programming
Important Note:
It is important to select the correct DIP switch position based on
BOTH
the model (first column) and the pipe
size (second column) shown in the table below.
FlowVis Model
Pipe Size
DIP Switch Position
1
2
3
4
FV-C; FV-C-L; FV-C-M-DN50
2” and DN50
ON
OFF
OFF
OFF
FV-C-S; FV-C-S-L
2”
ON
ON
OFF
OFF
FV-C; FV-C-L; FV-C-M-DN65
2.5”
ON
ON
ON
OFF
FV-C-S; FV-C-S-L
2.5”
ON
ON
ON
ON
FV-C-M-DN65-HF-S
DN65
OFF
ON
OFF
OFF
FV-3; FV-3-L; FV-C-M-DN80
3” and DN80
OFF
OFF
ON
OFF
FV-4; FV-4-L; FV-C-M-DN100
4” and DN100
OFF
OFF
OFF
ON
FV-6; FV-6-L; FV-C-M-DN150
6” and DN150
OFF
ON
OFF
ON
FV-8; FV-8-L; FV-C-M-DN200
8” and DN200
OFF
ON
ON
OFF
FV-C-15; FV-C-M-DN40
1.5” and DN40
OFF
ON
ON
ON
operation
After setting the DIP Switches to reflect the FlowVis model and Pipe Size employed in your application, the FlowVis Digital
is ready to use. No calibration or further settings are required. However, by default, the FlowVis Digital readout will display
the flow rate in US GPM and the Turnover Rate will show --- (indicating that this function is not activated). If you would like to
change the unit of measurement from US GPM to either LPM or m3/hr, and /or activate the pool Turnover Rate function, then it
will be necessary to access these functions as described in the Advanced Setup section.
Fig 2.9 (left)
The
default setting for
the DIP switches (all
switches set to the
OFF position).
Fig 3.0 (left)
DIP
switch number 1 set
to the ON position.