Esento Marine 8-12 Installation, Commissioning & Operating Manual

Approved Document Ref: UI-ESEN12MAR-01 Issue 8.0

19

SETUP & PROGRAMMING

PROGRAMMING OPTIONS INDEX

Option/Setting

Description

Code(s)

Page

View History

View the last 40 events

1111

20

Set Fault Buzzer Volume

Set the fault buzzer volume to high or low

2224

21

Clear All Disablements

Remove all disablements which have been set for any zone, 

sounder circuit, output or delay

1121

21

Initialise Factory Settings

Restores all programming, test modes and disablements back to 

factory default settings

1113

21

Muster Alarm Signal / VDR card

Set zones and RESOUND button to activate a muster alarm, 
Muster alarm Synchronisation,Set presence of VDR card

1222

22

Panel Wide Settings

•  Change/remove keypad access code
• 

Set number of repeater panels on system

• 

Set time for panel delay timer

• 

Disable battery monitoring/UPS mode

• 

Setup internal PCB config (add/remove zone cards)

•  Change network/repeater comms monitoring type 
• 

Set number of output cards

• 

Inhibit muted tone beeps

• 

Inhibit network alarms & faults for panel

• 

Set number of network slave panels on system (Master Panel 
only)

• 

Inhibit network slave panel fire & fault buzzer

2123

24

Zone Function Settings

• 

Set zone to latching or non latching

• 

Set zone to old B.S (short circuit = fire)

• 

Set zone for use with MTL5061 I.S. barrier

• 

Set zone to silent mode (provides visual & audible indication at 
the panel but no sounder operation)

•  Turn off priority alarm feature for zone
•  Turn off detector removal monitoring for zone
• 

Set detector removal monitoring type for zone (Schottky or 
Zener diode detector bases)

3121

30

Dependancy Modes (False Alarm 
Management)

Set panel & zones to dependancy mode A, B or C

2124, 2114, 2134

32

EN54 Sounder Resound Options

Set zones to not resound alarms after an initial fire condition

1114

34

Delays to Outputs

Apply delays to outputs in response to selected zones

2323

35

Input Functions

Change the default functions of the Class Change and Alert inputs 4141

36

Output Programmability & 
Miscellaneous

Set panel outputs to be programmable, switch on fault latching, 

invert fault output

4142

37

Panel Output Zonal Responses

Set how each output and sounder circuit responds for each zone 
(off, continuous or pulsing)

4242, 4342

38

Panel Output Functional Options

Change the default panel output & sounder circuit responses to 
‘Silence Alarms’, ‘Evacuate’, ‘Class Change’, ‘Alert’ and ‘Delay’

4244, 4344

40

Network Output Responses

Set local output & relay responses to network fires

4224

42

Network Sounder Responses

Set local sounder cct responses to network fires

4324

43

Comms PCB Output Functional 

Options

Change the default comms PCB o/p responses to ‘Silence 
Alarms’, ‘Evacuate’, ‘Class Change’, ‘Alert’ and ‘Delay’

4343

44

System Diagnostics Mode

Tests system PCB config setup for fault diagnosis  

3114

45

Repeater Programming

Repeater panel setup & programming

4443

46

Содержание ESENTO ESEN-8MAR

Страница 1: ...Installation Commissioning Operating Manual MARINE APPROVED 8 12 ZONE CONVENTIONAL CONTROL PANEL Approved Document UI ESEN12MAR 01 Issue 8 0 MED Ref 0832 15...

Страница 2: ...ted by the manufacturer or distributors of this fire alarm panel for any misinterpretation of an instruction or guidance note or for the compliance of the system as a whole The manufacturer s policy i...

Страница 3: ...UIT SCHEMATIC 11 INSTALLATION 12 SAFETY 12 ESD PRECAUTIONS 13 GENERAL 13 MOUNTING THE CABINET 13 MAINS CONNECTIONS 14 CONNECTING THE BATTERIES 15 SETUP PROGRAMMING 16 NETWORK PANELS SETUP 16 LEVEL 3 E...

Страница 4: ...button keypad is used to control the system and allow access to the function options The three main buttons RESOUND red SILENCE blue and RESET green being much larger and colour coded to assist the e...

Страница 5: ...Esento Marine 8 12 Installation Commissioning Operating Manual Approved Document Ref UI ESEN12MAR 01 Issue 8 0 3 ABOUT THIS PANEL CABINET 60mm 85mm 310mm 455mm 300mm 450mm Fire Detection System...

