Table 4 RTC105 N/DN-module, LXV408.99.20101, 1-channel (continued)
Module
Name
Terminal Signal
Channel Function
1-fold analog input
KL3011 1(+) 2(-)
0/4 to 20 mA 1
Optional: Flow rate to biological treatment
Bus end terminal
KL9010
—
—
—
Bus termination
Table 5 RTC105 N/DN-module, LXV408.99.20111, 2-channels
Module
Name
Terminal Signal
Channel Function
4-fold digital output KL2134 1
+24 V/0 V
1
Nitrification/denitrification
5
+24 V/0 V
1
RTC channel 1 operating (24 V), RTC
defective (0 V)
4
+24 V/0 V
2
Nitrification/denitrification
8
+24 V/0 V
2
RTC channel 2 operating (24 V), RTC
defective (0 V)
1-fold analog input
KL3011 1(+) 2(-)
0/4 to 20 mA 1
Optional: Flow rate to biological treatment
Bus end terminal
KL9010
—
—
—
Bus termination
Table 6 RTC105 N/DN-module with O
2
step control, LXV408.99.21101,1-channel
Module
Name
Terminal Signal
Channel Function
8-fold digital output KL2408 1
+24 V/0 V
1
Nitrification/denitrification
5
+24 V/0 V
1
Aeration step 2 ON/OFF
2
+24 V/0 V
1
Aeration step 4 ON/OFF
6
+24 V/0 V
1
Aeration step 6 ON/OFF
3
+24 V/0 V
1
Aeration step 1 ON/OFF
7
+24 V/0 V
1
Aeration step 3 ON/OFF
4
+24 V/0 V
1
Aeration step 5 ON/OFF
8
+24 V/0 V
1
RTC operating (24 V), RTC defective (0 V)
1-fold analog input
KL3011 1(+) 2(-)
0/4 to 20 mA 1
Optional: Flow rate to biological treatment
Bus end terminal
KL9010
—
—
—
Bus termination
English
9
Содержание RTC105
Страница 503: ......