![Hach RTC105 Скачать руководство пользователя страница 19](http://html1.mh-extra.com/html/hach/rtc105/rtc105_basic-user-manual_576768019.webp)
Table 20 RTC113 ST-module, LXV412.99.00111, 2-channels (continued)
Module
Name
Terminal Signal
Channel Function
2-fold analog output KL4012 1(+) 3(-)
0/4 to 20 mA
2
Set point of the polymer flow rate
5(+) 7(-)
0/4 to 20 mA
2
Set point of the feed flow rate
1-fold analog input
KL3011 1(+) 2(-)
0/4 to 20 mA
1
Input of the feed flow rate
1-fold analog input
KL3011 1(+) 2(-)
0/4 to 20 mA
1
Input of the polymer flow rate
1-fold analog input
KL3011 1(+) 2(-)
0/4 to 20 mA
2
Input of the feed flow rate
1-fold analog input
KL3011 1(+) 2(-)
0/4 to 20 mA
2
Input of the polymer flow rate
Bus end terminal
KL9010
—
—
—
Bus termination
Startup
User interface and navigation
Keypad description
for the keypad description and navigation information.
Figure 3 Keypad description
1
Enter: Saves the setting and exits the current
screen to the CONFIGURE menu
4
Delete: Removes a sensor from the selection
2
Cancel: Exits the current screen to the
CONFIGURE menu without saving the setting
5
UP and DOWN arrows: Moves the sensors up or
down the list
3
Add: Adds a new sensor to the selection
Add a sensor
Note: Make sure that an RTC communication card is installed in the sc1000 sensor module.
1.
Connect the controller. Refer to the controller documentation.
2.
Select MAIN MENU>RTC MODULES/PROGNOSYS>RTC
MODULES>RTC>CONFIGURE>SELECT SENSOR.
3.
Push
Add
. Refer to
A list with all network connections shows.
4.
Select the applicable sensor for the RTC module and push
Enter
. The sensor is shown in the
sensor list.
Note: The sensor names in black are available for an RTC module. The sensor names in red are not available
for an RTC module. A sensor name identified with a "(p)" is available for PROGNOSYS.