Planning information
Technical changes reserved
15
Item
Dimensions in
mm
Power loss in W at ΔT in K
(without fan)
D
IN
d
oo
r (
R/
L
)
Pan
el
h
ei
gh
t
E
ffect
ive p
an
el
h
ei
gh
t
Pan
el
wi
dth
PL
E
ΔT
10 K
15 K
20 K
25 K
30 K
Floor-standing enclosures 90 min.
FB21SE
2048 x 398
34
50
67
84
101
R
12
11
1
132
FB22SE
2048 x 648
57
85
113
140
169
R
12
11
2
264
FB23SE
2048 x 898
80
119
158
196
236
R
12
11
3
396
FB24SE
2048 x 1148
101
151
202
253
303
R
12
11
4
528
Wall-mounted enclosures 90 min.
FB31SE
598 x 398
16
25
33
42
50
R
3
2
1
24
FB32SE
598 x 648
22
33
44
55
66
R
3
2
2
48
FB41SE
748 x 398
18
27
37
46
55
R
4
3
1
36
FB42SE
748 x 648
26
39
52
65
78
R
4
3
2
72
FB51SE
898 x 398
20
30
41
51
61
R
5
4
1
48
FB52SE
898 x 648
29
44
60
75
90
R
5
4
2
96
FB61SE
1048 x 398
22
33
45
55
66
R
6
5
1
60
FB62SE
1048 x 648
33
50
67
84
101
R
6
5
2
120
FB63SE
1048 x 898
45
67
90
112
135
R
6
5
3
180
FB71SE
1198 x 398
24
36
48
60
72
R
7
6
1
72
FB72SE
1198 x 648
37
56
74
93
113
R
7
6
2
144
FB73SE
1198 x 898
51
75
101
126
152
R
7
6
3
216
FB82SE
1348 x 648
41
62
82
104
124
R
8
7
2
168
FB83SE
1348 x 898
59
88
118
147
177
R
8
7
3
252
Planning information
ATTENTION
Property damage due to increased heat in the event of a fire.
The increase in heat that occurs inside the enclosure in the event of fire
must be taken into account.
This must also be factored in when designing the layout.
To facilitate more detailed planning, an example is provided below of the
temperature increase in the event of fire, according to the Standard
Time-Temperature Curve, in an empty housing at a height of 2/3 in the FB23LE
fire protection enclosure:
Duration
Temperature curve
10 minutes
2 K
15 minutes
4 K
20 minutes
9 K
25 minutes
15 K
30 minutes
24 K
-
Information about other enclosure versions can be provided on request.