Esento Marine 2-4 Installation, Commissioning & Operating Manual
Approved Document UI-ESENMAR-01 Issue 6.0
17
SETUP & PROGRAMMING
OPTION 3
. Inhibit Muted Tone Beeps
With the zone 3 fire LED lit press the ENTER button. The zone 1 fire LED will pulse to indicate ‘edit mode’.
Press button 1 to light the zone 1 amber fault LED. - Beeps are now silenced.
OPTION 2
. Set Presence of Output Card
An output/relay card may be added to each control panel to provide additional common or zonal outputs.
The presence of the card must be setup to enable operation.
With the zone 2 fire LED lit, the amber, fault LED (zone 1) will show the current setting.
Zone 1 amber fault LED ON = Output Card present.
Press the ENTER button, zone 1 fire LED will pulse to indicate adding or removing the card.
Then use button 2 to add or remove the card, indicated by the amber fault LED ON (added) or OFF
(removed).
When finished press the ENTER button again and the zone 2 fire LED will return to steady ‘view mode’.
Press button 1 to move to next option or hold button 1 for 3 seconds to exit programming mode 2-1-2-3.
OPTION 4.
UPS Mode / Disable Battery Monitoring (EN54!) & Disable Battery Hi Z Monitoring (EN54!)
The battery monitoring may be disabled for applications where this is appropriate such as non fire alarm
use or where no battery backup is required.
Note: There is no remote PSU fault input available on the
panel.
This is also known as ‘UPS Mode’ where the panel is supplied from a local 24v supply rather than
mains and intenal batteries.
With the zone 4 fire LED lit, the amber, fault LEDs will show the current setting.
Press the ENTER button, zone 1 fire LED will pulse to indicate ‘edit mode’ for std battery monitoring.
Use button 1 to toggle between pulsing fire LEDs 1 & 2 for editing std or Hi Z battery monitoring as per
above.
Now use button 2 to change the setting indicated by the amber fault LED as per above.
When finished press the ENTER button again and the zone 4 fire LED will return to steady ‘view mode’.
Press button 1 to move to next option or hold button 1 for 3 seconds to exit programming mode 2-1-2-3.
Note:
When batteries are unmonitored the input 24v dc voltage may vary between 20v dc & 32v dc.
FAULT LED 1
FAULT LED 2
SETTINGS
OFF
ON
Battery & Hi Z monitoring normal (default)
ON
ON
Battery & Hi Z monitoring both ‘OFF’ (UPS mode)
ON
OFF
Battery & Hi Z monitoring both ‘OFF’ (UPS mode)
OFF
OFF
Battery monitoring ‘ON’, Hi Z monitoring ‘OFF’