2
6LE004186A
tebis
/
TX206H
§
Heating Actuator 6 channels
User instructions
¢
£
•
Physical adressing push-button
Maximum of 13 actuators
Main 230V~
power source
3. Cover locks into place by
turning the screws. Basis is
now ready for operation.
4. Connect transformer to the
power outlet.
Changing the fuse
1. Fuse indicator lit.
The unit must be checked
by a qualified specialist.
2. Pull out fuse casing.
3. Spare fuse is located in
transparent cover.
4. Change the fuse type T 2A.
Technical Data
- Supply voltage:
230V~ 50/60Hz
- Bus KNX/EIB:
30V
s
SELV
- Max. power uptake:
50W
- Bus power consumption:
< 10mA
- Standard fuse:
T 2A
- Max. number of actuators:
13
- Dimensions (mm) H/W/L:
70 x 75 x 302
- Safety class:
II
- Protection type:
IP20
- Connection :
Flexible capacity:
0,5 —> 1,5 mm2
Rigid capacity:
1 —> 1,5 mm2
- Operating temperature:
-5 °C —> +40 °C
- Storage temperature:
-20 °C —> +60 °C
- Pollution category:
2
- Rated impulse voltage:
4kV
- Overvoltage Category:
3
- Software structure:
class A
- Voltage and current declared for the needs
of EMC emissions tests:
30V - 10mA
- Communication media KNX :
TP1
- Configuration mode KNX :
Smode
Installation on mounting bracket
1. Simple installation on
mounting bracket (EN 50022).
2. Attach mounting bracket using
the 2 screws of the delivery
contents.
3. Clip the base unit onto the
mounting bracket.
4. To remove the base from
the rail, use a screwdriver
as shown.
KNX/EIB connection
1. Insert both ends of
the KNX/EIB cable into
the KNX/EIB terminal.
Indicator lights
- Power light
illuminates when unit is
connected to power.
- Fuse indicator illuminates
when fuse is blown. System
needs to be
checked by a qualified specialist.
- Indicator
illuminates, when zone is
operating.
Commissioning
1. Use the correct
connections on the basis.
2. Fit transparent cover.
Orientation of screws must
be parallel with junction
unit.
Application and description
The TX206H is a 6 channels heating actuator.
It becomes heating information from room
thermostats and control thermal actuators.
This system is adapted to residential applications
as well as various types of service buildings and
facilities.
It is suitable for installation in heat circulation/
distribution system and is equipped with Triacs
to ensure silent switching operations.
Configuration
• TX100 V1.6.3 or higher: detailed description
is included in User’s Instructions supplied
with the configurator
• ETS : application software TL206D,
database and description available from the
manufacturer.
Safety Instructions
- Before opening the basis always switch the
system off.
- To clean the unit use a dry towel only.
- Never clean the unit with water or other
solvents (e.g. spirit, acetone).
In case of emergency
Immediately remove the plug from the mains.
Network connection / Connection of
actuators
- Each actor requires its own connection to the
main power supply.
- Possibility to connect up to a maximum of
13 actuators to the basis.
1. Press the wires into the
cable grip so that the
sheath is flush with the
top edge.
2. Insert die end of the
lines into the terminals.
Observe the color coding
of the connections.
3. A maximum of 4
actuators can be
connected to each channel.
Installation
Mounting on the wall
1. To lift the transparent cover from
the junction unit, loose the screws.
2. Prepare the device for
installation by seperating
all pieces.
3. Install the base unit directly onto
the wall (Ø for screws 2,5 mm).
or
To allow wiring to be routed
behind install the base unit with
spacers.
Bus KNX/EIB
Description
TX206H
Système 24V
Témoins lumineux
V1.6.3
:.?Bn
6LE004186A
- This device must be installed only by
a qualified electrician.
- Conform to TBTS installation rules.
(Applicable in the European Union and other European countries
with separate collection systems).
This marking shown on the product or its literature indicates that
it should not be disposed with other household wasted at the
end of its working life. To prevent possible harm to the
environment or human health from uncontrolled waste disposal,
please separate this from other types of wastes and recycle it
responsibly to promote the sustainable reuse of material
resources.
Household users should contact either the retailer where they
purchased this product, or their local government office, for
details of where and how they can take this item for
environmentally safe recycling.
Business users should contact their supplier and check the
terms and conditions of the purchase contract. This product
should not be mixed with other commercial wastes of disposal.
Usable throughout Europe
å
and in Switzerland
Correct Disposal of This product
(Waste Electrical & Electronic
Equipment).