System-disconnection relay EU400 NA-protection 

 

32 

 

 

Subject to technical changes 

  Press the   button 1x  

 display

 

8

Pin 

8

 

8

   504

8

 

  Use the 

 buttons to set the new, desired pin code 

(

caution: write down the pin code

  Press the   button 1x

 

  Code lock on, display

 

8

  

on

8

 flashes three times

 

  Code lock off, display 

 

8

 

oFF 

8

 flashes three times

 

  Return to menu mode, menu item code lock

 

 
If there are any problems with the code lock (pin forgotten), the lock can be switched off and the pin can be 

reset to 504 by keeping the Set key pressed while switching on the mains until   

 

8

Code

8

 

8

 oFF

8

 appears in 

the display. 
 

12.17 

Sealing 

All the settings and the simulation mode can be locked. 

If the 

LED is illuminated, the EU400 is locked.  

If an attempt is made to change a setting in the locked state, for 3s the display shows

 

8

LOc 

8

.

 

 
Adjustment procedure Sealing/Lock ON (OFF): 

  If present, remove seal (only authorised person) 

  Apply control supply voltage at A1-A2 

  Slightly lift the key cover and turn 180° 

  Actuate the small blue button by pressing the button cover very firmly (LED starts flashing) 

until the green LED 

 is illuminated. 

 

12.18 

Simulation 

Here, the voltage, frequency or a vector surge can be simulated and the setting can be tested. All 3 phases 
plus the 10 minute mean value are always simulated. All functions of the device operate as if this value is 
actually being measured. Alarm and error messages are only indicated with the LEDs and not in the display. 
The set values are simulated until the menu item   

si  .

  

 

is exited with the 

 or 

 button. If the EU400 is sealed/locked, simulation is not possible. 

If the section switch feedback contacts are connected to the EU400 and enabled, (set value > section-switch 
turn-on time under 

8

trel.

8

), after a shut-down, the tripping time (dAL + time of slowest section switch) is 

displayed. 

 

Adjustment process: 

  Select the menu item with the 

 buttons until 

 display 

8

si  .

8

 

  Press the    button 1x  

 display

 

8

si  

8

 

8

u   

8

 

 

  Use the 

 buttons to set the measurement factor for simulation:

 

o

 

8

u   

8

 V 10min mean value (frequency = last simulated value) 

o

 

8

f   

8

 Frequency (voltage = last simulated value) 

o

 

8

uSr 

8

 Vector shift 

  Press the   button 1x 

 display

 

8

 230

8

 (selected measurement factor is simulated)

 

  Use the 

 buttons to set the desired value 

 

After exiting the Simulation menu item with the 

 buttons, the unit switches over to monitoring the limits. 

The unit automatically returns to the display mode if no button is pressed for 15 minutes. 

 

Hint: A limit value should be tested that is higher than the set 10min mean value. If the 10min mean value has 

to be temporarily switched off, set (

8

Um  .

8

 

 

8

 oFF.

8

 since otherwise it will trip first. The same applies, 

for example, for 

 U¯   

, during a simulation of 

 

U¯ ¯   

in Pr3 and Pr4. (Medium voltage) 

 

 

Содержание EU400 NA-protection

Страница 1: ...eset 2 s L1 L2 L3 N tolerance Master Slave regulation communication error return error K1 K2 limit error high low parameter error overrange max 300V L L max 520V L N E1 2 s V Hz s 1 K1 10 min average...

Страница 2: ...AR N 4105 2011 2018 11 VSE NA EEA NE7 CH 2020 power generators at the low voltage grid TAR medium voltage VDE AR N 4110 2018 11 and TAR high voltage VDE AR N 4120 2018 11 for use in power generators a...

Страница 3: ...12 New default setting Pr11 14 VDE AR N 4110 2018 11 New Firmware 0 13 Switching on behaviour adjustable 8UFon8 easy measurement of disengaging ratio 8ruEF8 New Firmware 0 14 Monitoring of zero voltag...

Страница 4: ...ed contacts medium voltage VDE AR N 4110 2018 11 high voltage VDE AR N 4120 2018 11 18 8 6 Using integrated switches of PV and battery inverters according to DIN EN 62109 VDE 0126 4 19 8 7 Generator o...

Страница 5: ...r 1 7 39 Adjustment values table BDEW June 2008 acc 3 2 3 3 1 Medium Voltage Pr 3 6 39 Adjustment values table VDE AR N 4105 2018 11 Low Voltage 6 table 2 Pr 2 40 Adjustment values VDE AR N 4110 2018...

Страница 6: ...fications Display and controls 1 Test button Press briefly Display test menu Relay K1 8tst18 or relay K2 8tst28 can be tested independently 3min without a button is pressed go back to the normal mode...

Страница 7: ...rms standby counter standby time Up pushing Set button for 2 s resets the stored values Press for 2 s Display of MAX Up MIN Down measured values additional pushing of Set button for 2 s deletes the st...

Страница 8: ...10 0 10 0 10 0 10 doF OFF delay s 60 60 60 60 60 60 60 U_ 27 S1 27 S1 U_ Alarm on off on on on on on on on U_ Undervoltage V 184 184 184 46 2 80 0 184 318 H_ Hysteresis V 5 0 12 0 5 0 1 0 1 0 3 0 3 0...

Страница 9: ...ber of phases 3ph 3ph 3ph 3ph 3ph 3ph 3ph rocf 81r rocf Alarm on off oFF oFF oFF oFF oFF oFF oFF dfdt delta f delta t Hz s 0 800 2 000 0 800 0 800 0 800 0 800 0 800 Per periods 20 20 20 20 20 20 20 dA...

Страница 10: ...age V 63 5 110 253 438 H Hysteresis V 1 0 1 0 3 0 3 0 dAL Response time s 0 10 0 10 0 10 0 10 doF OFF delay s 60 60 60 60 U_ 27 S1 27 S1 U_ Alarm on off on on on on U_ Undervoltage V 46 2 80 0 184 318...

Страница 11: ...tor shift 10 0 10 0 10 0 10 0 doF OFF delay s 3 3 3 3 dEon Suppression time s 3 3 3 3 uSr Number of phases 3ph 3ph 3ph 3ph rocf 81r rocf Alarm on off oFF oFF oFF oFF dfdt delta f delta t Hz s 2 000 2...

Страница 12: ...elay s 60 60 20 20 20 20 1 U_ 27 S1 27 S1 U_ Alarm on off on on oFF oFF oFF oFF on U_ Undervoltage V 184 184 200 348 50 2 95 7 161 H_ Hysteresis V 11 5 12 0 5 0 5 0 1 0 1 0 5 0 dAL Response time s 1 0...

Страница 13: ...time s 2 2 2 2 2 2 2 uSr Number of phases 3ph 3ph 1ph 1ph 1ph 1ph 3Ph rocf 81r rocf Alarm on off oFF oFF on on on on on dfdt delta f delta t Hz s 0 800 2 000 1 000 1 000 1 000 1 000 1 000 Per periods...

Страница 14: ...be changed if required and be protected with a code and or a seal With a test button the function of the connected switches can be tested and their switching time can be measured The standby input all...

Страница 15: ...ontrol receiver or clock Contact closed and 8uSr 8 8 on 8 repressed vector shifts e g when switching on contact closed and 8uSr 8 8y1y2 8 no evaluation of the feedback contacts e g for synchronisation...

Страница 16: ...lant without recording an alarm e g with contact of a ripple control receiver 5 Fuses only when line protection necessary e g 3x16A 6 Contact closed an 8uSr 8 8StbY 8 default setting Standby K1 2 swit...

Страница 17: ...and 8uSr 8 8 on 8 repressed vector shifts e g when switching on contact closed and 8uSr 8 8y1y2 8 no evaluation of the feedback contacts e g for synchronisation 7 1 phase Application connect L1 L2 L3...

Страница 18: ...d 8uSr 8 8 on 8 repressed vector shifts e g when switching on contact closed and 8uSr 8 8y1y2 8 no evaluation of the feedback contacts e g for synchronisation 7 1 phase Application connect L1 L2 L3 2...

Страница 19: ...3 NC or NO contacts can be connected self learning when switching on 4 Switch off the plant without recording an alarm e g with output contact of a ripple control receiver 5 Fuses only when line prote...

Страница 20: ...ripple control receiver 5 Fuses only when line protection necessary e g 3x16A 6 Contact closed an 8uSr 8 8StbY 8 default setting Standby K1 2 switched off e g by ripple control receiver or clock Cont...

Страница 21: ...r 8Pr 58 3 Nc or no contacts can be connected automatic detection when switching on 4 Switch off the plant without recording an alarm e g with output contact of a ripple control receiver 5 Fuses only...

Страница 22: ...lead to death bodily injury or property damage to the device itself and to other devices and equipment If the information contained in the operating instructions operating manual are not sufficient pl...

Страница 23: ...8 E1 E2 closed K1 and K2 off standby vector shift off 8uSr 8 8Y1Y2 8 E1 E2 closed Feedback contacts no evaluated vector shift off when using with generator mains synchronization Y0 Y1 Y2 Inputs feedba...

Страница 24: ...ntil the button is pressed again The longer time of both channels is always displayed Alarm counter The unit saves max 100 alarms cause measurement value at operating time The LEDs indicate the cause...

Страница 25: ...frequency 2x under frequency 10min average value 1x vector shift 1x ROCOF 230V TOR Erzeuger Typ A B C D 15 3 AC with N 230V VSE NA EEA NE7 CH 2020 20 3 2 1 AC with N 2x over voltage 2x under voltage 2...

Страница 26: ...1 AC N TOR Erzeuger Typ A B C D 15 3 AC N VSE NA EEA NE7 CH 2020 20 3 2 1 AC N G98 G83 2 G99 G59 3 21 3 AC 22 3 AC N 23 3 AC 16 3 AC N Synergrid C10 C11 Display mode Unit Up Down simultaneously sets...

Страница 27: ...2 1 AC N Unit Up Down simultaneously sets the value to the lowest value Code Reset 2 s Set when mains are switched on Pin 504 Error messages Err4 Tolerance Master Slave Err5 Internal control Err6 Comm...

Страница 28: ...ay Alarm 8dAL 8 An alarm is suppressed for the set time seconds 8 0 058 8300 08 8 0 058 8180 08 Turn on time delay Off 8dOF 8 8dOFA8 Reset is delayed for the set time also during voltage recovery this...

Страница 29: ...e display mode Function button Set Reset Press briefly Change into the configuration mode Press for 2 s Returns to the display mode the most recently set values are then applied Function key Up Down P...

Страница 30: ...y OFF When the disengaging value is reached 8dAL cancelled relays ON Disengaging ratios can only be checked for U U U U not for f zero voltage and 10min average value For testing e g U U must be switc...

Страница 31: ...t connected activated feedback contacts 8noY18 or 8noY28 is displayed To exit the test menu wait for 3 minutes without a button or select 8end 8 by pressing the buttons Up Down and confirm by pressing...

Страница 32: ...med through a ripple control receiver Query the standby counter Change into the display mode Press the button several times until display 8acxx8 Press the button 2x display 8StbY8 8xxxx8 The standby t...

Страница 33: ...re always simulated All functions of the device operate as if this value is actually being measured Alarm and error messages are only indicated with the LEDs and not in the display The set values are...

Страница 34: ...of the feedback contacts is suppressed when E1 E2 are closed 8Deon8 Delay Enable On suppression time when switching on and after opening the enable input 81 ph 8 83 ph 8 Single phase three phase vecto...

Страница 35: ...520 V Measurement voltage phase N AC 10 310 V 5 V 0 is displayed Adjustment range phase N AC 15 300 V Measurement principle Real root mean square measurement both half waves Hysteresis Adjustable 1 0...

Страница 36: ...5 35 V ca 4mA Voltage Current E1 E2 DC 15 35 V ca 6mA Contactor response time section switch Adjustable 0 5 99 0 s Test conditions IEC EN 60255 Rated impulse voltage 4000 V Overvoltage category III Po...

Страница 37: ...connection single strand each 1 x 4mm2 Finely stranded with wire end ferrule each 1 x 2 5mm2 Protection class housing IP 30 Protection class terminals IP 20 Mounting snap on fastening on 35 mm mountin...

Страница 38: ...hreshold value check the threshold values 8Err98 appears in the display Parameter error Reset to factory settings see Program setup A time expires in the display Always when an OFF delay time 8doF 8 i...

Страница 39: ...l base 3 Riegel bar for snap mounting 4 Sealing max 1 8 mm 5 Frontplatteneinsatz front panel 6 Kennzeichen f r unten position downward 7 Bar for wall attachment with screws Riegelbohrung 4 2 mm Bolt h...

Страница 40: ...47 5Hz 100 ms 60 s Frequency increase protection f F 51 5Hz 100 ms 60 s Switching conditions UFon off Adjustment values table BDEW June 2008 acc 3 2 3 3 1 Medium Voltage Pr 3 6 Function BDEW Hager Ad...

Страница 41: ...60 s Frequency increase protection f F 51 5 Hz 100 ms 60 s Frequency decrease protection f F_ 47 5 Hz 100 ms 60 s Switching conditions UFon off Adjustment values VDE AR N 4110 2018 11 Medium Voltage V...

Страница 42: ...EEA NE 7 CH 2020 Hager Adjustment range of the protective relay in the external IR protection relay in the inverter Voltage increase protection U U 1 00 1 30 Un 1 20 Un 100 ms 1 20 Un 100 ms Voltage i...

Страница 43: ...00 Un 0 8 Un 1 5 s 0 8 Un 1 5 s Voltage decrease protection U U_ _ 0 10 1 00 Un 0 45 Un 300 ms 0 45 Un 300 ms Frequency increase protection f F 50 0 65 0 Hz 51 5 Hz 100 ms 51 5 Hz 100 ms Frequency de...

Страница 44: ...43 09 2021 6LE002996C Hager Electro S A S Boulevard d Europe B P 3 67215 OBERNAI CEDEX France T 33 0 3 88 49 50 50 F 33 0 3 88 49 50 53 info hager com hager com...

Отзывы: