Energy storage system components in
flow
sets
XEM1000 XEM2000 XEMV1000 XEMV2000
XEM800 Energy storage system including
electronics
1
1
1
1
XEM100 Battery module 5.8 kWh
1
2
1
2
XEM002 Inverter
1
1
1
1
-
Supporting rail for energy storage
system wall mounting
1
1
1
1
-
Mounting tabs with fixing screws
4
4
4
4
-
Spacer for base assembly
2
2
2
2
-
Battery module connection cable set
1
2
1
2
XEM200 Optional accessory
Base for upright assembly
XEM250
Optional accessory
SG Ready interface for heat pump
connection
Table 1: Scope of delivery
Tool list
–
Insulating pliers
–
Suitable voltage meter
–
Rotating field indicator
–
Slot screwdriver 0.4 x 2.5 mm (data plug assembly, terminal block connection)
–
Slot screwdriver 0.8 x 4 mm (for connecting the battery cable terminal)
–
Philips screwdriver (for connecting the energy storge system with the base)
–
Knife (removing the sheathing from the leads)
–
Hammer drill with fitting drill bit (for wall mounting the energy storge system)
–
Size 13 spanner (fixing the energy storage system hangers)
–
Torx screwdriver T25 (attaching the inverter)
–
Torx screwdriver T 20 (battery clamps in the battery modules)
–
Spirit level, side cutter, combination pliers
Additional installation material (not included in scope of delivery)
Additional construction materials and tools must be provided in addition to the materials includ-
ed in the scope of delivery. The following materials are required for the assembly of the energy
storage system described below:
–
Minimum 4 attachments (e.g. screw-anchor combinations) for hanging up the energy stor-
age system
–
Recommended cable NYM-J 5x6 or 10 mm² for connecting the energy storage system
–
PE cable 6 mm² for connecting the overvoltage protection in the energy storage system
–
Residual current circuit-breaker type B 300 mA CFB640E as preliminary fuse in the cable
cut
–
Circuit breaker 32 A B Characteristic MBN332 as preliminary fuse in the cable cut
–
Cat. 6 network cable with RJ45 plugs for network connection
–
Maximum 2 photovoltaic strings with 4 MC4 plugs