Assembly
Technical changes reserved
21
FBxxSE wall mounting including cooling cable duct
-
Wall mounting is the same as for the FBxxLE enclosure.
For the FBxxSE, a cooling cable duct must be placed over all the cables. The
cooling cable duct must be filled with mineral wool, melting point >1000°C
(included in delivery).
Securing the cooling cable duct
-
The cooling cable duct is secured to the housing and the wall using two
brackets.
-
Use two dowels each to fasten it to the wall. (Use suitable fastening
materials)
-
Use flat headed screws 4.5 x 35 including washers to secure the housing and
the cooling cable duct.
1 Securing bracket and dowel affixed to existing wall
2 Securing bracket affixed to housing
3 Temperature sensor
ATTENTION
The temperature sensor (3) should not be placed inside the cooling cable
duct!