Delayed Egress Wall Controller

Installation Instructions

I-EA00052

Rev 2, Rev Date: 02/06/15

Always visit www.hagerco.com for the latest Installation Instructions

HAGER COMPANIES 139 Victor Street, St. Louis, MO 63104 • (800) 325-9995

Verbal Exit Instructions or

Alarm Tone Only and

Digital Countdown Display

· 

Stop Employee Theft

· 

Stop Retail Shoplifting

· 

Restrict Airport Patrons

· 

Restrict Wandering Patients 

The integral verbal message, digital countdown display and sign

provide comprehensive and clear instructions of the door operation

for persons without prior knowledge of the exit delay, including the

sight and hearing impaired.

The digital keypad eliminates the need to carry and locate keys for

reset and bypass functions.

Features:

Egress Delay

· 

15 or 30 second exit delay

· 

1 or 2 second nuisance delay

Built-In 3 Function keypad

· 

Alarm and lock reset

· 

1 to 30 second bypass

· 

Sustained bypass

· 

Additional keyswitch optional

Control Inputs

· 

1 to 30 second request-to-exit and 
bypass  input with anti-tailgate and 

jumper selectable door prop alarm.

· 

Reset

Built-In Annunciation

· 

Armed mode

· 

Nuisance mode

· 

Irreversible egress mode

· 

Release mode

· 

Digital countdown mode

· 

Field selectable voice notification or 
tone

· 

Field selectable male voice with 
security message or female voice with 

safety message

Monitoring Outputs

· 

Armed mode

· 

Egress initiation status

· 

Released status

Trigger Modes

· 

Egress alarm triggered by Push Bar

· 

Trigger input from external device 
field selectable (N/O or N/C)

Code Compliance

· 

IFC International fire Code

· 

IBC International Building Code

· 

NFPA 101 Life Safety Code

· 

NFPA 1 Uniform Fire Code

· 

California Building Code

· 

Field selectable automatic or manual power up after emergency release or power 
loss.  Use of manual power up complies with California Building Code (OSHPD) 

requirements.

· 

Choice of Mounting

· 

Recessed mounted

       (3 gang metal plaster ring included)

· 

Surface mounted with optional 3 
gang box (2-679-0641)

· 

Optional shroud (2-679-0642) to be 

used with (2-679-0641) surface box.

2-679-0630

WALL CONTROLLER

4500/4600

RIM MOUNT OR

VERTICAL ROD

EXIT DEVICES

NOTE: Hager 2908 Power Supply required

Application:

When unauthorized egress is initiated 4500 DE   

delays egress through the door

for 15 seconds (or 30 seconds).  Meanwhile,

the person exiting must wait while personnel

or security responds.  The door unlocks after

15 seconds have elapsed permitting egress.

When powered by a fire control supervised

power supply, the lock will release

immediately in an emergency.

SYSTEM SPECIFICATIONS

INPUT VOLTAGE

INPUT VOLTAGE

MAX CURRENT DRAW

(SINGLE)

430mA @ 24 VDC

(TANDEM)

680mA @ 24 VDC

MONITOR RELAYS

CONTACT RATING

1 AMP @ 12/24 VDC

(RESISTIVE)

TEMPERATURE

o

0  C – 70  C

o

Page 1 of 7

Содержание 2-679-0630

Страница 1: ...th security message or female voice with safety message Monitoring Outputs Armed mode Egress initiation status Released status Trigger Modes Egress alarm triggered by Push Bar Trigger input from external device field selectable N O or N C Code Compliance IFC International fire Code IBC International Building Code NFPA 101 Life Safety Code NFPA 1 Uniform Fire Code California Building Code Field sel...

Страница 2: ...screws supplied RECESSED DRY WALL MOUNTING KEY CYLINDER INSTALLATION WITH KEY CYLINDER IN PROPER POSITION INSIDE SWITCH BLOCK TIGHTEN THE SET SCREW TO LOCK CYLINDER IN PLACE 1 1 4 KEY CYLINDER REQUIRES COLLAR 3 3 4 1 Cut hole in dry wall to dimensions shown 2 Mount wall bracket over hole 3 Carefully insert unit and secure with screws supplied 5 3 4 PUSHUNTILALARM SOUNDS DOORCANBE OPENEDIN15SECONDS...

Страница 3: ...R COMPANIES 139 Victor Street St Louis MO 63104 800 325 9995 RECOMMENDED MOUNTING PROCEDURE WIRE UNIT AS SHOWN SHOWN WITH NO OPTIONS SLIDE PACKING FOAM BETWEEN WALL AND UNIT TO PREVENT DAMAGE TO FACEPLATE USE 1 1 4 SCREWS SUPPLIED WITH WALL MOUNT FRAME TO HANG UNIT TEMPORARILY FOR WIRING PURPOSES W H T W H T R E D B L K TO PANIC DEVICE FROM POWER SUPPLY Page 3 of 7 ...

Страница 4: ...15 20 30 1 N C N O UNLOCKED LOCKED VOICE TONE TONE ONLY FEMALE MSG MALE MSG ON DELAY TIME ON OFF 1 2 3 4 5 6 7 8 NUISANCE DELAY REX PERIOD TRIGGER TYPE PWR UP STATE ALARM TYPE MESSAGE JUMPER J1 PWR LOCK RED R NO C TRIG REX RESET C NO C NO C NO To Power Supply TANDEM UNIT PAIR OF DOORS WHT WHT BLK RED WHT WHT BLK RED POWER TRANSFER HINGE POWER TRANSFER HINGE DPS DPS To Power Supply PWR LOCK RED R N...

Страница 5: ...ypad 00 00 The door is unlocked and has been opened ALARMED UNLOCKED Alternating Display The door is unlocked and the alarm is sounding To return to Armed Mode close the door and turn the key to Reset or enter the Reset Code 11 on the keypad BYPASS Extended Unlock Green LED Flashing Door Closed Door has been opened Keypad Code 33 The door is unlocked indefinitely To return to Armed Mode turn the k...

Страница 6: ...t programming mode YELLOW Keypad is in Programming Mode For ADA requirements it will light each time a key is pressed Slow Flash Single Flash Adding a User Changing User Pin Codes Option 1 To add a user 1 Enter Programming Mode 2 Press 1 User Number 2 digits New Pin Code Output Code For example 99 1234 1 05 55 2 adds user 5 s pin code 55 as one that will activate authorized exit 3 Exit Programming...

Страница 7: ...gramming Steps 1 Test the controller to verify that all default codes are working as expected 2 Record all desired users names and PIN codes in the table below 3 Enter programming mode 4 Delete all default users using the Delete All Users option on page 6 5 Change the Master Code to the desired Master Code 6 Exit programming mode 7 Enter programming mode using the new Master Code to test it 8 Add ...

Отзывы: