background image

9

9

 

About Heat Pump Systems 

 

1)

 

Terminal 5 (O) is energized for cooling   
Terminal 6 (B) is energized for heating 

 

In most applications, the reversing valve is energized for cooling and should be connected to the "O" terminal.  
If the heat pump requires the reversing valve to be energized for heating, connect the reversing valve to the 
"B" terminal. 

 

2)

 

With a call for Stage 2 on a two speed heat pump, 

both

 compressor outputs Y1 and Y2 are energized.  When 

2 stages of cooling and 2 stages of heating are configured for a heat pump, Stage 2 is considered high speed 
on the heat pump and not auxiliary heat.  If auxiliary heat (or emergency heat) in needed, configure 3 stages 
of heating on the heat pump. 

 

3)

 

To temporarily disable Energy Efficient Control and heat as quickly as possible, press [HOLD] and select 
“On”.  The RC-2000 will use the Auxiliary Heat as needed to reach the heat setting.

 

 

4)

 

Terminal 9 (L) is used to indicate a fault with the heat pump compressor.   When there is a compressor fault, 
the display will flash red and the “Heat Pump Fault” error message is shown. 

 

5)

 

The Emergency Heat Relay (E Terminal) and outdoor thermostats (usually accessories to a heat pump), are 
not used.  The RC-2000 automatically controls auxiliary heat efficiently.  If the heat pump is equipped with an 
outdoor thermostat, it should be removed from the auxiliary heat circuit. 

 

About Dual Fuel Heat Pump Systems 

 

A dual fuel heat pump typically has a gas furnace combined with a heat pump.  The gas furnace is used as 
auxiliary heat unless the outdoor temperature is very low, in which case it is used as the primary heat source. 

 

1)

 

When used with dual fuel heat pumps, the RC-2000 requires a method for obtaining the outdoor 
temperature.  A temperature sensor can be physically connected to the “Remote Temp. Sensor” terminals on 
the thermostat or the RC-2000 can obtain the outdoor temperature from a remote system. 

 

If the RC-2000 can not obtain the outdoor temperature, the heat pump compressor will not operate and the 
thermostat will only call for the auxiliary heat until the problem is resolved.  When this occurs, the display 
will flash red and the “Problem With Outdoor Temperature Sensor.  Some Heat Stages May Be Disabled” 
error message is displayed.  After the error has been acknowledged, “Outdoor Sensor Fault” will be 
displayed in the Message Bar until the problem is resolved. 

 

2)

 

Balance Setpoint Limits: 

 

¾

 

If the outdoor temperature is above the “Upper Balance Setpoint” (45

°

F by default), the heat pump is 

used exclusively.   

¾

 

If the outdoor temperature falls below the “Upper Balance Setpoint” but is above the “Lower Balance 

Setpoint” (35

°

F by default) and if the heat pump is unable to heat at a rate of 5 degrees per hour or 

better, the heat pump will turn off and auxiliary heat will be used until the call for heat has been 
satisfied.   

¾

 

If the outdoor temperature falls below the “Lower Balance Setpoint”, the heat pump will turn off and 

the auxiliary heat will be used until the call for heat has been satisfied. 

¾

 

The Balance Setpoint Limits can be adjusted according to the manufacturer’s specifications under 
“Balance Setpoint”

 – See

 

Installation Settings

 

3)

 

When the RC-2000 makes a call for auxiliary heat, the heat pump compressor is turned off and the 
auxiliary heat is used exclusively.

 

Содержание RC-2000

Страница 1: ...t 2 A on any circuit 3 A total The following requirements must be observed for installation in Europe CE 1 This equipment must be installed in accordance with National wiring rules for the country in...

Страница 2: ...Removing an existing thermostat 1 Disconnect the power to the control transformer 2 Remove the cover to the existing thermostat 3 Disconnect the wires going to each terminal on the thermostat Label ea...

Страница 3: ...iagram for the application See Figures 11 13 Upon completion of wiring the thermostat push all excess wiring into the hole in the wall Plug the hole with the supplied insulating foam to ensure an accu...

Страница 4: ...d cooling the metal jumper between Terminal 1 RC and Terminal 2 RH on the left terminal strip must remain in place See Figure 4 2 From the factory the RC 2000 is configured to control a single stage c...

Страница 5: ...rmostat or HVAC system does not perform as stated in the Power Up steps under the wiring diagram for the respective HVAC system recheck all wiring See Troubleshooting Tips 7 For HVAC systems with sepa...

Страница 6: ...e that there are no stray wires or wire strands at the connections 2 Connect power to the transformer and system The display will show the current thermostat settings 3 Press FAN and select On The fan...

Страница 7: ...t W from the individual zones when the W2 terminal is energized and calls for cool Y when the Y1 terminal is energized Neither W2 nor Y2 is energized when the mode is set to OFF Therefore the RC 2000...

Страница 8: ...ure that there are no stray wires or wire strands at the connections 2 Connect power to the transformer and system The display will show the current thermostat settings 3 Press FAN and select On The f...

Страница 9: ...ture is very low in which case it is used as the primary heat source 1 When used with dual fuel heat pumps the RC 2000 requires a method for obtaining the outdoor temperature A temperature sensor can...

Страница 10: ...t power to the transformer and system The display will show all of the thermostat settings 3 Press FAN and select On The fan should come on 4 Press FAN and select Auto The fan should go off 5 Press HO...

Страница 11: ...t thermostat settings 3 Press FAN and select On The fan should come on 4 Press FAN and select Auto The fan should go off 5 Set the Mode to Heat Raise the desired heat setting 1 degree above the curren...

Страница 12: ...or 4 conductor wire from the HAI system to the thermostat location All thermostats on an HAI Home Control system are connected to Ground Zone 16 and Output 8 See Figure 11 THERMOSTAT Leave Jumper Conn...

Страница 13: ...terminal strip See Figure 12 5 15 VDC ANY SYSTEM WITH A RELAY OR 5 15 VDC OUTPUT THERMOSTAT Leave Jumper Connected Black Green UP Figure 12 Connections to a Remote Setback Switch Notes 1 When connecti...

Страница 14: ...feet twisted pair with foam polyethylene insulated conductors shielded must be used Wire runs must not exceed 250 feet Make the connections to the Green and Black terminals under the section marked R...

Страница 15: ...gs 6 Read the warning and then press Continue to proceed 7 To exit Setup mode press Back several times until the Home Page is displayed Notes 1 The thermostat will automatically default to the Home Pa...

Страница 16: ...GY STAR program When used with a remote system HAI recommends that the Program Mode be configured as None or Occupancy This will disable the internal program schedules The program options setting sets...

Страница 17: ...rift farther from the setpoint decreasing comfort When combined with Heat Minimum Off cycles per hours can be obtained by using the following calculation 60 Heat Minimum On Heat Minimum off The defaul...

Страница 18: ...w far from the setpoint the temperature has to be before the auxiliary heat turns on This is only available for heat pump systems Conventional 1 Cool 1 Heat Zone Control 1 Cool 1 Heat Heat Pump 1 Cool...

Страница 19: ...ration Read the warning and then press Yes to proceed or Cancel to return to Installation Settings LIMITED WARRANTY HAI warrants this product against defects in material and workmanship under normal u...

Страница 20: ...thermostat and the remote system are set to the proper configurations for communication SYMPTOM ACTION TO TAKE 1 Allow 30 minutes for thermostat to adjust 2 Adjust calibration offset Temperature Readi...

Отзывы: