display features

The FlowVis Digital Display comprises certain standard features as well as user-defi ned parameters / adjustments. Standard 

features include a Digital and Bar Graph reading of the measured fl ow rate. The user has the option to program the Unit 

of Measurement to be displayed in either US GPM (default), LPM or M

3

/hour. The patent pending feature that displays the 

Turnover Rate is activated by the user during programming. The Displays format can also be programmed by the user to 

change its appearance under prescribed conditions, e.g., fl ash above or below a certain fl ow rate.

troubleshooting

FlowVis Digital has been designed to be an easy to install, accurate and reliable addition to the renowned FlowVis fl ow 

meter. However, should an unexpected problem occur, please refer to the following Troubleshooting Guide.

As always, please feel free to contact us with any questions or concerns. Tel: 888.635.0296

Graphical display 

of fl ow rate

Unit of measurement 

options: US GPM, 

LPM, m3/h

Digital readout of 

fl ow rate

Pool turnover rate 

in hours

H2fl ow Controls 

internal reference 

only

Observation

Solution

Digital Display not 

illuminated

•  Check Power Supply is plugged into its receptacle, if yes...

•  Check for 12 VDC power at terminals PSU+ and PSU- on rear of Display, if no voltage...

•  Check to see if wires from the Power Supply are securely terminated into the PSU+ and 

PSU- terminals, if yes...

•  Check to see if 120V power source is active. If yes, Power Supply needs to be replaced

Digital Display reads 

zero fl ow rate with pump 

running

•  Is Display illuminated? If yes...

•  Check to see if FlowVis is reading the expected fl ow. If yes...

•  Check to see if there is a blue fl ashing light on the sensor. If no...

•  Check sensor wiring and terminations into the rear of the Display - red wire to I input +, 

black wire to I input -, and green wire to COM. Is everything is secure and correct? If yes...

continued on next page

Содержание FLOWVIS

Страница 1: ...RTANT NOTE For the most up to date version of this manual please visit www h2flow net product literature English Rev 1 1 10 2019 www h2flow net Tel 888 635 0296 Toll Free OR 1 419 841 7774 International Operating Manual EN ...

Страница 2: ...ts Description 3 Compatibility 3 Safety Information 3 What s included 4 Dimensions 5 Installation 5 Wiring 6 Output 7 Programming 8 Operation 8 Advanced Setup 9 Auxiliary Relay 11 Display Features 13 Troubleshooting 13 Environmental 14 Standards Approvals 14 Specifications 15 Warranty 16 2 ...

Страница 3: ...dditional details relating to this can be found on Page 12 of the FlowVis Operating Manual Using the Advanced Setup features FlowVis Digital can be interfaced with other systems such as heaters chemical feeders and UV units so that they will only operate above a user defined flow rate When using this option it will be necessary to include the Auxiliary Interface Unit with your purchase compatibili...

Страница 4: ...ended length lid screws Fig 1 8 Optional extension cable if purchased Fig 1 9 For 1 5 2 2 5 FlowVis models New flapper with attached indicator arm with magnet Fig 2 0 For 3 and 4 FlowVis models Complete new lid assembly Fig 2 1 Optional Auxiliary Interface Unit Fig 1 0 FlowVis flow meter with pre installed sensor and cable Fig 1 1 120VAC to 12VDC Power Supply Fig 1 2 NEMA 4X enclosure with pre mou...

Страница 5: ...s you may have purchased and c close enough to a 120V receptacle to allow the power supply to connect d Connect the Power Supply low voltage 12VDC output to the Display e Connect the Sensor to the display using either the standard length cables provided or the extension cable if purchased Disclaimer The sensor to display cables MUST NOT be cut or spliced in any way Doing so will invalidate the Flo...

Страница 6: ...les you may have purchased and c close enough to a 120V receptacle to allow the power supply to connect e Connect the Power Supply low voltage 12VDC output to the Display f Connect the Sensor to the display using either the standard length cables provided or the extension cable if purchased g Plug in the Power Supply and ensure that the Digital Display illuminates and the blue light on the sensor ...

Страница 7: ...www h2flow net Tel 888 635 0296 Toll Free OR 1 419 841 7774 International 7 output 4 20 mA Auxiliary Relay Auxiliary Relay Connections Fig 2 6 Fig 2 7 Fig 2 8 ...

Страница 8: ...ON OFF ON FV 8 FV 8 L FV C M DN200 8 and DN200 OFF ON ON OFF FV C 15 FV C M DN40 1 5 and DN40 OFF ON ON ON operation After setting the DIP Switches to reflect the FlowVis model and Pipe Size employed in your application the FlowVis Digital is ready to use No calibration or further settings are required However by default the FlowVis Digital readout will display the flow rate in US GPM and the Turn...

Страница 9: ...m net A spare USB 2 0 port for later connection to the Display An internet connection Step 1 Download and install the Advanced Panel Display Configurator Software Launch an internet browser page and go to www h2flow net flowvis digital flow meter and locate the Configurator section either by click on the tab titled Configurator in the page header or by scrolling down the page to this section Click...

Страница 10: ... 10 advanced setup cont Step 2 Programming the advanced features of the FlowVis Digital Display Connect the Display to your PC using the Type A to Type B cable that was delivered with your FlowVis Digital Open the FlowVis Configurator Program to display the following screen ...

Страница 11: ...to see turbulence in the flow stream this may be caused by other equipment such as heaters filters or even simply other plumbing fittings such as tees or elbows Under such conditions it is advisable to set the sensitivity to its default value of Low meaning that the flow readings and any features related to that reading such as the Turnover Rate or the Visual Alarm are not too erratic in their rea...

Страница 12: ...ry Relay comprises two sets of double pol double throw dry contacts Both sets of contacts will operate at the same programmed flow rate as set in Step 5 above Each of the two sets of contacts has a normally open and a normally closed relay The normal state is the condition that the contacts are in before they are activated by the coil is energized by the programming value Please refer to the Auxil...

Страница 13: ...ing Troubleshooting Guide As always please feel free to contact us with any questions or concerns Tel 888 635 0296 Graphical display of flow rate Unit of measurement options US GPM LPM m3 h Digital readout of flow rate Pool turnover rate in hours H2flow Controls internal reference only Observation Solution Digital Display not illuminated Check Power Supply is plugged into its receptacle if yes Check ...

Страница 14: ... further guidance Turnover rate appears to be inaccurate The turnover rate is calculated by the programmed pool volume divided by the flow rate Perform a manual calculation as follows Pool Volume Flow Rate from FlowVis 60 Turnover rate in hours If this number is different to the value shown on the FlowVis Display reconnect your laptop and check that the pool volume has been accurately entered Exte...

Страница 15: ... Socket 25 feet 7 62M long Power Supply Power Connection Receptacle style Power Source 120 240VAC 0 5 Amps Power Output 12 VDC 1 0 Amps Low Voltage Cable Length 60 1 52M User Extendable Yes but polarity sensitive Auxiliary Relay Output Contacts Double Pole Double throw Form C Dry Contacts Contact Ratings 20A max Relay Coil 12VDC sourced and controlled by the Display Analog Output 4 20mA Scaled to ...

Страница 16: ...mpts of individuals other than H2flow Controls Inc staff to repair or service the product c damage has been caused by the improper use of the product including but not limited to the installation of a FlowVis unit using a chlorination system as described on page 4 of this manual Charges Under cover of this warranty H2flow Controls Inc will pay the carriage and insurance charges for the shipment of...

Отзывы: