Esento Marine 8-12 Installation, Commissioning & Operating Manual
Approved Document Ref: UI-ESEN12MAR-01 Issue 8.0
27
SETUP & PROGRAMMING
OPTION 6.
Change Network/Repeater Comms Monitoring Type (EN54!)
The network & repeater panels are designed to be wired in a fault tolerant (fail safe) loop configuration,
from comms A to B and back to the main panel again. This enables network & repeater panels to still work
if there is a break in the cables.
If replacing an older system where the existing cabling cannot be configured in a loop as above, it is
possible to change the panel back to radial circuit comms monitoring.
With the zone 6 fire LED lit, the amber, fault LED will show the current setting.
LED 1 OFF = fault tolerant monitoring (default). LED 1 ON = legacy, radial circuit monitoring.
Press the ENTER button, zone 6 fire LED will pulse to indicate ‘edit mode’.
Now use button 2 to change the setting indicated by the amber fault LED ON or OFF as per above.
When finished press the ENTER button again and the zone 6 fire LED will return to steady ‘view mode’.
Press button 1 to move to next option or hold button 1 for 3 seconds to exit programming mode 2-1-2-3.
RESOUND
SILENCE
RESET
ENTER
1
2
3
4
Disable
Mode
Test
Mode
Mute
Buzzer
Test
Lamps
RESOUND
SILENCE
RESET
ENTER
1
2
3
4
Disable
Mode
Test
Mode
Mute
Buzzer
Test
Lamps
COMS A COMS B 28
V+
SW -ve OUTPUTS
+ - + -
1
2
3
4
5
6
1
2
3
4
ON
ADDRESS
COMS A COMS B 28
V+
SW -ve OUTPUTS
+ - + -
1
2
3
4
5
6
1
2
3
4
ON
ADDRESS
COMS A COMS B 28
V+
SW -ve OUTPUTS
+ - + -
1
2
3
4
5
6
1
2
3
4
ON
ADDRESS
Radial/Legacy Wiring
Main Panel
Repeater/Network Panel 1
Repeater/Network Panel 2
120Ω
120Ω
Note:
When using legacy mode, comms connections should be made from ‘Comms-A’ to ‘Comms-A’.
If linking onto further units double up in Comms-A. I.e. do not use ‘Comms-B’ in legacy radial circuit
monitoring. See diagram below.