System-disconnection relay EU400 NA-protection
19
Subject to technical changes
8.6 Using integrated switches of PV and battery inverters according to
DIN EN 62109 (VDE 0126-4)
1)
Feedback contacts Y1/Y2 not connected set
8
rel .
8
→
8
trel.
8
→
8
oFF.
8
2)
N connected
→
only for programs with N
3)
If the inverter requires an external power source
4)
Switch off the plant without recording an alarm, e.g. with output contact of a ripple control receiver
5)
Fuses only when line protection necessary, e.g. 3x16A
6)
Contact closed an
8
uSr .
8
→
8
StbY.
8
(default setting) = Standby, K1+2 switched-off
(e.g. by ripple control receiver or clock,
…)
Contact closed and
8
uSr .
8
→
8
on.
8
= repressed vector shifts
(e.g. when switching on …),
contact closed and
8
uSr .
8
→
8
y1y2.
8
= no evaluation of the feedback contacts
(e.g. for synchronisation, …)
7)
1 phase Application connect L1-L2-L3, 2 phase Application L1 / L2+L3 (only Pr 5, 7, 10, 13, 20)
8)
non-islanding inverters acc. to DIN EN 62109 (VDE 1026-4) with integrated AC switches (internally
monitored), approved according to VDE-AR-N 4105:2018-11