Installation, handling and maintenance
7.3.6
Fire barrier
Fire barriers are required for busbar elements which pass through fire area.
They are fitted to the busbar element during the manufacturing process.
Comment:
-
After assembling the busbar run, seal the joints in the fire barrier or fire ceiling
with dimensionally stable, non-flammable construction material (Class A1 or
A2-s1; d0 conforming to EN 13501--1) completely to component thickness,
e. g., with concrete or grout. The concrete or grout must meet the applicable
regulations to preserve the fire resistance classification of the wall or ceiling,
e. g., EN 206--1 and EN 998--2.
-
Make sure that, in the case of large wall or ceiling penetrations, e.g., through
reinforcements or steel brackets, the fasteners are secured from slipping out.
Dimensions of the penetrations
The following dimensions are specified for penetrations:
System
a [mm]
b [mm]
KEH33S* - 800 A
350
350
KEH34S* - 1000 A 350
350
KEH35S* - 1250 A 350
400
KEH36S* - 1600 A 350
400
KEH37S* - 2000 A 350
450
KEH31D* - 2500 A 350
550
KEH32D* - 3200 A 350
650
KEH33D* - 4000 A 350
650
Technical changes reserved
77
Содержание Unibar H 800 A
Страница 1: ...Busbar system unibar H System manual 800 A to 4000 A...
Страница 10: ...Construction and characteristics 10 Technical changes reserved...
Страница 19: ...Construction and characteristics Technical changes reserved 19 Notices...
Страница 40: ...Product selection 40 Technical changes reserved Copper...