Esento Marine 2-4 Installation, Commissioning & Operating Manual
Approved Document UI-ESEN4MAR-01 Issue 6.0
18
SETUP & PROGRAMMING
1
1
1
4
Select sounder resound options for zones.
By default, after an initial fire condition and the (blue) Silence Alarms button has been activated, any new
fire condition in a different zone will cause the alarms to resound.
It is possible to change this on a zonal basis so that any new alarm in a different zone will not resound the
alarms.
Enter the above code and press the ENTER button. The Sounder Status LED will pulse slowly. Zone Fault
LEDs will show their current status (see below) with Zone 1 pulsing to indicate it is under selection.
Use Button 1 (Disable Mode) to move to the zone for programming (indicated by a pulsing LED) and press
the ENTER button to change the status. Pressing the ENTER button again will toggle the status, indicated
by a rapid or slow pulsing LED (see below). Then use Button 1 to move to the next zone. If the zone has
been set to not resound alarms, the LED will be off. If kept as default, new fire condition will resound
alarms, then the LED will be on steady.
Rapid Pulse
= Zone is under selection and is set to have alarms resound (default).
Slow Pulse
= Zone is under selection and has been set to not resound alarms on new fire condition.
LED Off
= Zone has been set to not resound alarms on new fire condition.
LED On
= Zone is set to have alarms resound (default).
RESOUND
SILENCE
RESET
ENTER
1
2
3
4
Disable
Mode
Test
Mode
Mute
Buzzer
Test
Lamps
RESOUND
SILENCE
RESET
ENTER
1
2
3
4
Disable
Mode
Test
Mode
Mute
Buzzer
Test
Lamps
When finished, press and hold Button 1 (Disable Mode) for 3 seconds or alternatively wait approx 10
seconds and the panel will save the settings and revert back to Level 3 access mode.
Enter the next programming code or disable the controls and return DIL switch 3 to ‘OFF’.
Содержание ESENTO MARINE
Страница 44: ...www haes tech com ...