![Hach RTC105 Скачать руководство пользователя страница 25](http://html1.mh-extra.com/html/hach/rtc105/rtc105_basic-user-manual_576768025.webp)
Table 31 RTC111 SRT-module (1-channel)
Tag name
Parameter Unit
Channel Description
MEASUREMENT 1 Qeff 1
L/s
1
Effluent flow as supplied to the RTC.
MEASUREMENT 2 Qsas 1
L/s
1
Surplus activated sludge flow
MEASUREMENT 3 Qsasm 1
kg/h
1
Sludge mass flow in surplus start sludge
MEASUREMENT 4 Vol 1
m
3
1
Actually aerated volume
MEASUREMENT 5 Vols 1
m
3
1
Averaged aerated volume during past sludge retention
time.
MEASUREMENT 6 TSmL 1
g/L
1
Averaged TS concentration in aeration basins during past
sludge retention time.
MEASUREMENT 7 TSs s1
kg
1
Mass of sludge in aeration basins, averaged for past
sludge retention time.
MEASUREMENT 8 SRT 1
days
1
Calculated actual aerobic sludge retention time
ACTUAT VAR 9
SRTSP 1
days
1
Set point for aerobic sludge retention time
ACTUAT VAR 10
Qs c1
L/s
1
Theoretical flow set point for surplus start sludge flow
ACTUAT VAR 11
Qs 1
L/s
1
Effective set point for surplus activated sludge flow
including all preset limits.
ACTUAT VAR 12
Digi 1
no unit 1
Surplus activated sludge pump ON/OFF signal
ACTUAT VAR 13
msaSP 1
kg/d
1
Set point for sludge mass draw off.
ACTUAT VAR 14
msasd 1
kg/d
1
Surplus activated sludge mass draw off during last
24 hours.
ACTUAT VAR 15
msash 1
kg/h
1
Actual surplus activated sludge mass draw off.
ACTUAT VAR 16
msas 1
kg
1
Surplus activated sludge mass draw off during actual
calendar day.
Table 32 RTC111 SRT-module (2-channels)
Tag name
Parameter Unit
Channel Description
MEASUREMENT 1 Qeff 1
L/s
1
Effluent flow as supplied to the RTC.
MEASUREMENT 2 Qsas 1
L/s
1
Surplus activated sludge flow
MEASUREMENT 3 SRT 1
days
1
Calculated actual aerobic sludge retention time
MEASUREMENT 4 Qeff 2
L/s
2
Effluent flow as supplied to the RTC.
MEASUREMENT 5 Qsas 2
L/s
2
Surplus activated sludge flow
MEASUREMENT 6 SRT 2
days
2
Calculated actual aerobic sludge retention time
ACTUAT VAR 7
SRTSP 1
days
1
Set point for aerobic sludge retention time
ACTUAT VAR 8
Qs 1
L/s
1
Effective set point for surplus activated sludge flow
including all preset limits.
ACTUAT VAR 9
Digi 1
no unit 1
Surplus activated sludge pump ON/OFF signal
ACTUAT VAR 10
msaSP 1
kg/d
1
Set point for sludge mass draw off.
ACTUAT VAR 11
msas 1
kg
1
Surplus activated sludge mass draw off during actual
calendar day.
ACTUAT VAR 12
SRTSP 2
days
2
Set point for aerobic sludge retention time