Страница 6: ...CIRCUIT BOARDS Esento Marine 8 12 panels comprise of two main circuit boards plus optional ancillary boards PSU 28V 0V C NC NO C NC NO FIRE FAULT FR FLT CC PUL OP OP IP IP SNDR1 SNDR2 ZONE1 ZONE2 ZON...

Страница 7: ...3 4 5 6 1 2 3 4 ON ADDRESS ZONE A ZONE B ZONE C ZONE D 1 2 3 4 ON D C B A TWIN OPA OPB AUX SNDR A SNDR B C NO TPCA04 S Std spec 4 zone extension card TPCA05 Comms PCB TPCA04 H High spec 4 zone extensi...

Страница 8: ...sed Max 3A 30vdc Commmon fault VFCO relay maintained fail safe unfused Max 3A 30vdc Programmable O P Programmable O P Alert pulses sounders Precint class change activates sounders Switched ve inputs S...

Страница 9: ...A SNDR B C NO Conventionalfire zone circuits fused 500mA Relay Coil Relay Coil Programmable O P Programmable O P Programmable relay O P unfused Max 3A 30vdc 28v 28v Switched ve outputs Max load 40mA...

Страница 10: ...Monitoring current limit 28mA fused 500mA Typical max load 22 devices 18mA each per circuit Ensure 2 4A is not exceeded Zone 1 4 Conventionally wired fire alarm zone circuits 4K7 Ohm 5 0 25W EOL resi...

Страница 11: ...imum load shared between outputs 2 4A Power supply output voltage 21 27 29 68vdc Tolerance 0 1 Max continuous load ImaxA Max continuous load whilst battery charging is not required ImaxB ImaxA 610mA I...

Страница 12: ...Esento Marine 8 12 Installation Commissioning Operating Manual Approved Document Ref UI ESEN12MAR 01 Issue 8 0 10 DESIGN CONSIDERATIONS GENERAL DETECTION CIRCUIT SCHEMATIC...

Страница 13: ...ved Document Ref UI ESEN12MAR 01 Issue 8 0 11 DESIGN CONSIDERATIONS GENERAL SOUNDER CIRCUIT SCHEMATIC 4K7 OHM END OF LINE RESISTOR SNDR1 MOTORISED BELL POLARISED MOTORISED BELL POLARISED ELECTRONIC SO...

Страница 14: ...to take such steps as are necessary to ensure that any appropriate information about this product is made available by you to anyone concerned with its use This equipment is designed to be operated f...

Страница 15: ...ds used in the system must be suppressed to avoid damage to the control equipment The panel is only suitable for mounting in dry control rooms or dry accomodation spaces The site chosen for the locati...

Страница 16: ...outs provided A suitable cable gland must be used to secure the outer sheath of the cable used The earth must first be connected to the primary earth stud peg marked with a symbol using a suitable rin...

Страница 17: ...voltage will appear on the output leads or terminals due to intelligent battery controls b Check the power supply voltage at the 28v 0v supply output terminals With the batteries disconnected the vol...

Страница 18: ...n the top of the Comms PCB to re connect the display board ribbon cable Each panel to be included in the network is defined by setting switch 5 on the 6 way DIL switch located on the main circuit boar...

Страница 19: ...loop configuration from comms A to B and back to the Master panel again see drawing below This enables the network to still function if there is a break in the cables If replacing an older system wher...

Страница 20: ...signify that Level 3 access is active Programming throughout the panel is carried out in a sequence where the fire LEDs indicate the options to set and the fault LEDs indicate the status of these set...

Страница 21: ...one to silent mode provides visual audible indication at the panel but no sounder operation Turn off priority alarm feature for zone Turn off detector removal monitoring for zone Set detector removal...

Страница 22: ...ults If a sounder circuit fault is displayed pressing and holding the ENTER button will reveal which sounder circuit was at fault This is indicated by the fire LEDs 1 6 as per the table below Repeater...

Страница 23: ...3 seconds Any disabled zone sounder circuit output or delay will now be enabled The panel will bleep to acknowledge the reset When finished enter the next programming code or disable the controls and...

Страница 24: ...larm 3 for changing muster alarm priority or 4 for Muster Alarm Synchronisation LED 1 LED 2 LED 3 LED 4 LED 5 Select muster alarm zones Set RESOUND button Set muster alarm priority OFF Muster synch mo...

Страница 25: ...and exit programming mode Then enter next programming code or return DIL switch 6 to OFF position and disable controls 28V 0V C NC NO C NC NO FIRE FAULT FR FLT CC PUL OP OP IP IP 28V 0V C NC NO C NC N...

Страница 26: ...ls on system 11 Inhibit fire fault buzzer on network slave panel The keypad can be used to activate the panel controls instead of using the key switch The default code is 1 2 3 4 however this can be c...

Страница 27: ...ton 1 to move to next option or hold button 1 for 3 seconds to exit programming mode 2 1 2 3 The panel delay time for all outputs is set here To actually apply the delay to the desired outputs see pro...

Страница 28: ...rogramming mode 2 1 2 3 The control panel monitors all internal PCBs for correct function If adding or removing any of the additional extension zone cards the panel must be programmed for the new conf...

Страница 29: ...fire LED will pulse to indicate edit mode Now use button 2 to change the setting indicated by the amber fault LED ON or OFF as per above When finished press the ENTER button again and the zone 6 fire...

Страница 30: ...1 fault LED Beeps are now silenced When finished press the ENTER button again and the zone 7 fire LED will return to steady view mode Press button 1 to move to next option or hold button 1 for 3 seco...

Страница 31: ...to add or remove all 7 addresses in one go When finished press the ENTER button again and the zone 10 fire LED will return to steady view mode Press button 1 to move to next option or hold button 1 fo...

Страница 32: ...safe operation This option changes the zone alarm and short circuit thresholds to allow for an MTL 5561 type intrinsically safe barrier to be used in the circuit Silent mode This setting provides a vi...

Страница 33: ...press the ENTER button to enter editing mode The fire zone 1 LED will now pulse to indicate the editing of attribute 1 fire latching for the selected zone Use button 1 to scroll to the attribute that...

Страница 34: ...ints should be used on such zones to provide an instant un delayed alarm A 470 call point will be included in the dependency delay sequence Dependency B will apply the following sequence 1 The first d...

Страница 35: ...ED will change back to a slow pulse Press and hold button 1 for 3 seconds to save the settings and exit the programming mode There are two programmable timings for dependency mode B the confirmation t...

Страница 36: ...lse Zone is under selection and is set to have alarms resound default Slow Pulse Zone is under selection and has been set to not resound alarms on new fire condition LED Off Zone has been set to not r...

Страница 37: ...are to be delayed The choice toggles between all sounder circuits all aux outputs or all sounder circuits and all aux outputs The selection is indicated by the Sounder Status LED and the Aux Output St...

Страница 38: ...function of the CC input Use button 1 to move to zone 2 fire LED for setting the function of the PUL input and then back to zone 1 again The current setting for the input will be indicated by the ambe...

Страница 39: ...s constant and dissapears when a fault occurs for fail safe operation To set either of the two miscellaneous options above or to make outputs programmable enter the above code and press ENTER The fire...

Страница 40: ...fire LED 1 10 as per table below The setting of the output is indicated by the amber fault LED ON OFF or PULSING RESOUND SILENCE RESET ENTER 1 2 3 4 Disable Mode Test Mode Mute Buzzer Test Lamps RESO...

Страница 41: ...fire LED 1 6 as per table below The setting of the sounder circuit is indicated by the amber fault LED ON OFF or PULSING RESOUND SILENCE RESET ENTER 1 2 3 4 Disable Mode Test Mode Mute Buzzer Test La...

Страница 42: ...10 Fire Relay Main PCB Fault Relay Main PCB Fire O P Main PCB Fault O P Main PCB OPA Zone ext card 1 Zones 5 8 OPB Zone ext card 1 Zones 5 8 Aux Relay Zone ext card 1 Zones 5 8 OPA Zone ext card 2 Zon...

Страница 43: ...n cards with same custom reponses as above the process is exactly the same but using the code 4 3 4 4 I e Use button 1 to select the sounder circuit first indicated by a steady fire zone LED as per ta...

Страница 44: ...e required relay or output then use button 2 to change the response indicated by the amber fault LED Each press of button 2 will toggle through the 3 available responses RESOUND SILENCE RESET ENTER 1...

Страница 45: ...LEDs 1 6 respectively A pulsing red fire LED indicates which circuit is selected and the setting is represented by the amber fault LED as per table below Use button 1 to move the pulsing fire LED to t...

Страница 46: ...e above indicated by the amber fault LED ON Pulsing or OFF Then use button 1 to move to the next function if required Press the ENTER button to return back to the output selection indicated by a stead...

