Esento Marine 8-12 Installation, Commissioning & Operating Manual
Approved Document Ref: UI-ESEN12MAR-01 Issue 8.0
31
SETUP & PROGRAMMING
Fire LED
(pulsing)
LED 1
LED 2
LED 3
LED 4
LED 5
LED 6
LED 7
LED 8
LED 9
Attribute
Fire
latching
Short
circuit as
fire
I.S
operation
Silent
mode
Priority
alarm
Detector
removal
monitoring
Zener
diode
detector
bases
Gate valve
& fire
pump (see
over page)
Delayed
(info only)
Amber
fault LED
(default
setting)
ON
OFF
OFF
OFF
ON
ON
OFF
OFF
OFF
RESOUND
SILENCE
RESET
ENTER
1
2
3
4
Disable
Mode
Test
Mode
Mute
Buzzer
Test
Lamps
Enter the code
3 1 2 1
and press the ENTER button.
The zone 1 fire LED will light. This indicates setting zone function attributes for zone 1. The amber, fault
LEDs will show the current settings for that zone.
Use button 1 to move to the zone that requires editing.
With the required zone for editing LED lit, press the ENTER button to enter ‘editing mode’.
The fire zone 1 LED will now pulse to indicate the editing of
attribute 1 (fire latching) for the selected zone.
Use button 1 to scroll to the attribute that requires editing,
inidicated by a pulsing fire LED 1 - 9 as per table below.
The setting of the attribute is indicated by the amber, fault LED,
ON or OFF.
Use button 2 to switch the attribute ON or OFF, indicated by the amber, fault LED, then use button 1 to
move to the next attribute if required.
Press the ENTER button to return back to the zone selection, indicated
by a steady zone fire LED
RESOUND
SILENCE
RESET
ENTER
1
2
3
4
Disable
Mode
Test
Mode
Mute
Buzzer
Test
Lamps
RESOUND
SILENCE
RESET
ENTER
1
2
3
4
Disable
Mode
Test
Mode
Mute
Buzzer
Test
Lamps
RESOUND
SILENCE
RESET
ENTER
1
2
3
4
Disable
Mode
Test
Mode
Mute
Buzzer
Test
Lamps
RESOUND
SILENCE
RESET
ENTER
1
2
3
4
Disable
Mode
Test
Mode
Mute
Buzzer
Test
Lamps
When finished all the zone function programming, enter the next programming code or disable the controls
and return DIL switch 6 to ‘OFF’.