REMOVING A THERMOSTAT FROM THE Z-WAVE NETWORK
When prompted by Z-Wave primary or inclusion controller to exclude the thermostat from the network, press
and release the ‘Hold’ button on the thermostat. This will exclude the thermostat from the Z-Wave network.
The thermostat supports the following command classes:
COMMAND_CLASS_THERMOSTAT_MODE
COMMAND_CLASS_THERMOSTAT_SETPOINT
COMMAND_CLASS_THERMOSTAT_FAN_MODE
COMMAND_CLASS_THERMOSTAT_FAN_STATE
COMMAND_CLASS_THERMOSTAT¬_OPERATING_STATE
COMMAND_CLASS_SENSOR_MULTILEVEL
COMMAND_CLASS_ASSOCIATION
COMMAND_CLASS_CONFIGURATION
COMMAND_CLASS_VERSION
COMMAND_CLASS_MANUFACTURER_SPECIFIC
COMMAND_CLASS_SWITCH_BINARY
COMMAND_CLASS_CLOCK
COMMAND_CLASS_THERMOSTAT_MODE
Upon power up, allow 10 seconds for the RC-112BZ thermostat to initialize. After 10 seconds, a controller can
set the mode, get the current mode, and get the modes supported by the thermostat.
COMMAND_CLASS_THERMOSTAT_SETPOINT
Upon power up, allow 10 seconds for the RC-112BZ thermostat to initialize. After 10 seconds, a controller can
change setpoints, get current setpoints, and request the setpoints that are supported by thermostat.
COMMAND_CLASS_SENSOR_MULTILEVEL
The RC-112BZ thermostat uses this command class to report the actual temperature.
COMMAND_CLASS_ASSOCIATION
Upon power up, allow 10 seconds for the RC-112BZ thermostat to initialize. After 10 seconds, a controller can
issue an Association Set, Remove, or Get command. The thermostat must be associated with a controller to
provide feedback.
COMMAND_CLASS_CONFIGURATION
Upon power up, allow 10 seconds for the RC-112BZ thermostat to initialize. After 10 seconds, a controller can
change individual register settings for the outdoor temperature. The Parameter Number is 67. The size of the
data is a 1 byte value. The Value is the temperature to which the register is set.