Страница 47: ...will display for 10 seconds and then the panel will automatically exit the diagnosis mode Pressing button 2 will reveal the origin of a system fault indication Note After power up the system should be...

Страница 48: ...ter panels on the system See panel wide settings 2 1 2 3 option 2 Set Number of Repeater Panels on System Addressing Each repeater panel needs to have a seperate address The addressing is done using t...

Страница 49: ...default o p 1 is set to activate on common fire and o p 2 is set to activate for common fault There are 4 programming options available for the inputs and outputs in the repeater panels Outputs 1 6 ac...

Страница 50: ...The use of a code entry to activate the controls is enabled by default but can be disabled in the Level 3 engineering functions To activate the controls using the key switch Turn the key clockwise to...

Страница 51: ...ode entries It can also be used for fault diagnosis see FAULT DIAGNOSIS section LED On LED Pulsing Zones in Fire 1 12 N A Indicates alarm condition in zone Zone Fault Disabled Test 1 12 Indicates zone...

Страница 52: ...LED and finally to the Delay LED Pressing the button once more will move the selection back to Zone 1 again When the desired circuit outputs or delays to be disabled is indicated by a slow pulsing LE...

Страница 53: ...Pressing the button once more will move the selection back to Zone 1 again When the desired zone to be tested is indicated by a slow pulsing LED use the ENTER button to select it Once selected the ind...

Страница 54: ...fter pressing ENTER LED Steady after pressing ENTER LED Off after pressing ENTER Location Zone 1 Fire LED off Sounder circuit 1 short circuit Sounder circuit 1 open circuit OK Main PCB SNDR 1 Zone 2 F...

Страница 55: ...re occurs alarm sounders and outputs will still function Main Board or zone extender boards System Fault LED continous and General Fault LED pulsing and continous buzzer sound Main board or extender c...

Страница 56: ...is no longer compliant with this part of BS 5839 THE NEED FOR MAINTENANCE ROUTINE MAINTENANCE TESTING DUTIES OF THE RESPONSIBLE PERSON The system user needs to appoint a single named member of the pr...

Страница 57: ...s would normally be a qualified electrical contractor or fire alarm specialist Inspection servicing visits are normally conducted on a quarterly basis unless such factors as a dirty environment warran...

Страница 58: ...Y INITIALS OF TESTER TIME OF TEST SCHEDULE OF TESTING This Section To Be Used To Record ALL Weekly Tests Of The Fire Alarm System Esento Marine 8 12 Installation Commissioning Operating Manual Approve...

Страница 59: ...Y INITIALS OF TESTER TIME OF TEST SCHEDULE OF TESTING This Section To Be Used To Record ALL Weekly Tests Of The Fire Alarm System Esento Marine 8 12 Installation Commissioning Operating Manual Approve...

Страница 60: ...Y INITIALS OF TESTER TIME OF TEST SCHEDULE OF TESTING This Section To Be Used To Record ALL Weekly Tests Of The Fire Alarm System Esento Marine 8 12 Installation Commissioning Operating Manual Approve...

Страница 61: ...Y INITIALS OF TESTER TIME OF TEST SCHEDULE OF TESTING This Section To Be Used To Record ALL Weekly Tests Of The Fire Alarm System Esento Marine 8 12 Installation Commissioning Operating Manual Approve...

Страница 62: ...AULTS ENGINEERS VISITS Esento Marine 8 12 Installation Commissioning Operating Manual Approved Document Ref UI ESEN12MAR 01 Issue 8 0 60 Fault Reason For Call Out Action Taken Date Work Completed Engi...

Страница 63: ...AULTS ENGINEERS VISITS Esento Marine 8 12 Installation Commissioning Operating Manual Approved Document Ref UI ESEN12MAR 01 Issue 8 0 61 Fault Reason For Call Out Action Taken Date Work Completed Engi...

Страница 64: ...AULTS ENGINEERS VISITS Esento Marine 8 12 Installation Commissioning Operating Manual Approved Document Ref UI ESEN12MAR 01 Issue 8 0 62 Fault Reason For Call Out Action Taken Date Work Completed Engi...

Страница 65: ...RATING section and press the blue SILENCE ALARMS button fig 1 To sound the alarms again press the red RESOUND button fig 2 4 In the event of a false alarm look for the device that has caused the alarm...

Страница 66: ......

Страница 67: ......

Страница 68: ...www haes tech com...

Отзывы: