Uh cb WcbZ fa bc fYZf YfUbh YU_U Y WLSLPJ HXDORNH WLSLPJ gidd YX dUfhg aUhYf U g UbX k f b cdYfUh c...

Страница 24: ...tection equipment should be suitable for use with all applicable refrigerants i e non sparking adequately sealed or intrinsically safe Presence of fire extinguisher If any hot work is to be conducted appropriate fire extinguishing equipment shall be available to hand Have a dry powder or CO2 fire extinguisher adjacent to the charging area No ignition sources All possible ignition sources including...

Страница 25: ...ce components only with parts specified by the manufacturer Other parts may result in the ignition of refrigerant in the atmosphere from a leak Cabling Check that cabling will not be subject to wear corrosion excessive pressure vibration sharp edges or any other adverse environmental effects The check shall also take into account the effects of aging or continual vibration from sources such as com...

Страница 26: ...re that only appropriate refrigerant recovery cylinders are employed Ensure that the correct number of cylinders for holding the total system charge are available All cylinders to be used are designated for the recovered refrigerant and labelled for that refrigerant i e special cylinders for the recovery of refrigerant Cylinders shall be complete with pressure relief valve and associated shut off ...

Страница 27: ... YYgZhh4AV Zg BcYjhig Va IVg J VclVc Vc KdVY Xd MZX ZkZadebZci SdcZ J c YVd 00 L VcYdc I K dciVXih4 M E z20 223 03 5 Q z20 223 0333 PZWh iZ4 lll V Zg Xdb ...

Отзывы: