background image

6

6

 

Single Stage Conventional

 

 

24VAC "HOT"

Heat

24VAC Common*

Fan

Cool

Humidifier

Dehumidier

UP

24VAC
CONTROL
TRANSMFOMER

Dehumidifier

Humidifier

Fan Relay

Cool Relay

Heat Relay

HVAC SYSTEM

THERMOSTAT

(RC)

(C)

(Y1)

(G)

(W1)

(D)

(H)

1

3

8

6

7

11

12

 

         *   Common wire is required in “heat only” or “cool only” applications.  Also use a common if heat, cool,  
 

  or fan relay cannot supply 15mA to power thermostat, without activating. 

 

Figure 6

 

 

Connections for single stage heat/cool thermostat

 

 

 
CONFIGURATION 
 

¾

 

From the factory, the RC-2000 is configured as a single stage conventional heat/cool thermostat.  

¾

 

In the default configuration, this thermostat does not turn the fan on with a call for heat.  If the furnace does 

not turn the fan on with a call for heat, the thermostat must be configured to do so under 

“System Options”

.   

 

POWER UP  

 

1.

 

Double check wiring, be sure that there

 

are

 

no stray wires or wire strands at the connections. 

2.

 

Connect power to the transformer and system.  The display will show the current thermostat settings. 

3.

 

Press [FAN] and select “On”.  The fan should come on.   

4.

 

Press [FAN] and select “Auto”.  The fan should go off. 

5.

 

Set the Mode to "Heat".  Raise the desired heat setting above the current temperature.  Ensure that the 
heating unit comes on.  Set the mode to "Off".  Ensure that the heating unit goes off. 

6.

 

Set the Mode to "Cool".  Lower the desired cool setting below the current temperature.

  

Ensure that the 

cooling unit comes on.  Set the mode to "Off".  Ensure that the cooling unit goes off. 

 

The RC-2000 thermostat is designed to work with most single state conventional 4-wire HVAC systems 
(without a transformer common).  However, if the RC-2000 “resets” when calling for heat or cool, or if the 
heat, cool, or fan relay cannot supply 15mA to power thermostat without the relay activating, the transformer 
common wire or the HAI Thermostat Power Supply Module (Part Number: 30A00-1) is required. 

Содержание RC-2000

Страница 1: ...t 2 A on any circuit 3 A total The following requirements must be observed for installation in Europe CE 1 This equipment must be installed in accordance with National wiring rules for the country in...

Страница 2: ...Removing an existing thermostat 1 Disconnect the power to the control transformer 2 Remove the cover to the existing thermostat 3 Disconnect the wires going to each terminal on the thermostat Label ea...

Страница 3: ...iagram for the application See Figures 11 13 Upon completion of wiring the thermostat push all excess wiring into the hole in the wall Plug the hole with the supplied insulating foam to ensure an accu...

Страница 4: ...d cooling the metal jumper between Terminal 1 RC and Terminal 2 RH on the left terminal strip must remain in place See Figure 4 2 From the factory the RC 2000 is configured to control a single stage c...

Страница 5: ...rmostat or HVAC system does not perform as stated in the Power Up steps under the wiring diagram for the respective HVAC system recheck all wiring See Troubleshooting Tips 7 For HVAC systems with sepa...

Страница 6: ...e that there are no stray wires or wire strands at the connections 2 Connect power to the transformer and system The display will show the current thermostat settings 3 Press FAN and select On The fan...

Страница 7: ...t W from the individual zones when the W2 terminal is energized and calls for cool Y when the Y1 terminal is energized Neither W2 nor Y2 is energized when the mode is set to OFF Therefore the RC 2000...

Страница 8: ...ure that there are no stray wires or wire strands at the connections 2 Connect power to the transformer and system The display will show the current thermostat settings 3 Press FAN and select On The f...

Страница 9: ...ture is very low in which case it is used as the primary heat source 1 When used with dual fuel heat pumps the RC 2000 requires a method for obtaining the outdoor temperature A temperature sensor can...

Страница 10: ...t power to the transformer and system The display will show all of the thermostat settings 3 Press FAN and select On The fan should come on 4 Press FAN and select Auto The fan should go off 5 Press HO...

Страница 11: ...t thermostat settings 3 Press FAN and select On The fan should come on 4 Press FAN and select Auto The fan should go off 5 Set the Mode to Heat Raise the desired heat setting 1 degree above the curren...

Страница 12: ...or 4 conductor wire from the HAI system to the thermostat location All thermostats on an HAI Home Control system are connected to Ground Zone 16 and Output 8 See Figure 11 THERMOSTAT Leave Jumper Conn...

Страница 13: ...terminal strip See Figure 12 5 15 VDC ANY SYSTEM WITH A RELAY OR 5 15 VDC OUTPUT THERMOSTAT Leave Jumper Connected Black Green UP Figure 12 Connections to a Remote Setback Switch Notes 1 When connecti...

Страница 14: ...feet twisted pair with foam polyethylene insulated conductors shielded must be used Wire runs must not exceed 250 feet Make the connections to the Green and Black terminals under the section marked R...

Страница 15: ...gs 6 Read the warning and then press Continue to proceed 7 To exit Setup mode press Back several times until the Home Page is displayed Notes 1 The thermostat will automatically default to the Home Pa...

Страница 16: ...GY STAR program When used with a remote system HAI recommends that the Program Mode be configured as None or Occupancy This will disable the internal program schedules The program options setting sets...

Страница 17: ...rift farther from the setpoint decreasing comfort When combined with Heat Minimum Off cycles per hours can be obtained by using the following calculation 60 Heat Minimum On Heat Minimum off The defaul...

Страница 18: ...w far from the setpoint the temperature has to be before the auxiliary heat turns on This is only available for heat pump systems Conventional 1 Cool 1 Heat Zone Control 1 Cool 1 Heat Heat Pump 1 Cool...

Страница 19: ...ration Read the warning and then press Yes to proceed or Cancel to return to Installation Settings LIMITED WARRANTY HAI warrants this product against defects in material and workmanship under normal u...

Страница 20: ...thermostat and the remote system are set to the proper configurations for communication SYMPTOM ACTION TO TAKE 1 Allow 30 minutes for thermostat to adjust 2 Adjust calibration offset Temperature Readi...

Отзывы: