2-9
Chassis dimensions and rack requirements
Figure2-7 S6116-48X chassis dimensions with the front mounting brackets installed at the
port side
(1) Power supply handle
(2) Front mounting bracket
Figure2-8 S6116-48X chassis dimensions with the front mounting brackets installed at the
power supply side
(1) Power supply handle
(2) Front mounting bracket
Follow these guidelines when you install the switch in a 19-inch rack:
•
The distance between the front and rear posts of the rack must meet the requirements
described in
•
To secure the switch to the rack, you must install not only front mounting brackets, but also slide
rails or rack-mount rail kit.
Table2-3 Rack requirements
Chassis
dimensions
Installation method
Distance
between the
front and rear
rack posts
Rack depth requirement
•
Height
—44 mm
(1.73 in) (1 RU)
•
Width
—440 mm
(17.32 in).
•
Total depth
—425
mm (16.73 in)
25 mm (0.98 in)
for the power
supply or fan
tray handle
400 mm (15.75
in) for the
chassis.
Front mounting brackets
at the port side
Rear mounting brackets
with the wide flange
inside the rack
372 to 536 mm
(14.65 to 21.10 in)
To ensure that the rack door
can be closed easily after
cables are connected, make
sure the rack meets the
following requirements:
•
A minimum of 800 mm
(31.50 in) in depth
(recommended).
•
A minimum of 130 mm
(5.12 in) from the front
rack post to the front door.
•
A minimum of 153 mm
(6.02 in) from the rear rack
post to the interior side of
the rear door.
Front mounting brackets
at the power supply side
Rear mounting brackets
with the wide flange
inside the rack
372 to 507 mm
(14.65 to 19.96 in)
Front mounting brackets
at the port side
Rear mounting brackets
with the wide flange
outside the rack
214 to 378 mm
(8.43 to 14.88 in)