REMOTE TEMPERATURE SENSOR

 

 
A remote temperature sensor can be installed to monitor the temperature from a remote location or can be 
combined with the onboard temperature sensor for the average temperature of two locations.   
 
Run a twisted pair, shielded cable from the RC-2000 to the remote temperature sensor location.  For distances 
up to 100 feet, typical twisted pair, PVC-insulated, shielded cable may be used.  For distances from 100-150 
feet, twisted pair with polypropylene insulated conductors, shielded must be used.  For distances from 150-250 
feet, twisted pair with foam-polyethylene insulated conductors, shielded must be used.  Wire runs must not 
exceed 250 feet. 
 
Make the connections to the Green and Black terminals under the section marked “Remote Temp Sensor” on 
the right terminal strip - 

See

 

Figure 13

.   

 

UP

THERMOSTAT

Black

Green

 

 

Figure 13 – 

Connections to a Remote Temperature Sensor  

 

 

Notes:

  

 
1.

 

When connecting a remote temperature sensor,

 

the shield and one of the wires from the remote 

temperature sensor are tied together and get connected to the Black terminal – See Figure 13. 

 
2.

 

At the location of the temperature sensor, wrap the shield around the jacket of the cable and tape. 

 
3.

 

Configure the temperature sensor according to the application – See “Temperature Sensors” under 
Installation Settings. 

 

Содержание RC-2000

Страница 1: ...t 2 A on any circuit 3 A total The following requirements must be observed for installation in Europe CE 1 This equipment must be installed in accordance with National wiring rules for the country in...

Страница 2: ...Removing an existing thermostat 1 Disconnect the power to the control transformer 2 Remove the cover to the existing thermostat 3 Disconnect the wires going to each terminal on the thermostat Label ea...

Страница 3: ...iagram for the application See Figures 11 13 Upon completion of wiring the thermostat push all excess wiring into the hole in the wall Plug the hole with the supplied insulating foam to ensure an accu...

Страница 4: ...d cooling the metal jumper between Terminal 1 RC and Terminal 2 RH on the left terminal strip must remain in place See Figure 4 2 From the factory the RC 2000 is configured to control a single stage c...

Страница 5: ...rmostat or HVAC system does not perform as stated in the Power Up steps under the wiring diagram for the respective HVAC system recheck all wiring See Troubleshooting Tips 7 For HVAC systems with sepa...

Страница 6: ...e that there are no stray wires or wire strands at the connections 2 Connect power to the transformer and system The display will show the current thermostat settings 3 Press FAN and select On The fan...

Страница 7: ...t W from the individual zones when the W2 terminal is energized and calls for cool Y when the Y1 terminal is energized Neither W2 nor Y2 is energized when the mode is set to OFF Therefore the RC 2000...

Страница 8: ...ure that there are no stray wires or wire strands at the connections 2 Connect power to the transformer and system The display will show the current thermostat settings 3 Press FAN and select On The f...

Страница 9: ...ture is very low in which case it is used as the primary heat source 1 When used with dual fuel heat pumps the RC 2000 requires a method for obtaining the outdoor temperature A temperature sensor can...

Страница 10: ...t power to the transformer and system The display will show all of the thermostat settings 3 Press FAN and select On The fan should come on 4 Press FAN and select Auto The fan should go off 5 Press HO...

Страница 11: ...t thermostat settings 3 Press FAN and select On The fan should come on 4 Press FAN and select Auto The fan should go off 5 Set the Mode to Heat Raise the desired heat setting 1 degree above the curren...

Страница 12: ...or 4 conductor wire from the HAI system to the thermostat location All thermostats on an HAI Home Control system are connected to Ground Zone 16 and Output 8 See Figure 11 THERMOSTAT Leave Jumper Conn...

Страница 13: ...terminal strip See Figure 12 5 15 VDC ANY SYSTEM WITH A RELAY OR 5 15 VDC OUTPUT THERMOSTAT Leave Jumper Connected Black Green UP Figure 12 Connections to a Remote Setback Switch Notes 1 When connecti...

Страница 14: ...feet twisted pair with foam polyethylene insulated conductors shielded must be used Wire runs must not exceed 250 feet Make the connections to the Green and Black terminals under the section marked R...

Страница 15: ...gs 6 Read the warning and then press Continue to proceed 7 To exit Setup mode press Back several times until the Home Page is displayed Notes 1 The thermostat will automatically default to the Home Pa...

Страница 16: ...GY STAR program When used with a remote system HAI recommends that the Program Mode be configured as None or Occupancy This will disable the internal program schedules The program options setting sets...

Страница 17: ...rift farther from the setpoint decreasing comfort When combined with Heat Minimum Off cycles per hours can be obtained by using the following calculation 60 Heat Minimum On Heat Minimum off The defaul...

Страница 18: ...w far from the setpoint the temperature has to be before the auxiliary heat turns on This is only available for heat pump systems Conventional 1 Cool 1 Heat Zone Control 1 Cool 1 Heat Heat Pump 1 Cool...

Страница 19: ...ration Read the warning and then press Yes to proceed or Cancel to return to Installation Settings LIMITED WARRANTY HAI warrants this product against defects in material and workmanship under normal u...

Страница 20: ...thermostat and the remote system are set to the proper configurations for communication SYMPTOM ACTION TO TAKE 1 Allow 30 minutes for thermostat to adjust 2 Adjust calibration offset Temperature Readi...

Отзывы: