System-disconnection relay EU400 NA-protection
24
Subject to technical changes
Commissioning
12.1 Program setup
The suitable program must be set on the EU4000 in accordance with the application. If the EU400 is
sealed/locked (red LED illuminated), the sealing has to be deactivated first.
Pr
Connection
Limit
Voltage
Country / Standard
* 2
3 AC with N
Low voltage
2x
over voltage
, 2x
under voltage
2x
over frequency
, 2x
under frequency
10min
average value
,1x
vector shift
1x ROCOF
230V
VDE-AR-N 4105:2018
1
3 AC with N
Low voltage
1x
over voltage
, 1x
under voltage
1x
over frequency
, 1x
under frequency
10min
average value
, 1x
vector shift
1x ROCOF
230V
VDE-AR-N 4105:2011
7
2/1 AC with N
11(3) 3 AC with N
Medium voltage
2x
over voltage
, 2x
under voltage
2x
over frequency
, 2x
under frequency
10min
average value
, 1x
vector shift
1x ROCOF
57,7V
VDE-AR-N 4110:2018
VDE-AR-N 4120:2018
(BDEW June 2008 by
3.2.3.3-1)
12(4) 3 AC without N
100V
13(5) 3/2/1 AC with N
230V
14(6) 3 AC without N
400V
10
3/2/1 AC with N
2x
over voltage
, 2x
under voltage
2x
over frequency
, 2x
under frequency
10min
average value
, 1x
vector shift
1x ROCOF
230V
TOR Erzeuger Typ
A,B,C,D
15
3 AC with N
230V
VSE NA/EEA-NE7 CH
2020
20
3/2/1 AC with N
2x
over voltage
, 2x
under voltage
2x
over frequency
, 2x
under frequency
10min
average value
, 1x
vector shift
1x ROCOF
230V
G98(G83/2) +
G99(G59/3)
21
3 AC without N
400V
22
3 AC with N
63,5V
23
3 AC without N
110V
16
3 AC with N
1x
over voltage
, 1x
under voltage
1x
over frequency
, 1x
under frequency
1x ROCOF, zero voltage
230V
Synergrid C10/C11
* default setting
Adjustment process:
If present, remove seal (only authorised person)
•
Apply control supply voltage at A1-A2
•
Slightly lift the key cover and turn 180°
•
Actuate the small blue button by firmly pressing the button cover (LED starts flashing) until the
green LED
is illuminated.
Sealing is deactivated
•
Press
button 1x
→
display
8
Info.
8
•
Press button 5x
→
display
8
Pr 1.
8
•
Set the program with the buttons
•
Press button 1x
→
display
8
no.
8
•
Press
button 1x
→
display
8
yes.
8
•
Press button
➔
Device resets and starts with the newly selected program
Hint:
When changing programs, all parameters of the selected program are reset to “default settings“ (see
table „Default settings“).
Only change the parameters after having selected the correct program.